A Glossary (continued) A2 Symbols Graphic symbols for block diagrams Binary elements according to DIN 40900 Part 12, September 1992, IEC 617-12: amended 1991 Analog information processing according to DIN 40900 Part 13, January 1981 To document the linking of analog and binary signals, additional symbols have been used, taken fram several, DIN documents. ‘As a rule, direction of the signal flow is from left to right and from top to bottom. Other flow directions are marked by an arrow. Input signals are listed on the left side of the signal flow, output signals on the right side. Symbol Description To obtain more space for I] | representing a group of H | | related elements, contours of _— | | the etements may be joined or cascaded if the following rules are met: IL] - ‘There is no functional linkage rn between elements whose common contour line is oriented in the signal flow direction. FI Note: This rule does not necessarily apply to configurations with two or more signal flow directions, such as for symbols with a control block and an output block. ‘There exists at least one logical link between elements whose common contour line runs perpendicularly to the signal flow direction. Description Components of a symbol ‘A symbol consists of ‘contour or contour ‘combination and one or ‘more qualifiers. (aya, Control block ‘A control block contains an input function common to several symbols. It is used for the collective setting of several trigger elements, for example. Output block ‘An output block contains an ‘output function common to several symbols. ‘Settable control block ‘The four digits represent the address under which the function shown in the text after the colon may be set via the local control panel Settable control block with function blocks ‘The digits in the function block show the settings that are possible at this address. ‘The text below the symbol shows the setting and the corresponding unit or meaning. 65 A Glossary (continued) Symbol Description Symbol Description Static input (en out of n) elemen ! Only the state of the binary Poy | ‘The output variable will be 1 4 input variable is eff only if just one input variable sured is 1 ‘The number in the symbol , may be replaced by any other 4 Only the transition from value tistborl decumbent ; Oto value 1 is effective. inputs bs nreesed or ss decreased accordingly. Negation of an output Delay element \ ‘The value up to the border The transition from value 0 to e line is negated af the output. 4 atthe output occurs after a time delay of 1 relative to the corresponding transition at the input. Negation of ap input The transition from value 1 to 4 ‘he input value i negate Oat the output oecurs ater a bs time delay of t2 relative to the sn corresponding transition at the input. Dynamic input with neaation ! Only the transition from value 1 and t2 may be replaced by “- 1 to value 0 is effective. the actual delay values (in sal seconds or strabe ticks). " Me Dent te wi = ‘The output variable will be 1 a Tho ou varaie wif bed eI | ony tthe input variable ; azul changes to 1. The output variable will remain 1 for 100 ms, independent of the ‘OR element duration of the input value 1 ‘The output variable will be 1 =o sama] OMY if atleast one input Gron-reviogerabte) variable boil. Without a 1 in the function Testo cleat Bee nermosai Mp fop i ‘The output variable will be 1 only if at least two input i variables are 1. The number ee cata te 66 in the symbol may be replaced by any other number. example, but it may be changed to any other duration. A Glossary (continued) Symbol Description Symbol Description Anaoa-tal converter ‘moiin 5 Arango aL —_ | Mute vr tony Wt converted {0.2 binary signal ifthe input variables also 1 Band ass er siete ewe Fhe ouput ony transmits the The upat vale isthe Soe component oe nat aference bat sea} Sols Alster requnces sn 4 summing element is (goeve and below 50 