Electromagnetic Flow Meter Modbus Communication

The L-MAG Electromagnetic Flowmeter Standard outlines the MODBUS communication protocol for electromagnetic flowmeters, detailing network structure, wiring, and RTU frame formats. It provides definitions for MODBUS registers, communication data analysis, and application examples, ensuring reliable data transmission in industrial settings. The document includes specific instructions for reading various flow parameters and configuring PLC addresses for effective integration.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views28 pages

Electromagnetic Flow Meter Modbus Communication

The L-MAG Electromagnetic Flowmeter Standard outlines the MODBUS communication protocol for electromagnetic flowmeters, detailing network structure, wiring, and RTU frame formats. It provides definitions for MODBUS registers, communication data analysis, and application examples, ensuring reliable data transmission in industrial settings. The document includes specific instructions for reading various flow parameters and configuring PLC addresses for effective integration.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

L-MAG Electromagnetic Flow meter Standard

MODBUS Communication Protocol

(Version number:LMAGMODRTUV77)

2012-10-1
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

目录
1. Introduction.......................................................................................................... - 3 -
2. L-mag network structure and wiring................................................................... - 3 -
3. RTU frame format of modbus protocol ............................................................... - 4 -
1) Master order frame structure ...................................................................... - 4 -
2) Slave response frame structure ................................................................... - 4 -
4. Code definition of MODBUS protocol order ...................................................... - 5 -
5. MODBUS register definition of electromagnetic flowmeter .............................. - 6 -
1) MODBUS register definition of electromagnetic flowmeter ...................... - 6 -
2) PLC address set illustration ......................................................................... - 6 -
6. Communication data analysis ............................................................................. - 8 -
1) Read instantaneous flow .............................................................................. - 8 -
2) Read instantaneous velocity ........................................................................ - 9 -
3) Read cumulative flow................................................................................. - 10 -
4) Read instantaneous flow unit .................................................................... - 11 -
5) Read the unit of the total amount of flow ................................................. - 11 -
6) Read alarm status....................................................................................... - 11 -
7. Application examples ......................................................................................... - 12 -
1) MODBUS example program with C ......................................................... - 12 -
2) Communication example of MODBUS debugging software MODUBS
poll……...…………………………………………………………………….- 14
-
3) Communication example of MODBUS debugging software modscan32..-15-
4) Communication example of “KingView 6.53”.......................................... - 18 -
5) Communication example of “力控 6.1”.................................................... - 22 -
6) MCGS communication example ............................................................... - 25 -

Remark: The routine of this protocol’s application example only provide reference.
Some parameters in the routine are different from the address definition of MODBUS

-1-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

register. Please subject to the address definition of MODBUS register.

-2-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

1. Introduction

L-mag electromagnetic flowmeter has the standard MODBUS communication


interface supporting baud rate 1200, 2400, 4800, 9600, 19200. Through MODBUS
communication network, host can collect instantaneous flow, instantaneous velocity
and accumulative flow.
L-mag electromagnetic flowmeter uses serial port parameters: 1 start bit, 8 data
bits, 1 stop bit, none parity bit.
L-mag electromagnetic flowmeter MODBUS communication port uses electric
isolation mode in physical structure. The isolation voltage is 1500V and it owns ESD
protection. Thus it can overcome various interferences from industrial scene to ensure
the reliability service of communication network.

2. L-mag network structure and wiring

L-mag electromagnetic flowmeter’s standard MODBUS communication network


is bus network. It can support 1-99 electromagnetic flowmeters to network
organization. As the farthest electromagnetic flowmeter in the network, it usually
needs a 120  matched termination resistor to connect the two ports of
communication wire in parallel. The standard communication connection media is
shielded twisted pair.

Resistor

Flow meter Flow meter Flow meter


#1 #2 #99

Figure-1 Electromagnetic flowmeter network structure


L-mag electromagnetic flowmeter communication wiring is shown in
electromagnetic flowmeter in detail.
-3-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

3. RTU frame format of modbus protocol

MODBUS protocol is a kind of master-slave communication. Every


communication is started from master and slave responds master’ order through
passing back data.
L-mag electromagnetic flowmeter uses the MODBUS RTU frame format
(hexadecimal format). Its frame format is shown in figure2.
1) Master order frame structure

Device Function Register Register


Start CRC Stop
address code address length

T1-T2-T3-T4 8Bits 8Bits 16Bits 16Bits 16Bits T1-T2-T3-T4

Fiture-2 Master RTU message frame


2) Slave response frame structure

Device Function
Start Data CRC Stop
address code

T1-T2-T3-T4 8Bits 8Bits n 8Bits 16Bits T1-T2-T3-T4

Figure-3 Slave RTU message frame

Remark:
 T1-T2-T3-T4 is start or stop frame. MODBUS protocol sets that every two
frames must have 3.5 char delay at least. It is shown in figure-4.

