0% found this document useful (0 votes)
36 views4 pages

SLM Pro

The SLM PRO is a versatile electrical power meter with Class 0.5s accuracy for active energy and features a bright 7-segment display, harmonic measurement, and event logging for power quality analysis. It supports various installation types and provides comprehensive measurement capabilities, including import-export counters and demand measurement. The meter is designed for remote monitoring, energy management, and tenant billing, with communication support via MODBUS-RTU protocol over RS485.

Uploaded by

1kriteshverma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views4 pages

SLM Pro

The SLM PRO is a versatile electrical power meter with Class 0.5s accuracy for active energy and features a bright 7-segment display, harmonic measurement, and event logging for power quality analysis. It supports various installation types and provides comprehensive measurement capabilities, including import-export counters and demand measurement. The meter is designed for remote monitoring, energy management, and tenant billing, with communication support via MODBUS-RTU protocol over RS485.

Uploaded by

1kriteshverma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

SLM PRO

ELECTRICAL POWER METER

Class 0.5s accuracy for Active energy as per the IS14697.

4 digits X 3 rows bright 7-Segment display.

Compact 96 X 96 DIN Enclosure.

Computed Neutral Current.

Shows all three types of Power Factors – True , Displacement and Distortion.

Harmonic measurement: All six waveforms up to 30th order, even and odd, including THD.

Event logging of Sags, Swells and Interruptions as per IEC 61000-4-30.

Demand Measurement: Fixed or Sliding for KW, KVA, KVAR and Avg.Amps.

RUN Hour and ON Hour measurement.

Energy Pulse Output LED on the front – selectable for Real/Apparent/Reactive Energy.

3P4W, 3P3W and 1P2W connections.

Import – Export counters for all three energies and all Power Demands.

User selectable CT and PT Ratios. 5A or 1A operation, eld selectable.

Trinity introduces the SLM PRO, an easy-to-use, accurate and very versatile electrical power meter
with innovative features, which is ideal for remote monitoring of electrical installations, Energy
accounting and management, tenant billing and Power quality analysis.

The meter has three LEDs in the front, one to calibrate energies, one to indicate the status of RS485
communication and one to indicate conversion from kilo to mega. The display consists of three
rows of four-digit seven segment red LEDs of 0.56 inches. Twenty four LEDs in two columns on
either side of the display indicate the various parameters being shown.

It supports MODBUS-RTU protocol over RS485 port.


Installation and connection

The CT Primary and Secondary, PT Ratio and installation types are site selectable, thus
making it possible to use the meter in all types of installations like 3P4W, 3P3W and 1P2W.

Comprehensive Measurement

In addition to basic metering of the previous models , SLM PRO adds support for Import-
Export measurement on three energies and demands , logging of minimum-maximum
values, all three types of power factors like True , Displacement and Distortion , Phase angle
measurements, unbalance percentages and computed neutral current.

Power Quality Analysis as per IEC 61000-4-30 & IEC 61557-12

For Power Quality Analysis - SLM PRO measures individual harmonics for all voltage and
current waveforms, both even and odd, up to the 30th order, with THD as per IEC 61557-12.
It also records in it's non-volatile memory with date and time stamp, twenty Interruption
events and thirty SAG/SWELL events, as per IEC 61000-4-30 standard

Three Phases and Neutral of a 3P4W system /


Supply Three Phases of a 3P3W system / Single Phase
and Neutral of a 1P2W System

Direct Voltage Input : up to 500V L-L, 300V L-N

Voltage PT Ratio : Site Selectable

Burden : 0.5VA

Secondary Current Input : 5A or 1A


INPUT

(Site Selectable)
CT Primary : Site Selectable
Range of Reading : up to 5000A
Current Burden : < 1.0VA
Overload : 5A CT → 6A RMS
Continuous
: 1A CT → 1.2A RMS
Continuous

Power Supply Auxiliary Supply : 60 - 480 VAC/DC, 50-60 Hz.


True RMS Basic Voltage (Volts L-N & L-L) Accuracy : 0.5% of Reading.
Parameters
Current
Accuracy : 0.25% of Reading
(Amps IR, IY, IB)

Line Frequency 45 to 55 Hz, Accuracy : 0.05% of Reading

Active Power (P) Accuracy : 0.5% of Reading(For IPFI>0.5)

Reactive Power (Q) Accuracy : 1.0% of Reading


Power
MEASUREMENT

Apparent Power (S) Accuracy : 0.5% of Reading

For Individual phases and System PF

Power Factor Accuracy : 0.5% of Reading (IPFI≥0.5)

Range of Reading : 0.05 to 1.00 Lag/Lead

Range of Reading : 0 to 999999999.9


Total Active Energy (KWh)
Accuracy : Class 0.5s as per IS14697
Energy

Total Apparent Energy Range of Reading : 0 to 999999999.9


(KVAh) Accuracy : 0.5% of Reading

Total Reactive Energy Range of Reading : 0 to 999999999.9


(KVARh) Accuracy : 1.0% of Reading
Quality
Power

THD and Individual Harmonic


Class 5.0 as per IEC 61557-12 up to 30th order.
For each phase V and A

Parameters KW, KVA, KVAR and Avg.Amps.

Window 15 minutes or 30 minutes selectable.


Demand

Mode Fixed or Sliding selectable.

Present, Predicted, Maximum Demand and Last


Maximum Demand
Calculation
(Import & Export – For Power Parameter Only)
Dimensions
Bezel 96 X 96 mm

Panel Cutout 92 X 92 mm

Depth of installation 55 mm

Display 4x3, 7 Segment, bright Red.

Operating temp 0°C to 55°C

Weight 310 gms (Approx).

Operating Current Range 0.4% to 120% of CT primary


Communication
MISCELLANEOUS

Modbus-RTU protocol : 2 – Wires, 9600, 19200,


RS485 PORT 38400 baud.
Parity – None, Stop bit – 1. Isolation : 2.5KV RMS

Instantaneous 1S
Display
update

Demand 1S

Harmonics 3S

Three Keys for navigation and programming of


Keypad
various parameters.

Red color. 1000 impulses/unit.


Calibration LED.
Import/Export of KWh/KVAh/KVARh.

Dual color LED.


Communication LED
Data Receive – Green LED.

Data Transmit – Red LED.

* 0.5s accuracy applicable only in 3P4W mode.

Note : Some parameters are available only on RS485 , so please refer to the user manual
for more details.

TRINITY ENERGY SYSTEMS PVT. LTD.


386, Savli G.I.D.C Estate, Manjusar-391775,
Dist.-Vadodara, Gujarat, India. Tele: +91-9228004452/53/54
E-Mail: [email protected]

*Specifications are subject to change without notice due to continuous improvement.

You might also like