Fee Lab Manual 24-25
Fee Lab Manual 24-25
BACHUPALLY, HYDERABAD-500090
Department of Electrical and Electronics Engineering
CERTIFICATE
This is to certify that this book is a bonafide record of practical work done in the
Basic Electrical Engineering Laboratory in ........semester of………year during the
academic year ..................... by
Name :-……………………………..
Roll.No :-……………………………
Branch :-…………………………….
Date:-…………
Course Outcomes:
At the end of this course, students will able to
1. Demonstrate the common electrical components and their ratings. (BL2)
2. Summarize the basic fundamental laws of electric circuits. (BL2)
3. Distinguish the measurement and relation between the basic electrical parameters. (BL4)
4. Examine the response of different types of electrical circuits with three phase excitation. (BL4)
5. Outline the basic characteristics of Electrical machines. (BL2)
Apparatus Required:
Theory:
Ohm’s Law:
Ohm’s law states that, “At constant temperature current flowing through the conductor is directly
proportional to the potential difference existing between the two ends of the conductor. i.e.,
VαI
V = Constant * I
Where
V is the potential difference across the conductor in volts,
I is the current flowing through the conductor in amps
The constant of proportionality = R
Where R is the resistance of the conductor in Ohms.
Circuit Diagram:
Fig.1
Procedure:
Σ I= 0
This idea by Kirchhoff is commonly known as the Conservation
ation of Charge , as the current is
conserved around the junction with no loss of current.
Here in this simple single junction example, the current IT leaving the junction is the algebraic sum
of the two currents, I1and I2 entering the same junction. That is IT = I1 + I2.
Note that we could also write this alternatively as the algebraic sum of: IT - (I1 + I2) = 0.
Kirchhoff’s voltage law states that the algebraic sum of the potential differences in any loop must
be equal to zero as: ΣV = 0. Since the two resistors, R1 and R2 are wired together in a series connection;
conne
they are both part of the same loop so the same current must flow through each resistor.
Thus the voltage drop across resistor, R1 = I*R1 and the voltage drop across resistor,
R2 = I*R2 giving by KVL:
Circuit Diagram:
Figure 2
2. KVL ( Kirchoff’s Volatge Law):
Figure. 3
Observations:
1. KCL:
Theoretical Practical
2. KVL:
Theoretical Practical
Calculations:
Result:
2. Verification of Thevenin’s and Norton’s Theorems
Aim:
To verify Thevenin’s and Norton’s theorems and to find the full load current for the given circuit.
Apparatus Required:
Statement:
Thevenin’s theorem states that any two output terminals ( A & B ) of an active linear network containing
independent sources (it includes voltage and current sources) can be replaced by a simple voltage source of
magnitude Vth in series with a single resistor Rth where Rth is the equivalent resistance of the network when
looking from the output terminals A & B with all sources (voltage and current) removed and replaced by their
internal resistances and the magnitude of Vth is equal to the open circuit voltage across the A & B terminals
Procedure:
1. Connections are given as per the circuit diagram.
2. Set a particular value of voltage using RPS and note down the corresponding ammeter readings.
To find VTH
3. Remove the load resistance and measure the open circuit voltage using multimeter (VTH).
To find RTH
4. To find the Thevenin’s resistance, remove the RPS and short circuit it and find the RTH using multimeter.
5. Give the connections for equivalent circuit and set VTH and RTH and note the corresponding ammeter reading.
6. Verify Thevenin’s theorem.
Calculations:
Theoretical and Practical Values
Practical
Norton’s Theorem
Norton’s Theorem may be stated as Any Linear Electric Network or complex circuit with Current and Voltage
sources can be replaced by an equivalent circuit containing of a single independent Current Source IN and a
Parallel Resistance RN.
To Find IN:
To Find RN:
5. Remove RPS and short circuit the terminal and remove the load and note down the resistance across the two
terminals. Equivalent Circuit:
6. Set IN and RN and note down the ammeter readings.
7. Verify Norton’s theorem.
Calculations:
Theoretical and Practical Values
Practical
Result:.