Figure-4 MODBUS frame interval


 Device address: It is electromagnetic flowmeter’s communication address. It
couldn’t have two same address in a network.
-4-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

 Function code: It is set by MODBUS protocol. L-mag electromagnetic


flowmeter uses the function code 4 which realize the collecting function
through reading input register.
 Register address and register number: The start address of register which
restore data. Register number is the number that is used to store data.
 Slave response data: Byte number and N bytes data.
They are all shown in MODBUS protocol in detail.

4. Code definition of MODBUS protocol order

Table-1
Function code name function

01 Read coil status reservation

02 Read input status reservation

03 Read holding registers reservation

read Electromagnetic Flowmeter


04 Read input register
real-time information

05 Strong set single coil reservation

06 Preset single register reservation

07 read abnormal status reservation

08 Loopback diagnostic check reservation

09 Program(only used for 484) reservation

10 Control exercise(only used for 484) reservation

11 Read events count reservation

12 Read communication events record reservation

13 Program(184/384 484 584) reservation

14 Inquire(184/384 484 584) reservation

15 Strong multi-coil set reservation

-5-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

5. MODBUS register definition of electromagnetic

flowmeter

1) MODBUS register definition of electromagnetic flowmeter

Table-2
Protocol
Protocol Addresses
Addresses Data format Resister definition
(HEX)
(Decimal)
Instantaneous flow
4112 0x1010 Float Inverse
float representation
Instantaneous velocity
4114 0x1012 Float Inverse
float representation
Float representation of the
flow percentage
4116 0x1014 Float Inverse
(reservation for
battery-powered
Floating representation of
4118 0x1016 Float Inverse
fluid conductivity ratio
Integer part of the cumulative
4120 0x1018 Long Inverse
positive value
Decimal part of the
4122 0x101A Float Inverse
cumulative positive value
Integer part of the cumulative
4124 0x101C Long Inverse
negative value
Decimal part of the
4126 0x101E Float Inverse
cumulative negative value
Instantaneous flow unit
4128 0x1020 Unsigned short
(table-3)
Cumulative total units
4129 0x1021 Unsigned short
(table-4 or table-5)

4130 0x1022 Unsigned short Upper limit alarm

4131 0x1023 Unsigned short Lower limit alarm


4132 0x1024 Unsigned short Empty pipe alarm
4133 0x1025 Unsigned short System alarm

2) PLC address set illustration

If there isn’t function code setting options when we configure PLC, you should

-6-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

add 3 in front of register address when you use function code 04. If PLC register
address’s basic address is from 1, you should add 1 to original address when
configuring register address.
Example: L-mag electromagnetic flowmeter MODBUS register address is
4112(0x1010) and MODBUS function code is 4. So PLC register address is 34113.
The detailed configuration is seen in example chapter 2.
3) Address configuration illustration of KingView software
There isn’t option of configuring function code. Different drivers have different
configuration methods.
Take PLC- Modicon-MODBUS (RTU) driver for a example. You should add 8 in
front of register address when using function code 04. KingView register address’s
basic address is 1, so the original address should be added 1 when configuring
KingView register address.
L-mag electromagnetic flowmeter MODBUS register address is 4112(0x1010)
and MODBUS function code is 4. So PLC register address is 84113.
The detailed configuration is seen in example chapter 4.
4) Illustration of data’s meaning
 Float format:
L-mag electromagnetic flowmeter MODBUS uses IEEE754 which is 32 bits
float format. Its structure is shown as follows: (take Instantaneous flow for a example)

0X1010(34113) 0x1011(34114)

BYTE1 BYTE2 BYTE3 BYTE4

S EEEEEEE E MMMMMMM MMMMMMMM MMMMMMMM

S- Mantissa symbol; 1=negative, 0=positive.