Hz) are obtained by enagina the minus sign to a plus sign at Calnune the symbc a es ors ] At the + input the input +n variable transitions from 0 to ager wih binary te | —___| Schmit ger th bina _] {ate counted and treats Lol iit! the function block. TET | FARES out vale ima funtion ook = wil be! ‘ the input sire transition of the input variable es from 0 to 1 resets the counter The output variable remains ‘00 1 until the input signal drops below tne nacho sean —— Electromechanical drive vemunaamal a ingore hee 2 for ‘Storage of a binary or analog Le sana ” ‘Signal level converter wah elect oath Wen te mp arabe Datwoon mpet on efpu changes a a pulse soma] Ue oe vollage put Sequence is generated at the 2 output. ‘The ! to the left of the G indicates that the pulse ‘sequence starts with the input variable transition (synchronized star) If there is a ! to the right of the G, the pulse sequence ‘ends with the ending of the 1 signal at the input (synchronized stop). eg. voltage input Ut = device identifier 67 A Glossary (continued) ‘Symbol Description ‘symbol Description Input transducer PC interface at with conductor and device with pin connections a DE identifiers sen) (according to DIN EN 60445) Conductor identifiers for current inputs: for A: At and A2 for B: B1 and B2 for C: Ct and C2 for N: Ni and N2 Multiplier ic ‘The output variable is the Conductor entities for reat of the mutipicaion of Maia g ‘the two input variables. via transformer 1: si for A: 1U forB:1V Diviger for C: 1W 3 __| The output variable is tne for N: 1N ae * r result of the division of the via transformer 2: | two input varies. for A: 2U i for B: 2V — Devine identifiers for current ‘The output variable becomes 1 only if the input variable(s) transformers: for A: T4 are equal to the function in feet cao) the function block, forC:T3 for: T4 [ima] _ | The output variable becomes for voltage transformer 1 areas 1 only if the input variable(s) for a: TS ee cul Satisty the equation in the for: T6 function block. for ¢: 17 for N: TB for Vey transformer: T80 for voltage transformer 2 for A: TIS: Change-over contact os [— with device identifier Special symbol + Output relay in normally- vex} energized arrangement (closed-circuit operation’) 68 ecs.an24oy. 02/116 1208988 A Glossary (continued) A3 Examples of Signal Nam Al settings and signals relevant for protection are shown in the block diagrams of Chapter 3 as follows: ‘Signal Name Description @ FREC: Fault start Internal signal names are not ‘coded by an address. In the block diagrams they are marked with a diamond. The intemal signal names used and their origins are listed in Appendix 8. Signal names coded by an DIST: 21 tiggered address are referred to once [3804 by their address (in square brackets). The source is documented in Chapters 7 and 8. Dist: ‘Subsequent references use 21" tiggered the signal name only. MAIN: Control ext. A specific setting to be used 7no (off) later on is shown with its signal name and the setting with preceding setting arrow. A4 Symbols Used symbol Meaning t Time, duration v Voltage, potential difference v ‘Complex voltage 1 Electrical current 1 Complex current z ‘Complex impedance iz Modulus of complex impedance t Frequency 8 ‘Temperature in °C z ‘Sum, result a Unit of electrical resistance « Angle ° Phase angle. With subscripts: specific angle between a defined current and a defined voltage. x Time constant aT ‘Temperature difference in K 6 B Internal Signal Names Internal signal names are not coded by an address, They are indicated by a diamond in the block diagram. * Internal signal names Figure ‘Self-monit, blocking 24 MAIN: Autom. reset 20 MAIN: Block. tI> 2 MAIN: Block. tl>> 12 MAIN: Block. tIN> 12 MAIN: Block. tIN>> 12 MAIN: General reset 20 MAIN: Manual reset 20 IDMT/DTOC: Trip criterion 16 IDMT/DTOC: ti>/tiref elapsed 3 IDMT/DTOG: tl>> elapsed 3 IDMT/DTOC: tiN>/tINref elapsed 3 IDMT/DTOC: