Excitation Current Test

The Transformer Testing Report presents excitation current test results across various tap numbers, showing increasing current and wattage values in a symmetrical pattern. The middle phase readings are lower than the outer phases, which is typical for core type transformers, and no abnormalities were detected. The results serve as a benchmark for future trending purposes.

Uploaded by

Muhammad Faisal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
7 views1 page

Excitation Current Test

The Transformer Testing Report presents excitation current test results across various tap numbers, showing increasing current and wattage values in a symmetrical pattern. The middle phase readings are lower than the outer phases, which is typical for core type transformers, and no abnormalities were detected. The results serve as a benchmark for future trending purposes.

Uploaded by

Muhammad Faisal
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

20140006041218 Transformer Testing Report

Excitation Current Test

U-N V-N W-N

Tap Test mA Watts mA Watts mA Watts


no. kV
1 10 21.899 198.000 15.247 138.162 23.986 206.390
2 10 22.409 201.956 15.601 141.021 24.449 210.190
3 10 22.935 206.146 15.974 144.023 24.973 214.359
4 10 23.481 210.533 16.369 147.156 25.533 218.795
5 10 24.045 215.074 16.764 150.349 26.100 223.359
6 10 24.625 219.790 17.173 153.649 26.712 228.220
7 10 25.213 224.627 17.587 157.035 27.282 232.973
8 10 25.829 229.669 18.018 160.551 27.853 237.820
9 10 26.477 234.945 18.481 164.278 28.466 242.958
10 10 27.167 240.521 18.939 168.053 29.112 248.339
11 10 27.871 246.287 19.421 171.999 29.786 253.961
12 10 28.579 252.147 19.929 176.123 30.489 259.820
13 10 29.303 258.193 20.677 180.415 31.217 265.922
14 10 30.264 264.098 21.261 184.968 32.250 271.964
15 10 31.059 270.630 21.854 189.631 33.004 278.314
16 10 31.877 277.386 22.504 194.634 33.833 285.234
17 10 32.725 284.412 23.151 199.715 34.654 292.153
18 10 33.636 291.985 23.806 204.942 35.499 299.310
19 10 34.558 299.656 24.475 210.326 36.400 306.888
20 10 35.509 307.610 25.146 215.845 37.326 314.753
21 10 36.490 315.868 25.842 221.601 38.295 322.984
22 10 37.524 324.560 26.596 227.743 39.285 331.479
23 10 38.595 333.607 27.346 234.003 40.341 340.482
24 10 39.717 343.100 28.148 240.663 41.440 349.874
25 10 40.851 352.838 28.982 247.719 42.583 359.732

Comments:
Excitation current values are in ascending symmetry with increasing tap numbers which is typical for
this kind of transformer. In core type construction middle phase readings are lesser than the two outer
phases as expected. No abnormality found. These results could be treated as benchmark for further
trending purpose.