E- Exponent; expressed by the difference with decimal number 127.
M- Mantissa; low 23 bits and the decimal part.
When not all of the E is “0” and “1”, the conversion formula between float and
the decimal number is:

V  (1) S 2( E 127) (1  M )
-7-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

 Instantaneous flow unit


Code Unit Code Unit Code Unit Code Unit

0 L/S 3 M3/S 6 T/S 9 GPS

1 L/M 4 M3/M 7 T/M 10 GPM

2 L/H 5 M3/H 8 T/H 11 GPH

 Cumulative flow unit


Table 4 ( It is suit for B type and 511 type electromagnetic flowmeter converter)

Code 0 1 2 3

Cumulative unit L M3 T USG

Table 5 ( It is suit for C type electromagnetic flowmeter converter)

Code 0 1 2 3 4 5
Cumulative unit L L L M3 M3 M3
Code 6 7 8 9 10 11
Cumulative unit T T T USG USG USG

 Alarm
Upper limit alarm, lower limit alarm, empty pipe alarm, system alarm:
0 ------ No alarm; 1------ Alarm

6. Communication data analysis

Instantaneous flow, instantaneous velocity, flow percentage, fluid conductivity


ratio, decimal part of the cumulative positive and negative value, format conversion of
float, integer part of the cumulative positive and negative value, transmission of long.
1) Read instantaneous flow

Master sends command (hexadecimal number)


01 04 10 10 00 02 74 CE

Device Function Register Register Register Register CRC CRC


high high high low
address code high low
address address length length

-8-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

Data that master receives


01 04 04 C4 1C 60 00 2F 72

Device Function Data 4 bytes float CRC CRC


address code length (instantaneous flow) high low

Float: C4 1C 60 00
1100 0100 0001 1100 0110 0000 0000 0000
float byte 1 float byte 2 float byte 3 float byte 4
S=1: if mantissa symbol is 1, it is a negative.
E=10001000: Exponent is 136
M=001 1100 0110 0000 0000 0000, The mantissa is :
1 1 1 1 1
V  (1)1 2(136127) (1      )
8 16 32 512 1024
= -625.5
2) Read instantaneous velocity

Master sends command (hexadecimal number)


01 04 10 12 00 02 D5 0E

Device Function Register Register Register Register CRC CRC


high high high low
address code high low
address address length length

Data that master receives


01 04 04 C1 B0 80 00 A6 5F

Device Function Data 4 bytes float CRC CRC


address code length (instantaneous velocity) high low

Float: C1 B0 80 00
1100 0001 1011 0000 1111 1000 0000 0000
S=1
E= 10000011
M= 011 0000 1111 1000 0000 0000
1 1 1
V  (1)1 2(131127) (1    )
4 8 256
= -22.0625

-9-
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

3) Read cumulative flow

To express the 9 bits cumulative value of electromagnetic flowmeter totally,


integer part and decimal part of cumulative flow are expressed respectively. The
integer part uses long variable and the decimal uses float variable.
Cumulative flow is 1578m3
Master sends command to collect the integer value of cumulative flow
01 04 10 18 00 02 F5 0C

Device Function Register Register Register Register CRC CRC


high high high low
address code high low
address address length length

Data that master receives


01 04 04 00 00 70 71 1E 60

Device Function Data 4 bytes float CRC CRC


address code length (integer value of cumulative flow) high low

Integer value of cumulative flow is 28785


Master sends command to collect the decimal value of cumulative flow
01 04 10 1A 00 02 54 CC

Device Function Register Register Register Register CRC CRC


high high high low
address code high low
address address length length

Data that master receives


01 04 04 3F 00 00 00 3B 90

Device Function Data 4 bytes float CRC CRC


address code length (decimal value of cumulative flow) high low

Float: 3F 00 00 00
0011 1111 0000 0000 0000 0000 0000 0000
S=0
E= 0111111 126
M= 000 0000 0000 0000 0000 0000

V  (1)1 2(126127)  0.5

- 10 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

4) Read instantaneous flow unit

Master sends 8 bytes command to read instantaneous flow unit


01 04 10 20 00 01 34 C0

Device Function Register Register Register Register CRC CRC


high high high low
address code high low
address address length length

7 bytes data that master receives from slave


01 04 02 00 05 79 33

Device Function Data 2 bytes integer CRC CRC


address code length (instantaneous flow unit) high low

Flow unit is M3/H from table-3.