tIN>> elapsed 3 CBF: Trip by CBF 4 Signals 7 FREC: Reset signal mem. 20 FREC: Fault running 19 Waming 24 * trerinthe signal names coresponds to 1B (as reference curent) inte acess lt, 70 se 302.401602)278 124350 4 Changing Values ‘on: “on” (on-line) means that the value can be changed even when the protective function is enabled, off: “off” (offline) means that the value can be changed provided that the protective function is disabled. =: "means that the value cannot be modified by control action, ny: o: »): W): ‘Acchange in value is possible without activating the value-change enabling function, Indication "..." is possible and means that no value has been measured. Indication *..-" is possible and means that the value is out of range. The value change is password-protected. ‘The setting "2" is represented by the "00" display. n C Address List (continued) C14 Parameters C44 Device Identification € 4.4.4 Ordering Information ‘Address | Description [Change [Defautt [Rangeof Values | Unitor Neaning tere xy ment 00 50 ott “o ° 299 rn 00 55. ete ° OLD 399 1 ©4.4.2 Design Version ‘Address | Description ‘Change’ [Default [Range of Values | Unit or Neaning, Inere- xy ‘ment 02 09 : ror | 200 600 a o2 18 : tiox o.oo 2.2 33.59 0.01 2 soso. sonsnr-ecr/ SLs 12518506 C Address List (continued) © 1.2 Configuration Parameters € 4.2.1 Control Interfaces ‘Address | Description ‘Change [Detault [Range ofValues | Unt or Meaning Tnere- xy ent 03 1 on ° ora ne yee 03 3 on faseve |o.co .+. 9999 1.00 © 1.2.2 Binary Inputs ‘Address | Description ‘Change [Default [Range ofValues | Unit or Meaning tere xy ment — se or |me: ret. assigns. UL = = Se 04 [nes et. seston, U2 5 e003 sou fore 4038 s080 operating mode Ui a ora Operating node U2 i ora ©1.2.3 Binary Outputs ‘Address | Deseription a Ee ‘Range of Values ‘Unit or Meaning incre xy ment 5201 Ki - = 81 03 i agsigan. KZ = 51 08. Geese. 3 Z ~ “em . BRIN: Trip commana oMr/DTOC! Droc: 22> elapsed def. at/piOc: “e155 elapsed CBE: eCBF elapsed TOME/DTOS: LIND> lapsed Bar/roc! Seareing >> siisis/5>, NCB) 97 IND fDat/Broc! Stare-i> V 26> SMT: i> elapsed inv. 2 EMT. GING elapsed inv 2 1) DTOC protection made only 2)IDMT protection mede only, sscsara4o102 1517512643600 73 C Address List (continued) €1.2.4 LED Indicators ‘Address | Description [change [Detaut [Range ofvatues | Unitor Neaning inere- xy ment 57 01 [usp fot. assagm. #2 |- 36.70 3670 fou: Wazning 5703 |LeD: Fee. agesgnm #2 |= eles ees MAIN: Bloskes/ faulty Fer. assigns. hs [ose = = iehout Fonction er. asesgnn. He [ote - «000 ibet/ot0c: Gen. starting Fot. assign. HS [oft : $003, Gee: Inpst Ext feign. He [SEE = t008 NAD: Trip comand feel Seeignm He? [SEE ne £008 YDet/oTec: Starting A Fee we [eee = 008 rve/ Bree: £007 roer/otec: toos Ien/at0e: soe Dtoct ti> elapsed eet FE corn Thver/otoc: “er sors Toet/ot0c: 4022 coe: eces toze Tbez/Stee: e2x>> elapsed 023 TDHr/ot0c: Stazesne I> 031 IDet/Bt0c: e2(B)>/5>. 032 YDME/DTOC: SIN(3)2/T>> e035 Thwr/or0c: Staze.r> v TB> soso Tbr: tro elapsed inv 2 fest TDP: tune elapsed fav 2 toso kam: Hf pisek xt 4) DTOC pretecton mede only 2)IDMT protection mode oni 74 weer sonsoneens Sets 046608 C Address List (continued) 4.3 Function Parameters 1.3.4 Global aoe 7 30 ve ageignn. Tespi/2 Moun: Latehing mode 1/2 MAIN: Fet-asetgnn.Tetp2/2 MAIN: Latching node 2/: MAIN: Block mode MAIN: Outp.rel. Block USR ott ott Jott Range of Values | Unit or Meaning Tere ment ova no (nett) / yee (ron) 7 356 Tames a ior Sin i, 83 ny with Ty 12, 13 OMT} when changed ne Bleakage se IND, 21ND 512024010021 SLTS 1204096 5 C Address List (continued) €1,3.2. DTOC Protection Mode ‘Adéreas | Description [Change [Detaut [Range of Values | Unit or Neaning = zy ment 76 enesrsr24o1 an S15 000% C Address List (continued) € 1.3.3 IDMT Protection Mode Default | Range of Values category Tay isee ime delay [inv 3 17 38 | reer: character.t on fa.on foro... 1.00 o.08 a7 66 |wsan: ane cange . = Te 16 ois Tnce, C Address List (continued) 1.3.4 Supplementary Functions Ghange [Detaur [Range of values | Unitor Meaning nere= ment on 00 |c.oo... 9.99 se] s oer fur Yessucing Circus 27 23 | wos: trem. on | 5.00 5S T.8 33.9 2728 0.80 2.80 |x,nem 0.08 78 coe sozaon.c .78 12.880 C Address List (continued) © 2 Operation 24 Operating Value Measurement ‘Address | Description ‘Change [Default [Range ofValues | Unitor Meaning xy. i 9,00 +. 