3: Verification of Superposition and Reciprocity Theorems.
AIM: To verify the superposition theorem and Reciprocity theorems for the given circuits.
APPARATUS REQUIRED:
THEORY:
SUPERPOSITION THEOREM:
Superposition theorem states that in a lumped ,linear, bilateral network consisting more number of sources each branch
current(voltage) is the algebraic sum all currents ( branch voltages), each of which is determined by considering one
source at a time and removing all other sources. In removing the sources, voltage and current sources are replaced by
internal resistances.
CIRCUIT DIAGRAM:
PROCEDURE:
Reciprocity Theorem
STATEMENT:
“In a linear bi-lateral single source network, the ratio of excitation to the response is constant when the position of
excitation and response are interchanged”.
CIRCUIT DIAGRAM:
Procedure:
1. Connect the circuit as per circuit diagram.
2. Adjust the output voltage of R.P.S to an appropriate voltage say 10 V in Figure 1
3. Note down the response of I through 3.3 kΩ resistor and tabulate the values.
4. The circuit connections are changed as per the Figure 2,change the source to load end
and replace the source with internal resistance.
5. Note down the response of I through 1 kΩ resistor and tabulate the values.
6. Compare the theoretical & practical values and prove reciprocity theorem
Calculations:
Observations
Theoretical
Practical
Result :
4: Resonance in series RLC circuit
Aim:
To determine resonant frequency, band width and Q-factor for Series RLC circuits.
Apparatus Required:
Theory:
Series Resonance:
Consider a RLC circuit in which resistor, inductor and capacitor are connected in series across a
voltage supply. This series RLC circuit has a distinguishing property of resonating at a specific
frequency called resonant frequency. In this circuit containing inductor and capacitor, the energy is
stored in two different ways. When a current flows in an inductor, energy gets stored in magnetic
field. When a capacitor is charged, energy gets stored in static electric field.
In some cases, at certain frequency called resonant frequency, the inductive reactance of the
circuit becomes equal to capacitive reactance which causes the electrical energy to oscillate
between the electric field of the capacitor and magnetic field of the inductor. This forms a
harmonic oscillator for current. In RLC circuit, the presence of resistor causes these oscillation to
die out over period of time and is called damping effect of resistor.
At resonance in series RLC circuit, two reactance become equal and cancel each other. So in
resonant series RLC circuit, the opposition to the flow of current is due to resistance only. At
resonance, the total impedance of series RLC circuit is equal to resistance i.e Z = R, impedance has
only real part but no imaginary part and this impedance at resonant frequency is called dynamic
impedance and this dynamic impedance is always less than impedance of series RLC circuit.
Before series resonance i.e before frequency, fr capacitive reactance dominates and after resonance,
inductive reactance dominates and at resonance the circuit acts purely as resistive circuit causing a
large amount of current to circulate through the circuit.
Circuit Diagram:
Model Graphs:
Current Vs Frequency
Tabular Column:
Quality
Fr (Hz) FH (Hz) FL (Hz) Band Width Factor
Theoretical
Practical
Procedure:
Tabular Form:
Result:
5: Load Test on Single Phase Transformer (Calculate Efficiency and Regulation)
Aim:
To calculate Efficiency and regulation of Single phase transformer by conducting load test
on Single phase transformer
Apparatus Required:
Transformer Ratings :
Power:2 KVA,
Primary/Secondary :230/415 Volts,8.69/4.82 Amps.
Theory:
A transformer is a static apparatus used to transform a.c. electrical power from one voltage to
another voltage. It works on the principle of mutual induction.In a transformer there are two
windings primary winding & secondary winding. Both these windings are having their internal
resistance & leakage current. When the transformer is loaded there will be voltage drop in the
transformer due to the resistance & reactance of the windings.When the secondary winding of the
transformer is completed through a load an voltage V is applied to the primary winding ,the
transformer is said to operate under load condition.
Under this condition transformer copper loss increase with increase in current, due to that
efficiency changes. At half load efficiency is reaches to maximum, it gradually decreases when
further load increases. This is because at half load Cu loss is less and iron loss is also less, but
below half load iron loss will be more which results in less efficiency. This situation happens
when transformer is distribution transformer.