5) Read the unit of the total amount of flow

Master sends 8 bytes command to read instantaneous flow unit


01 04 10 21 00 01 65 00

Device Function Register Register Register Register CRC CRC


high high high low
address code high low
address address length length

7 bytes data that master receives from slave


01 04 02 00 01 78 F0

Device Function Data 2 bytes integer CRC CRC


address code length (cumulative flow unit) high low

Flow unit of B type and 511 type is M3 from table-4.


Flow unit of C type is L from table-5.
6) Read alarm status

Master sends 8 bytes command to read instantaneous flow unit


01 04 10 24 00 01 75 01

Device Function Register Register Register Register CRC CRC


high high high low
address code high low
address address length length

- 11 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

7 bytes data that master receives from slave


01 04 02 00 01 78 F0

Device Function Data 2 bytes integer CRC CRC


address code length (alarm) high low

Empty pipe is in alarm status if status is 1.


Other alarm status is the same and so on.

7. Application examples

1) MODBUS example program with C

 CRC16 algorithm:
INT16U CRC16(INT8U *puchMsg, INT16U usDataLen)
{
INT8U uchCRCHi = 0xFF; /* High CRC bytes initialization */
INT8U uchCRCLo = 0xFF; /* Low CRC bytes initialization */
INT8U uIndex; /* CRC index of the cycle */
while (usDataLen--) /* Message transmission buffer */
{
uIndex = uchCRCHi ^ *puchMsg++; /* calculate CRC */
uchCRCHi = uchCRCLo ^ auchCRCHi[uIndex];
uchCRCLo = auchCRCLo[uIndex];
}
return (uchCRCHi << 8 | uchCRCLo);
}

 Program of sending commands


This example is on the basis of that the core CPU is Mag64
void Read_InPut(INT8U Addr,INT16U Start,INT16U Len)
{
INT16U CRC;
SendBuffer_485[0]=Addr; //Device address
SendBuffer_485[1]=0x04; //MODBUS function code
SendBuffer_485[2]=Start/256; //Start is register address
SendBuffer_485[3]=Start%256;
SendBuffer_485[4]=Len/256; //Len is reading register length
SendBuffer_485[5]=Len%256;
CRC=CRC16(SendBuffer_485,6);
SendBuffer_485[6]=CRC/256; //CRC high bits
SendBuffer_485[7]=CRC%256; //CRC low bits
R485_OUT; //Enable RS485 to send data
SendLen_485=8;
- 12 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

SendNum_485=0;
CloseINT0(); //Close interrupt of serial port receiving data
UCSR0B |= BIT(UDRIE0); // Open interrupt of serial port sending data
}

 Analysis of the data return (take instantaneous flow as an example only)


Using serial port interrupt when receiving data. ReceivedBuffer_485 is received
data group. ReceivedNum_485 is received data length. ReceivedFlag_485 is data
symbol when it has received data. Function float Datasum(INT8U BYTE1, INT8U
BYTE2, INT8U BYTE3, INT8U BYTE4) changes 4 bytes float into a float.
float Datasum(INT8U FloatByte1, INT8U FloatByte2, INT8U FloatByte3, INT8U FloatByte4)
{
float aa;
union IntTOFP
{
FP32 F32;
INT8U T8[4];
};
union IntTOFP aa;
aa.T8[0] = FloatByte1;
aa.T8[1] = FloatByte2;
aa.T8[2] = FloatByte3;
aa.T8[3] = FloatByte4;
return aa;
}
void Read_Lmag(INT8U Ad)
{
INT8U i,j;
INT8U Num1[10],BIT;
INT16U CRC1,CRC2;
FP32 Flow; //aaa is instantaneous flow value
ReceivedFlag_485=1;
Open_Time1_Ms5(20);
Read_InPut(Ad,0x1010,2); //Send device address, register address and register length
while(ReceivedFlag_485); //Waiting receiving interrupt
if((ReceivedNum_485==9)&&(ReceivedBuffer_485[0]==Ad)) // Judge whether it is right
{
CRC1=CRC16(ReceivedBuffer_485,7);
CRC2=ReceivedBuffer_485[7]*256+ReceivedBuffer_485[8];
if(CRC1==CRC2)
{// Change data into float
Flow = Datasum(ReceivedBuffer_485[6], ReceivedBuffer_485[5],
ReceivedBuffer_485[4] ,ReceivedBuffer_485[3]);}}}
- 13 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

2) Communication example of MODBUS debugging software MODUBS


poll

Slave address is 1. Band rate is 9600. Read all of the real-time data. The setting
method is shown as follows.
As tabe-2 shows that start register address is 4113. Register number is 22.
i. Set collecting command including device address(1), MODBUS function
code(04), register address(4113), register length(2), sample interval(1000).

ii. Set serial port data


On the basis of L-mag electromagnetic flow meter serial port format( 1 start bit,
8 data bits, 1 stop bit, no parity bit), the detailed setting method is shown as follows.

