510
5 20
Unloaded at start Loaded at start Generally fans less than or equal to 45kW (60hp) Generally fans greater than or equal to 45kW (60hp) Special circuits ensure motor starts off-load Some compressor systems can be difficult to start No material in basin; off-load Material in basin
Low-Inertia Fan 10 High-Inertia Fan Off-Load Compressor Loaded Compressor Off-Load Mixer Heavy Mixer
30 5 20 5 20
FOR MOTOR OVERLOAD PROTECTION, THE SR33 MUST BE USED WITH A SEPARATE CUSTOMER-SUPPLIED OVERLOAD PROTECTION DEVICE THAT HAS A RATING CORRESPONDING TO THE APPLICABLE TRIP CLASS.
Volume 13
e14-10
Soft Starters
1 - 80 0 - 633 - 0405
Field I/O
Software C-more & other HMI Drives Soft Starters Motors & Gearbox Steppers/ Servos Motor Controls Proximity Sensors Photo Sensors Limit Switches Encoders Current Sensors Pressure Sensors Temperature Sensors Pushbuttons/ Lights Process Relays/ Timers Comm. Terminal Blocks & Wiring Power Circuit Protection Enclosures Tools Pneumatics Appendix Product Index
Class J High-Speed Circuit or RK5 Time-Delay Breaker Current-Limiting Rated Fuse *** 600VAC Rated 600VAC
35A 45A 60A 80A 125A 175A 200A 250A 350A 400A 450A 450A 350A 450A 500A
10 9 8 7 6 5
4 3 2
1 Rated Current
241A 280A 350A 430A 482A
1.5
361 420 525 645 723
2
482 560 700 860 964
2.5
602 700 875 1075 1205
3
723 840 1050 1290 1446
3.5
843 980 1225 1505 1687
4
964 1120 1400 1720 1928
** Suitable for use on a circuit capable of delivering not more than the RMS symmetrical Amperes as indicated at 480VAC maximum, when protected by fuses or inverse-time circuit breakers with rated maximum Amperes as indicated. *** Fuse comparable to Edison type JHL (class J) or ECSR (class RK5).
The SR33 can be used at ratings other than those stated. Use the above trip curves to determine the required unit for the duty. As an example, the SR33-280 will run a 200hp motor (280 Amp) at the maximum continuous running current and will allow an overload of 3 x 280 Amp (840A) for 12 seconds, 3 times per hour. The unit would also allow a 3.5 x overload (980A) for approximately 5 seconds, 3 times per hour. Following an overload trip, subsequent restarts can be restricted due to a cooling time. The severity of overload determines the cooling time, which has a maximum value of 10 minutes.
THE SOFT STARTER OVERLOAD TRIP CURVE
SHOWN ON THIS PAGE APPLIES ONLY TO
2018920.125A
SR33-241 THROUGH SR33-482, AND IT PROVIDES PROTECTION ONLY FOR THE SOFT STARTER. FOR MOTOR OVERLOAD PROTECTION, A SEPARATE CUSTOMER-SUPPLIED OVERLOAD PROTECTION DEVICE MUST BE PROVIDED.