12-Supervisory Input Module: Data and Installation

The document provides installation and configuration instructions for the 12-Supervisory Input Module (S4-34412) and Connection Converter (S4-34495) used in the Vigilon fire alarm control panel system. It details the required components, wiring specifications, LED usage, and compatibility with Vigilon systems, emphasizing the importance of using specific types of LEDs and ensuring proper EMC compliance. Additionally, it outlines the technical specifications, including dimensions, operating conditions, and environmental considerations for disposal.

Uploaded by

0xefee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views4 pages

12-Supervisory Input Module: Data and Installation

The document provides installation and configuration instructions for the 12-Supervisory Input Module (S4-34412) and Connection Converter (S4-34495) used in the Vigilon fire alarm control panel system. It details the required components, wiring specifications, LED usage, and compatibility with Vigilon systems, emphasizing the importance of using specific types of LEDs and ensuring proper EMC compliance. Additionally, it outlines the technical specifications, including dimensions, operating conditions, and environmental considerations for disposal.

Uploaded by

0xefee
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Data and Installation

12-Supervisory input module by Honeywell

S4-34412 & S4-34495

S4-34412 S4-34495
12-Supervisory Input Module Connection Converter

26-way
300mm ribbon cable
These instructions cover the 12-Supervisory input LED selection and operation
module (Also referred to as 12-input interface
module) (S4-34412) and Connector converter Only use high efficiency Red, Amber and Green
(S4-34495). These are designed to be installed in LEDs with this module.

"
custom panel to provide supervisory input to control
plant via Vigilon System. The module connects to a
loop circuit of a Vigilon fire alarm control panel. It Do not use Blue or White LEDs as these are
uses one of 200 device addresses on the loop and not suitable for use with the module.
responds to regular polls from the control panel, The LEDs provide a flashing indication when the
reporting the device type and the status of its corresponding switch is closed and switch operated
supervisory switch inputs. message is successfully sent to the control panel.

" The module can only accept non fire


supervisory switch inputs.
Cables
The internal connection from the Connection
converter to each switch and LED is made using a
standard PVC cable. Each switch and LED can be
26 Way ribbon cable
(supplied with S4-34412) positioned a maximum of up to 10m cable distance
away from the Connection Converter.

For recommendations on loop cable type refer to


the manual supplied with the Vigilon control panel.

Mounting
S4-34412 It is recommended that the 12-Supervisory input
module and Connection converter are mounted on
DIN RAIL
(not supplied)
DIN rails inside a suitably protected enclosure, the
S4-34495 custom panel. The switches, LEDs and associated
wiring should be contained in the same enclosure
The module is supplied with a 26 way ribbon cable
for mechanical protection.
for connecting to a Connector converter that holds

"
the terminals for external input switches and
corresponding confirmation LEDs for each switch.
The designer of the custom panel in which
the modules, LEDs and switches are mounted must
Compatibility ensure the panel enclosure is EMC compliant and is CE
The 12-Supervisory input module is compatible for marked.
use in a Vigilon system where the Control panel
has specific MCC/MCB software, see technical data
section. The 12-Supervisory input module is
configured using the Vigilon Commissioning tool
V1.25 or higher.

4188-950_Issue 1_01/09_S4 12 sup i/p module 1


Data and Installation 12-Supervisory input module

Loop wiring
The loop cable screen must be continued through each module. The loop cable screens must be connected
to an earth terminal inside the enclosure.

