0% found this document useful (0 votes)
39 views4 pages

Distributed Power Unit

The DPU240D-N40A1 is a versatile distributed Power Unit designed for communication sites, supporting various installation modes and capable of integrating with existing power systems. It features intelligent operations, high reliability with an IP55 protection level, and a wide operating temperature range. The unit can accommodate modular capacity expansion and is suitable for macro sites, remote sites, and enterprise telecom scenarios.

Uploaded by

Adolfo Lama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views4 pages

Distributed Power Unit

The DPU240D-N40A1 is a versatile distributed Power Unit designed for communication sites, supporting various installation modes and capable of integrating with existing power systems. It features intelligent operations, high reliability with an IP55 protection level, and a wide operating temperature range. The unit can accommodate modular capacity expansion and is suitable for macro sites, remote sites, and enterprise telecom scenarios.

Uploaded by

Adolfo Lama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Distributed Pow er Unit

DPU240D-N40A1 Datasheet

Introduction

DPU240D-N40A1 is a new generation distributed Power Unit which


designed for communicate sites. It can be used in Multi-frequency and
high-power scenarios, and supports pole-mounted, wall-mounted and so
on. It can be widely used for macro site, indoor distributed RRU/AAU and
remote site. Can be parallel with existing power system, backup battery
sharing, and power compensation to existing system. Enable existing
power system smoothly migrate to blade power

The DPU240D-N40A1 can be configured with 3 kW blade modules


DPU240D-N40A1
(DPU60R-N06A1) and a maximum of 4+1 redundant rectifier modules.
The power distribution module in the middle integrates power distribution
and monitoring. The circuit breakers can be replaced as required.

Features
⚫ Simple Deployment

• Fast installation, 1 hour by 2 person

• Flexible design: modular capacity expansion is supported.

⚫ Easy O&M

• Supports intelligent O&M based on NetEco


DPU240D-N40A1
• Fan-free design, free of maintenance PDU

⚫ Intelligent

• Intelligent Voltage boosting, peak shaving, peak staggering for independent use

• Intelligent metering, slicing, power off based on frequency for all scenario

⚫ High Reliability

• IP55 protection level, N+1 Backup , higher reliability

• wide working temperature range:-40℃ to +55℃

Note: Any datasheet issued previously is invalid when new version releases. Issue date of this version: 2021-08-25
Distributed Pow er Unit
DPU240D-N40A1 Datasheet

Scenarios

⚫ RRU/AAU remote site

⚫ Easy Macro Site

⚫ Existing power expansion with power parallel connection

⚫ Enterprise telecom scenario

Note: Any datasheet issued previously is invalid when new version releases. Issue date of this version: 2021-08-25
Specifications
Distributed Power Unit for DC Load Scenarios
Product Type DPU240D-N40A1
PDU Dimension (W×D×H) 170 mm × 300 mm × 420 mm

3kW PSU Dimension (W×D×H) 60 mm × 300 mm × 420 mm

Weight PDU ≈ 19 kg 3kW PSU ≈ 8 kg

Installation Mode Wall-mounted, pole-mounted, tower installation

Max 3kw Number 4+1(backup)

Cabling Mode Bottom inlet and outlet

Protection Level PDU IP55 3kW PSU IP65


System
−40℃ to +55℃ (without solar radiation)
Working Temperature
−40℃ to +50℃ (Natural environment with solar radiation)

Cooling Mode Natural heat dissipation

Operating Environment Class C*

Grid Environment 1st/ 2nd/ 3rd rate grid*

CE:EN55032 Class A
EMC
RE:EN55032 Class A

Certification CE/TUV/RCM/ Nine Countries* /FCC/IC.

Storage Temperature −40℃ to +75℃

Operating Humidity 5% to 95% (non-condensing)


Environment
-60 to 5000 m (From 2000~5000m, each 200m increases in altitude will decrease the
Altitude
working temperature by 1℃)

Power Input Mode Single phase /Dual-live wire /Three phase

Single phase/ Dual-live wire AC: 85V AC ~300V AC


Input Voltage
Three phase: 147V AC ~519V AC
Power Input
Input Frequency 45 Hz - 65 Hz

AC Input 63A×4P

AC SPD 20 kA/20 kA, 8/20 µs

Three-phase input:
• Phase voltage 176~290 V AC :12000 W
• Phase voltage 85 V~ 176 V AC : lining degrading to 6000 W
Max Output Power
Single-phase or dual-live-wire input:
• 176V ~290V AC : 9000 W
• 85 V ~ 176 V AC :lining degrading to 4500 W

Output Voltage -42V DC to -58V DC


Load Output -57V DC(used with DBU50B)
Rated output voltage
-54.5V DC (No lithium battery or battery not support 57V output)

DC Output Basic configuration: 6 x 63 A, 6 x 32 A, and expansion: 6 x 32 A

Battery Branch Maximum Support 3x125 A Quick plug terminals

DC SPD 10 kA/20 kA, 8/20 µs

Efficiency Maximum efficiency ≥97%

South (RJ45): 1 × CAN, 1 × RS485* (4 line)


North (RJ45):1 × RS485* (4 line) , 1 × FE
Communication
Interface Definition Dry contact : 4×DO (multiplex 2×DI,1×DI
Note: AnyInterface
datasheet issued previously is invalid when new version
MBUS releases. Issue date of this version: 2021-08-25
Wireless backhaul (4G modules required)

Security standards IEC/EN60950-1,IEC/EN60950-22,IEC/EN62368-1


Others
MBTF >400,000 小时(@25℃)
*Remark:

MBUS Communication: DPU supports in-band communication with 5th generation Huawei RRU.

Nine countries: Algeria, Saudi Arabia, Qatar, Egypt, Nigeria, Kuwait, Uganda, Botswana, and Tanzania
.

Grid classification standard:


1st rate grid: power outage < 10hrs per month; 2nd rate grid: power outage < 10hrs per week; 3rd rate grid: power outage 2-8hrs per day

Operating environment definitions:


Class C-Sea environments or outdoor land environments (with simple shielding measures) near pollution sources. If a site is near a pollution
source, it is at most 3.7 km away from salt water such as the sea and salt lakes, 3 km away from heavy pollution sources such as smelteries,
coal mines, and thermal power plants, 2 km away from medium pollution sources such as chemical, rubber, and galvanization industries, or 1
km away from light pollution sources such as packing houses, tanneries, and boiler rooms.
Class D-Environments within 500 m away from the seashore. Class D environments are special Class C environments

Copyright © Huawei Technologies Co., Ltd. 2021. All rights reserved. HUAWEI TECHNOLOGIES CO., LTD.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Industrial Base
Huawei Technologies Co., Ltd.
Bantian Longgang
General Disclaimer
Shenzhen 518129, P.R. China
The information in this document may contain predictive statements including, without limitation, statements regarding the
future financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could Tel: +86-755-28780808
cause actual results and developments to differ materially from those expressed or implied in the predictive statements.
www.huawei.com
Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

Note: Any datasheet issued previously is invalid when new version releases. Issue date of this version: 2021-08-25

You might also like