Engineering Specification
Provide emergency audio as part of the main fire alarm control microphone, single switch function for paging to all — Alert zones,
panel. The emergency audio shall contain a paging microphone, Evacuation zones, and areas not programmed for signaling. The
pre-recorded messages <fire fighter telephone> and zoned system must provide high quality analog to digital conversion of
amplifiers capable of delivering multi-channel audio messages. paging sources. Digital transmission of paging must be provided
The system shall support a minimum of 100 audio channels. between system nodes over the same cabling as other system
Transmission of audio shall be over the same data network wiring data. The analog sources must be sampled and converted to
as the fire panel data. The network shall be over a dedicated digital across the network.
<single copper pair> <dual multimode fibers>, <dual Single mode System amplifiers must be distributed zoned type. Centrally
fibers><one single mode fiber> to remote parts of the facility. banked systems are not acceptable. The circuit must carry a
For systems requiring multiple locations for paging, the ability to minimum rating of 3.5 Amps for operating 24 Vdc signals.
Request/Grant/Deny page privileges shall be supported. Priorities The system shall provide fully integrated fire fighters’ telephone
shall be configured in software covering projects operational system that shall provide two-way communication between the
priorities between Autonomous Control Units (ACU), Central fire alarm control panel and any firefighters’ telephone station.
Control Station (CCS) and Local Operators Consoles (LOCs). << Audio and Firefighters’ Telephone shall be installed so that
Each panel shall store digitally up to 750 minutes of pre-recorded a seismic component Importance Factor of 1.5 is achieved.>>
audio messages as WAV files without the need to add additional <<The system shall include a dedicated color LCD touch screen
memory storage devices. These messages shall be automatically user display and controls. When a telephone is activated, a call-in
played in various areas of a facility under program control. The buzzer shall sound, and the location of the phone shall be shown
system shall have the capacity to store up to 200 individual audio on the LCD display. The display shall be capable of bilingual
messages. Each audio channel shall support up to 200 individual operation, displaying English, French, Spanish, or Portuguese
messages. Each panel shall simultaneously play back any of seven messages.
(7) different message channels in addition to a live page message All incoming calls and all connected phones shall be selected by
of the 100 available. touching the LCD screen. All subsequent telephone call locations
The system must provide operation to 25Vrms or 70.7Vrms shall be displayed in full text. The system shall display all incoming
speakers. The system must provide as a minimum the following calls, all connected phone(s) on the color LCD display. The system
paging common controls and indicators: Ready to page LED, shall be configured so that page messages may be issued from
three color VU display shows signal level provided by the any firefighter’s telephone connected to the system, as directed by
the emergency operator.