To next device
Custom panel on the loop

26 Way ribbon cable


S4-34495 S4-34412

2 4 6 8 10 12 14 16 18 20 22 24 26 0V
L2
0V
L1
1 3 5 7 9 11 13 15 17 19 21 23 25

DIN rail

From previous
device on the loop

Terminals and description

1 Switch 1 (SW1) 14 Common


2 Switch 2 (SW2) 15 Confirmation LED 1
3 Switch 3 (SW3) 16 Confirmation LED 2
4 Switch 4 (SW4) 17 Confirmation LED 3
5 Switch 5 (SW5) 18 Confirmation LED 4
6 Switch 6 (SW6) 19 Confirmation LED 5
7 Switch 7 (SW7) 20 Confirmation LED 6
8 Switch 8 (SW8) 21 Confirmation LED 7
9 Switch 9 (SW9) 22 Confirmation LED 8
10 Switch 10 (SW10) 23 Confirmation LED 9
11 Switch 11 (SW11) 24 Confirmation LED 10
12 Switch 12 (SW12) 25 Confirmation LED 11
13 Common 26 Confirmation LED 12

2 4188-950_Issue 1_01/09_S4 12 sup i/p module


12-Supervisory input module Data and Installation

Wiring the switches and LEDs

" The switch input and LED output wiring are not monitored for wiring faults. If using screened cables for
wiring the switches and LEDs, then the cable screens must connect to the earth terminal inside the Custom panel.
Custom Panel

S4-34495

2 4 6 8 10 12 14 16 18 20 22 24 26

1 3 5 7 9 11 13 15 17 19 21 23 25

SW2 SW1 SW4 SW3 SW6 SW5 SW8 SW7 SW10 SW9 SW12 SW11 LED2 LED1 LED6 LED2 LED3 LED5 LED8 LED7 LED10 LED9 LED12 LED11

SWX
LEDX
Flashing indication

Configuration
The following information is intended for use by the servicing organisation to assist with the
configuration of the 12-Supervisory input modules connected to the Vigilon system loops.

" Use Commissioning Tool software version 1.25 or greater to commission the 12-Supervisory input modules.

Open the system configuration in the tool, select the S4 interface icon to call up the
S4 Interface Configuration window.

Select the required 12-Supervisory input module from the list and then select the number of supervisory
inputs 'Number of Keyswitches' in use by the interface. Selecting a '0' setting will revert the window for
configuring a 4-channel S4 interface. Each of the used switch input of the 12-Supervisory input module can
be configured to trigger a command build action.

Continue configuring the Vigilon system and on completion Transmit the configuration data to the control
panel. Then test each switch input connected to the 12-Supervisory input module and ensure the configured
actions occur in the Vigilon system and where confirmation LEDs are wired ensure they are illuminated.

4188-950_Issue 1_01/09_S4 12 sup i/p module 3


Data and Installation 12-Supervisory input module

Technical data
S4-34412
12-Supervisory input module (also referred to as 12-Input interface module)
Designed to meet EN54-17:2005 and EN54-18:2005
Dimensions 102mm height x 65mm width x 98mm depth
Weight 175g
Storage temperature -30ºC to 70ºC
Operating temperature -10ºC to 60ºC
Relative Humidity Up to 95% - Temperature 5ºC to 45°C (Non condensing)
Colour White
Switch inputs Switch contact resistance of <1W with low current operation of <1mA.
Up to 12 normally open switches positioned no more than 10m cable distance away
from the Connection Converter are allowed (this wiring is not monitored for faults).
A closed switch provides a Supervisory (non fire) input into the Vigilon System.
LED outputs Up to 12 confirmation LEDs positioned no more than 10m cable distance away from
the Connection Converter are allowed (this wiring is not monitored for faults).
Use only high efficiency Red, Amber or Green LEDs.
Load Factor Module = 1 (if no confirmation LEDs are used)
LED outputs used = 5
EN54-17 data Vmax Vnom Vmin VSO max VSO min IC max IS max IL max ZC max
42V 40V 24V 14V 10V 0.4A 1A 20µA 0.10W
Vigilon Panel Fully compatible with LPC = V3.93 / V4.35 & MCC/MCB = V3.94 / V4.37
compatibility
102mm

Depth 98mm
65mm

Fault Healthy
amber green

System fault
amber

At the end of their useful life, the packaging,


product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.

WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk

by Honeywell Telephone: +44 (0) 116 246 2000 Fax (UK): +44 (0)116 246 2300

4 4188-950_Issue 1_03/09_S4 12 sup i/p module