When load increase beyond half load Cu loss will increase which again reduces the
efficiency. This test is performed to determine the efficiency and regulation of a transformer at
different load conditions.
REGULATION: If E0 is the load voltage of the secondary side & V, is the terminal voltage of
the secondary side. When it is loaded: Then,
E0 – V = Voltage drop in the transformer when it is loaded.
=Change in the terminal voltage of the transformer when it is loaded.
Circuit Diagram:
Voltage regulation of a transformer is the ratio of change in the terminal voltage of the secondary
from no load to load condition.
To its rated voltage, at a particular load current.
i.e % Regulation = E0 -V ×100
V rated
As the load current increases, the voltage drop in the transformer windings also
increases & hence the voltage regulation increases. The Regulation of a transformer should not
more than 8%. In a transformer lower percentage regulation is a better regulation.
EFFICIENCY:
The ratio of output power to the input power of a transformer is called the efficiency of the
transformer up to certain amount of load, efficiency increases with the increases in load and the
onward slightly decreases.
The above formula shows that efficiency depends not on the value of load current, but also
on the power factor (COSΦ) of the load current. If the load is purely resistive, the power factor i.e.
cosΦ =1.
.
EFFICIENCY = V2 I2
IN PUT POWER
Formula Used:
%η = (W2 / W1)*100
%reg = {(Vrated – V2) / Vrated} * 100
Procedure:
1. Connect the circuit diagram such that the supply on LV side and load on HV side as shown
in the fig
2. Gradually increase the voltage using auto transformer till the voltmeter reads the rated
voltage, 230v on LV side and also record the voltage on HV side.
3. Maintain the voltage V to be constant for all loads.
4. Switch on the load switches one by one and record the ammeter, voltmeter and wattmeter
readings. (The load current should not be exceed the rated current,4.82A.)
5. Switch off the supply and set the auto-transformer at zero position.
Observations:
Calculations:
Result:
6. Three Phase Transformer: Verification of Relationship between Voltages and Currents
(Star-Delta, Delta-Delta, Delta-star, Star-Star)
Aim:
To verify the relationship between voltages and currents in a three phase transformer for Star
Delta Connection
Apparatus Required:
Theory:
In this type of transformer connection, then primary is connected in star fashion while the
secondary is connected in delta fashion as shown in the Figure 1 below.
The voltages on primary and secondary sides can be represented on the phasor diagram as
shown in the Figure 2 below.
Procedure:
1. Connect the Circuit as per circuit diagram.
2. Adjust the Auto transformer till it reaches 230V and measure primary and secondary
voltages and currents.
3. Repeat the above step for different input voltages
4. Note down the values of phase(voltages and currents) and line(voltages and Currents)
5. Compare the measured values with theoretical values.
Observations:
Calculations:
Result:
.
7: Measurement of Active and Reactive Power in a balanced Three-phase circuit
Aim:
To measure active and reactive power using 2-wattmeters for balanced loads in a 3- phase
circuit.
Apparatus Required:
S. No Apparatus Range Quantity
1. 3 Phase Auto transformer 1 No
2. Ammeter 0-20 A 2 Nos
3. Voltmeter 0-300 V 2 Nos
4. Resistive Load Suitable
5. 1 Φ Transformer 1KVA, 230/415V 3 Nos
6. Connecting wires Required
Theory:
In a 3-phase, 3-wire system, power can be measured using two wattmeter’s for balance loads.
This can be verified by measuring the power consumed in each phase. In this circuit, the
pressures coils are connected between two phase such that one of the line is coinciding for
both the meters.
P1 + P2 = 3 VPhIPhCOSø
Power factor Cosø = Cos (tan-1 √3 ((P1 –P2)/ (P1 +P2)))
Considering the above figure (A) in which Two Wattmeter W1 and W2 are connected,
the instantaneous current through the current coil of Wattmeter, W1 is given by the
equation shown
below.