- 14 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

iii. Set data presentation format

iv. Successful communication interface

- 15 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

3) Communication example of MODBUS debugging software modscan32

Slave address is 1. Band rate is 9600. Read all of the real-time data. The setting
method is shown as follows.
As tabe-2 shows that start register address is 4113. Register number is 22.
i. Set collecting command including device address(1), MODBUS function
code(04), register address(4113), register length(2), sample interval(1000).

ii. Set serial port data


On the basis of L-mag electromagnetic flowmeter serial port format( 1 start bit, 8
data bits, 1 stop bit, no parity bit), the detailed setting method is shown as follows.

iii. Set data’s presentation format

- 16 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

iv. Successful communication interface

- 17 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

4) Communication example of “KingView 6.53”

The 1st step:


Build kingview project

The 2nd step:


Add standard Modbus device , KingView device list-PLC-Modicon-modbus
(RTU)。

Set device address as the electromagnetic flowmeter’s address. Take address 1 as


an example

- 18 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

The 3rd step:Double click device’s COM to set serial parameters

L-mag electromagnetic flowmeter’s serial port parameters: Baud rate is the same
as electromagnetic flowmeter’s, 1 start bit, 8 data bits, 1 stop bit, no parity bit. Take
baud rate 9600 for an example.

The 4th step:Click data dictionary to add L-mag data variable


According to KingView drivers illustration: Modicon-modbus (RTU) variable
name, register address and data format. See table as follows:
Variable name Register value Data format Frequency property
Instantaneous flow 34113 Float 500 Read only
Instantaneous flow velocity 34115 Float 500 Read only
Flow percentage 34117 Float 500 Read only
Fluid conductivity ratio 34119 Float 500 Read only
Integer part of positive
34121 Long 500 Read only
cumulative value
Decimal part of positive
34123 Float 500 Read only
cumulative value
Integer part of reverse
34125 Long 500 Read only
cumulative value
Decimal part of reverse
34127 Float 500 Read only
cumulative value
Data transition register SwapL0 Byte 0 Write only

- 19 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

Note: For the data storage format of electromagnetic flowmeter, When


adding variable to KingView, the data transition register must be added. Or
communication data will present abnormally.

- 20 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

The 5th step:


Create the window and link the variable.

The 6th step:


Save modification and run project

- 21 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

5) Communication example of “力控 6.1”


The 1st step:
Build a project

The 2nd step:


IO port device configuration chooses IO device-Modbus- standard
Modbus-Modbus(RTU serial port)

Choose serial port

- 22 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

Set displaying data format

The 3rd step:


Database configuration

Set the data format and address offset

- 23 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

Data example

The 4th step:


Create the window and link the variable

The 5th step:


Run the project

- 24 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

6) MCGS communication example


Using guide:
The 1st step:
Create a project and it will appear window as follows. Then choose “设备窗口”,
double click it.

Choose “设备工具箱”. Click “设备管理” and then add “通用串口父设备” and


“标准 MODBUSRTU 设备” to project.

Choose “通用串口父设备 0” and “设备 0”.

- 25 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

Device’s address is 1. 32 bits float’s decoding order is 0-1234. Parity format is


0-LH [low bytes, high bytes]. Choose “设置内部属性”.

Click “添加通道”. Then appear:

Register address Data format Channel number Register definition

4113 32 bits float 1 Flow percentage

4115 32 bits float 1 Fluid conductivity ratio

4117 32 bits float 1 Integer part of positive


cumulative value
4119 32 bits float 1 Decimal part of positive
cumulative value
4121 32 bits unsigned binary 1 Integer part of reverse
number cumulative value
4123 32 bits float 1 Decimal part of reverse
cumulative value
4125 32 bits unsigned binary 1 Flow percentage
number
4127 32 bits float 1 Fluid conductivity ratio

- 26 -
L-MAG Electromagnetic Flowmeter Standard MODBUS Communication Protocol

Choose “通道连接”

Choose “设备调试”

- 27 -