18.00, 9.00 21! 18!00 Range of values © 2.2.2 Binary Inputs ‘Address | Description ‘Change | Defautt | Range of Values [een ncre- xy ment © 2.2.3 Binary Outputs ‘Address | Description ‘Change [Defautt [Range ofValues | Unit or Meaning There xy ment 51 00 eka : ova snactive/sotive 51 2 ok 2 : ord 51 08 eK : Oya 51 06 eke = ora ona 0-01.09 .78 120486964 79 C Address List (continued) © 2.3 Control and Testing ‘Radress | Description ‘Change [Detaut [Range of Values] Unitor Weaning tnere- xy ment os og |rnsc: naset sig. memory — [on ° 0... 9999 [Reser : ox key 03 08 |uoN: Reset non. sig. nem. [on ° ost) 30 [Reser : 2x E Key 02 10 |oc: value change enable fon ° orn ne / yes 0339 | MAIN: Warm restare oft ° orn ne / yes 03 40 |aman: Man. tetp ond. use fon ° ora no / yes a7 €2 |wnaw: A/D offset ads one ° orn ne / yes 2209 [wanes Rese: tacen. use or ° ora ne / yes ‘Change [Detautt [Range of Values | Unitor Meaning incre. 0902 |Mow: Mon. etgnat memory |- poseable Eneriee soca [ow raw : 7 Tear 5002 |ow: exeapeton - > To aEne Fete 9003 |uow: earancters a Checkewn error 0.13 MON: Signal nenory 2 Checksum exzor $0 14 [Mow Monitor sig. meno: 3 Chesham estor 0 21 | HON: Operat. wacchdoa : 7 Reset $0 22 |Mow: Aux. voltage : 8 Power fail w/o HW reset 50 26 |Mow: tocar system conse. |= 2 Checkoue, $027 [Mow Timer : 3 Not ramming 0 26 yon: Cols restare 5 ° After checksum necking 9830 |uow: Meas.val acquisition |- ° Calibration not carr. out cold / Ween Rees 98 00 |uow: rnsetatizacion ~ 7 Tartar i RAM (external) é Eprom 2 Activate operating systen 1 Pover tasiure ie Gole ressart 80 sce 90240-62676. 1204650 64 C Address List (continued) ©3 Events 34 Event Counters PREC: Signal rom. svesflow NON: waning Sovt/orec: Gen. ste: MAIN: Block outp. re Cer elapsed "Address | Description [Change [Detaut [Range of Values | Unit or Meaning tnre- xy ment 04 05 : oO... 9999 [reset : ax z Key a 04 20 - 011) 9389 Reset via 02 08 i C 3.2 Fault Data Acquisition ‘Address | Description Change [Defauit | Range ofValues | Unit or Meaning incre xy ment oe 21 > 0.00 s o.o2 be 35 : 000 oe, ron 3.3 Fault Signals Description ‘Change [Default [Range ofValues | Unit or Meaning mere ment Signa? nensey e a at D Set Value Record Sheets Serial No. Order No. Diagram No. 89431-0- 89431.401 Nominal device data Inom Va.rom 82 AAC! voc D Set Value Record Sheets (continued) D1 Device Identification D 4.4 Ordering Information IDENT: Device type (00 §0_| IDENT: Auxiliary voltage 00.55 | IDENT: Control voltage D 4.2 Design Version 0200 | IDENT: Data model 101 0218 | IDENT: SW version L 1.0x Version number 83, D Set Value Record Sheets (continued) D2 Configuration Parameters D241 Control interface 0311 |LOG: Access lock active ee SAE a Lae ce en ne oS Bene eee | 0313 |LOG: Autom. retum addr. D22 Binary Inputs Aare Toe op we Ge le eaae baled ay oe - 5401 | INP: Fet. assign. U4 5404 | INP: Fet. assignm. U2 5402 | INP: Operating mode U1 5405 _|INP: Operating mode U2 D 23 Binary Outputs i Se OUTP: Fet. assign. K1 oe OUTP: Fet. assignm. K2 OUTP: Fet. assignm. K3 OUT: Fet. assignm. K 4 D24 LED Indicators a ee 5701 _ | LED: Fet. assignm. H1 MON: Waming eee a 5703 _| LED: Fet. assignm. H2 MAIN: Blocked/faulty 8705 | LED: Fet. assignm. H3 8707 | LED: Fet, assignm. H4 5709 | LED: Fet. assignm. H§ 8711 _[LED: Fet, assignm. H6 8713 _|LED: Ft. assignm. H7 5715 | LED: Ft, assignm. H8 D Set Value Record Sheets (continued) D3 Function Parameters D31 Global " Adaress | ee pen