W1
M L
V
C
W2 C
V
L M
Observations:
W1 W2 I1 I2 Vph W1+W2
TYPE OF LOAD (W) (W) (mA) (mA) (V) (W) P
(KW)
Instantaneous power measured by the Wattmeter, W1 is
The instantaneous current through the current coil of Wattmeter, W2 is given by the equation
Therefore, the Total Power Measured by the Two Wattmeters W1 and W2 will be obtained by
adding the equation (1) and (2).
Where P – the total power absorbed in the three loads at any instant.
Procedure:
1. Connect the circuit diagram as shown in figure.
2. Keep all the switches at off position.
3. Switch on the supply and apply the balanced R Load in all the Phases.
4. Note the Readings of Wattmeter, voltmeter and Ammeter.
5. Keep all the switches at off position and switch of the supply.
Calculations:
Result:
8. Performance Characteristics of a Separately Excited DC Shunt Motor
Aim:
To obtain the performance characteristics of a DC shunt motor by load test.
1. Output ~ Armature current
2. Output ~ Speed
3. Output ~ Torque
4. Output ~ efficiency
Apparatus Required:
The value of “Eb” is zero while starting the motor. Hence, the voltage across the armature has to
be increased gradually.The power developed in the rotor (armature) =EbIa= Tω
Where ω=2N
60is the angular velocity of the pulley, in rad/sec.
In a dc motor T α ΦIa,
Where Φ= Flux produced by the shunt field per pole
Ia= Armature current
If Φ is constant in the shunt motor, by neglecting the armature reaction; the speed falls as Eb
falls. In a dc motor Ra is very small, hence IaRa is a small value and fall in Eb with increase in load
is small. Thus, the speed falls slightly as Iaincreases.
Armature current ~ Torque characteristics:
If Φ is constant, developed torque increases with increase in Ia.
T = KΦIa
In actual condition, Φ slightly falls with increase in Iadue to the effect of armature reaction.
Observations:
Armature voltage = Volts
Field voltage = Volts
Field current = Amps
No load speed = rpm
Tabular Column:
Sample Calculations:
Model Graphs:
Calculations:
Result:
9: Torque-Slip Characteristics of a Three-phase Induction Motor
Aim:
To perform the brake test on a 3-ф slip ring induction motor and obtain its torque slip characteristics
Nameplate details:
AC slip ring induction motor
Stator Rotor
Voltage 415V 200v
Current 7.5A 11.0A
Winding Star Star
Power 5.0 h.p
Speed 1440 r.p.m
Apparatus Required:
Theory:
The slip ring induction motor consists of two main parts. They are stator and rotor.
Stator: It is a star connected 3- ф winding. Each phase winding is separated by 1200 electrical, 3-
ф supply is connected to the stator, it produces a rotating magnetic field in the stator core.
Rotor: It is also a star connected 3- ф winding and wound for the same number of poles as the
stator. Its external terminals are short-circuited. Due to the relative speed between the rotating
flux in the stator and the stationary flux in the rotor. The rotor rotates nearer to the synchronous
l20f
speed maintaining a low slip.The synchronous speed of the rotating flux in the stator N s =
P
Where 'f is the supply frequency in Hz and 'P' is the number of poles.
Slip : It is the relative speed of the rotor with respect to synchronous speed of the rotating
magnetic field.
(Ns N )
Percent Slip = X100
Ns
Torque τ = 9.81(τ1 – τ2). R, Where R is at the radius of the brake drum.
2N
Output = watts
60
output
%ŋ = x100
input
Pph (Where 'Pph' is the input power per phase)
Power factor = cosф =
Vph.Iph
Circuit Diagram:
Procedure:
1. Connect the circuit diagram as shown in fig.
2. Keep the 3-ф auto transformer at zero voltage position.
3. Loosen the rope on the brake drum and set the tension meters at zero position.
4. Switch - ON the motor and increase the auto - transformer gradually till the voltmeter reads
the rated phase voltage 230V.
5. Note down the readings of the voltmeter, ammeter, tachometer, spring balances and
wattmeter readings at no-load.