ivalue ee ee ic en 17.27 _|MAIN: Gen. star. mode 17 28_| MON: Meas. circ. monitor 1731 | MAIN: 1732 _ | MAIN: Latching mode 1/2 1733 _[MAIN: Fotassignm.Trip2/2 17.34 | MAIN: Latching mode 2/2 1761 _ | MAIN: Protection mode 17.90 |MAIN: Block mode E1 1792 _| MAIN: Block mode E2 2114 _[MAIN: Outp.rel, block USR ‘ct.assignm.Tript/2 anc senor. /6t78 12048596 85 D Set Value Record Sheets (continued) 13.2 DTOC Protection Mode 4701 _| |DMT/DTOC: b> 4703 | DTOC: IN> | 1704 | DTOC: t> s 4706 | IDMT/DTOC: t>> 5 17.08 | IDMT/DTOC: tIN> s 4709 | IDMT/DTOG: IN>> Thom 4710 | IDMT/DTOG: tIN>> Unit orMea 1701 | IDMTIDTOC: b> 17.06 _| IDMT/DTOG: ti>> 5 17.08 | IDMT/DTOC: tIN> s 1708 _|IDMT/DTOG: IN> = 17 10_| IDMT/DTOG: tIN>> 5 1713 |1OMT: 1B te 1714 _[IDMT: INB Thom 17.35 | IDMT: Character. type L 17:36 | IDMT: Character.factor kL 1737 | IDMT: Charact. category N 17:38 _| IDMT: Character. type N 1739 | IDMT: Character.factor kG 17.64 | MAIN: INB range 86 D Set Value Record Sheets (continued) 3.4 Supplementary Functions Circuit Breaker Failure Protection: ‘Measuring Circuit Monitoring: fan beret 1724 |MON: Imem> nom 47.23 | MON:tmem> = soe. s0n4mr 2/66 1204196 7 E Terminal Connection Diagram A? GH bess, 43 4 BBVWBWOB Fo] mtn saloceeetesity ES tomros Starting & eee vino situ estcig¢ vbniFotet «Svartueg Gh ES vines eee | Bio ratte TEEN Hreecee—t Jeger vetene seat |ma s dese ttch ints mae fly salack set eal Cc ih MH OC ro ste 36 Terminal connection clara for PS 431, dagram 89431-407 E 88 s 3 3 fe 23 i Ha 2 locus Protection systems for ALSTOM Soles Offices with power generation; System Protection Specialists istribution serine GEC AISTHOM TED S.A. Hong Kong GEC AISTHOM TED re Lavelle 3568 1603, Protection & Control Ville arto Rm, 2006-760 Wu Building P. de Buenos Aires 302-308 Hennessy Rood Phone +541730-1800, Wanchai, GPO Box 15 Far 54730-1529 Hong Keng Phone 485228336265 Fox +85228345279 “Rutolia GECASTHOMTED Trdia GEC ALSTHOM india Ud : « 25 Princes Rd. POB 22 Fellovaram works Supervision equipment for the Regents Park 19/1, GST Road Pallavarem ‘i Nsw2143 ‘adas-600048 monttoring/of ground faults, Phone +61296450735 Phone +91442360621 insulation, currents, Fox +61297438488 Fox +91442367276 Brea GEC AISTHOM TED Poland GEC ALSTHOM TaD voltages, frequency and agen eee reverse power Protection & Control Straogomske 23/27 ‘A Inverlogos, 42111 158-160 Swibodsice 04661-300 S00 Paulo Phone +4874548410, Phone 55115241044 Fox 44874541692 Fox + 55115483429 Canada GEC ALSTHOM GECALSTHOM Soles Network In 35-37 Eleventh Road Integrated control and 5112 Timberle Sve Kew, Johannesburg, 2090 protection systems for Mississauga Phone +271 18853240 . Onorio LaW.285 Fox271 188511 substations ILS® Phone +1905-6248300 eee Fox + 1905.6248855 Englond GEC AISTHOM TAD Span GECALSTHOM Protection & Contrel Limited Soles Network SA St Leonard Works Poxeo dela Cestellano, Stfford STI 741K 257 Phone #+441785-223251 28046 Mocks Fox + 441785-212232 Phone +341334.59.50 Fox 341934.59 51 Fronce GECATSTHOMTED USK GEC ALSTHOM TED Protection & Contrele 4 Sloline Drive ‘Avenue de Figures, Hawthome BP 75 New York 10592-2160 54975 Lottes Codex Californie 90034 Phone 43346720.5526 Phono +1-914347-5166 NS® is o registered trade-mork of Fox +3346720-5584 Fox +1-914347-5508 ALSTOM Energictechnile GmbH 07980 ‘Addresses of more tales offices and countries on request Please visit our World Wide Web site in the Internet: http://ourworld.compuserve.com/homepages/slt_f ALSTOM Energietechnik GmbH Bereich Schutz- und Schaltanlagenleittechnik Lyoner StraBe 44-48 D-60528 Frankfurt Postfach 71 01 07 D-60491 Frankfurt Phone +49 69 66 32-15 21 Fax +49 69 66 32-25 48 ASV 12.04950/0899EN Printed in Germany Contents Subine to Change ALSTOM AISTOM Energjetechrik Gb BarechSchute- und Schatonloyenetechnk yore Srfie 4448 -D- 60528 Fen - Postfach 710107 0-60491 Forkfud (069) 6632-1821 - Tlan: 069) 6632-25 48

You might also like