6. Now increase the load gradually by tightening the rope till the ammeter reads the rated
current. Pour some water inside the break drum for cooling.
7. Note down Vph, Iph, Pph, T1, T2 and speed.
8. Switch – OFF the supply and adjust the 3-ф auto - transformer at zero position.
Observations :
Model Graph:
Calculations:
Result:
10: No-Load Characteristics of a Three-phase Alternator
Aim:
To plot No load charecteristics of Three phase alternator.
Apparatus Required:
Motor Ratings:
DC Motor Alternator
O.C.C:
Open Circuit Characteristics is plotted from the given data as shown as in D.C Machines, this
is plotted by running the machine on no-load and by noting the values of induced voltage and
field excitation current. It is just like a B-H curve.
The output voltage of an alternator depends essentially upon the total flux in the air gap. At
no load, this flux is established and determined exclusively by the dc field excitation.Under load,
however, the air gap flux is determined by the ampere-turns of the rotor and the ampere-turns of
the stator. The latter may aid or oppose the MMF (magneto motive force) of the rotor depending
upon the power factor of the load. Leading power factors assist the rotor, and lagging power
factors oppose it.
Because the stator MMF has such an important effect upon the magnetic flux, the voltage regulation
of alternators is quite poor, and the dc field current must continuously be adjusted to keep the voltage
constant under variable load conditions. If one phase of a three-phase alternator is heavily loaded, its
voltage will decrease due to the IR and IXL drops in the stator winding. This voltage drop cannot be
compensated by modifying the dc field current because the voltages of the other two phases will also
be changed. Therefore, it is essential that three-phase alternators do not have loads that are badly
unbalanced.
Circuit diagram:
Procedure:
If Eoc
(Amps) (Volts)
Result:
11. Verification of Maximum Power Transfer Theorem.
Aim
To verify of Maximum Power Transfer Theorem for the given circuit.
Apparatus Required:
Description:-Maximum power transfer theorem states that “ In two terminal a.c. net work the load will
absorb maximum power from a generator if the load impedance is the complex conjugate of the
Internal impedance of the generator.” But in d.c. circuit the load draws maximum power from the source,
when the load resistance is equal to the internal resistance of the source i.e. at RL = RS the power consumed
by the load is maximum. The power in the load is given by P =IL2RL = VL2 / RL.
Procedure: - The circuit is connected as shown in the figure-1. First the load is removed from the circuit.
The battery is replaced by its internal impedance (Assume that the internal impedance is equal to zero and
the terminals are short- circuited).
The resistance between the terminals A and B is measured by using a multi-meter. It is the resistance of
the source (RS). Now the battery and the load resistance RL are connected in their places. By varying the
Value of RL from RL < RS to RL > RS, the voltage across the load and current through the load are noted.
The values are tabulated as shown.
Now the power is calculated by using the formula P =IL2RL = VL2 / RL for each value of current IL or VL
Take the value of RL at the maximum power. If RL value is equal to the internal resistance of source or
Generator RS, then the theorem is proved.
Formula: - Power P =IL2RL = VL2 / RL watt
Where IL= Load current. RL= Load resistance. VL = Voltage across the load
Graph:-
A graph is drawn between the power P and the load resistance RL,as shown in the figure 2, by taking power P on
Y- axis and load RL on X - axis. The graph shows that the power is maximum when the load resistance is equal
to the internal resistance of the source.
Precautions:-
1) The load resistance RL is varied from < RS to > RS .
2) Internal resistance of the source should be measured before going to the experiment.
3) The battery should be removed and those terminals should be shorted while measuring the source resistance.
Results:-
12. Power factor improvement by using capacitor bank in parallel with inductive load.
Aim
To Educated in how to improve power factor using capacitors in parallel with inductive load.
Observations
Load 1
P V I COSØ= P/VI
Without Capacitor
With Capacitor
Load 2
P V I COSØ= P/VI
Without Capacitor
With Capacitor
Load 3
P V I COSØ= P/VI
Without Capacitor
With Capacitor
Calculations:
Result