Single Line Riser Diagram: Watts Volts

The document details the load computation for electrical outlets at Biliran Province State University, including specifications for lighting, convenience, and air conditioning outlets. It outlines the required wire sizes, conduit types, and electrical notes for installation compliance with local codes. The total computed current is 55.91 amperes, with specific instructions for installation and verification by a licensed electrical engineer.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views1 page

Single Line Riser Diagram: Watts Volts

The document details the load computation for electrical outlets at Biliran Province State University, including specifications for lighting, convenience, and air conditioning outlets. It outlines the required wire sizes, conduit types, and electrical notes for installation compliance with local codes. The total computed current is 55.91 amperes, with specific instructions for installation and verification by a licensed electrical engineer.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

LOAD COMPUTATION

CKT OUTLETS PROTECTION WIRE SIZE


LOAD DESCRIPTION LO CO OTHER
WATTS VOLTS AMPERE AT POLE (THHN) CONDUIT
NO.

1 LIGHTING OUTLET 12 1200 220 5.45 15 2 2 - 2.00 SQ.MM 15 MMØ PVC


ELECTRICAL NOTES:
15 MMØ PVC
1. ALL ELECTRICAL INSTALLATION WORKS HEREIN
2 LIGHTING OUTLET 9 900 220 4.09 15 2 2 - 2.00 SQ.MM
SHALL BE DONE IN ACCORDANCE WITH THESE
3 CONVENIENCE OUTLET 6 1080 220 4.91 20 2 2 - 3.50 SQ.MM 15 MMØ PVC PLANS & SPECS, AND YHE APPLICABLE
PROVISIONSOF THE LATEST EDITION OF THE
4 CONVENIENCE OUTLET 9 1620 220 7.36 20 2 2 - 3.50 SQ.MM 15 MMØ PVC PHILIPPINE ELECTRICAL CODE, IT'S RULES AND
REGULATIONS, OF THE LOCAL ENFORCING
15 MMØ PVC
5 AIRCON OUTLET 1 1500 220 6.82 20 2 2 - 3.50 SQ.MM AUTHORITY & THE REQUIREMENTS OF THE LOCAL
6 AIRCON OUTLET 1 1500 220 6.82 20 2 2 - 3.50 SQ.MM 15 MMØ PVC
POWER COMPANY. THE ELECTRICAL WORK SHALL
BE UNDER THE EMMEDIATE SUPERVISION OF A
7 SPARE (Water Pump Motor Outlet) 1 1500 220 6.82 30 2 2 - 3.50 SQ.MM 15 MMØ PVC DULY LICENSED PROFESSIONAL ELECTRICAL
ENGINEER.
8 SPARE 1 1500 220 6.82 30 2 2 - 3.50 SQ.MM 15 MMØ PVC

1
2. ALL WIRES SHALL BE COPPER & THERMOPLASTIC
2 - 3.50 SQ.MM 15 MMØ PVC
9 SPARE 1500 220 6.82 30 2
INSULATEDTYPE "THHN" UNLESS OTHERWISE
TOTAL 12300 220 55.91 60 2 2 - 5.50 SQ.MM 25 MMØ PVC INDICATED. USE PHELPS DODGE OR COLUMBIA
BRAND.
TOTAL COMPUTED CURRENT (I) = 55.91 AMPERES @ 85%DF
= 47.52 AMPERES
3. THE CONTRACTOR SHALL VERIFY & ORIENT THE
ACTUAL LOCATION OF SERVICE ENTRANCE FOR
USE : 2 - 5.5 SQ.MM (#10 AWG), THHN COPPER WIRE IN 25 MM (1 " DIA.) PVC PIPE CONNECTION TO THE POWER SUPPLY.
WITH 60 AT MAIN CIRCUIT BREAKER, 100 AF, SINGLE PHASE, 220 V, 60 HZ
4. ALL FEEDERS & BRAND CIRCUIT HOMERUNS
SHALL BE INSTALLED AS INDICATED ON THE PLANS.
BRAND CIRCUIT HOMERUN WIRES SHALL BE
INSTALLED IN INDIVIDUAL HOMERUN CONDUITS.
5. ANY DISCREPANCY IN LOCATION & RAINGS OF
EQUIPMENT AND/OR APPARATUS TO BE INSTAALED
HSALL BE VERIFIED ITH THE OWNER OR HIS
POWER SUPPLY
SINGLE PHASE
AUTHORIZED
220 VOLTS, 60 HZ REPRESENTATIVE, & CHANGES SHALL BE AMDE
ACCORDINGLY.
2-5.50MM² (#10 AWG) THHN COPPER
WIRE IN 25MM (1 " DIA.) PVC PIPE
6. ALL MATERIALS & EQUIPMENT TO BE USED &
INSTALLED SHALL BE BRAND NEW, OF THE
60 AT
LIGHTING OUTLET
APPROVED TYPE FOR THE LOCATION AND
LIGHTING OUTLET
15AT
CONVENIENCE OUTLET
1
PURPOSE INTENDED.
2 15AT 20AT 3 7. ALL POWER & CONVENIENCE OUTLETS SHALL BE
4
CONVENIENCE OUTLET AIRCON OUTLET
5
GROUNDING SUPPLY.
20AT 20AT
AIRCON OUTLET
SPARE
7
6 20AT 30AT
(Water Pump Motor Outlet)
8. ENTRANCE SERVE SHALL BE INSTALLED IN
8
SPARE
30AT 30AT
SPARE
9 ACCORDANCE WITH THE REGULATION OF THE
LOCAL POWER CO.
GROUND
9. INCOMING POWER SHALL BE 220V. 60CYCLE
SINGLE PHASE , 2- WIRES

10. INCASE OF DOUBT CONSULT THE ELECTRICAL


ENGINEER IN CHARGE FOR VERIFICATION AND
1 SINGLE LINE RISER DIAGRAM DECISION...
A-5 NOT TO SCALE

SCHOOL: SHEET CONTENT: CHECKED BY: DRAFTED BY: SHEET NO:

BILIRAN PROVINCE STATE UNIVERSITY SINGLE RISER DIAGRAM


ENGR. DHAN NIÑO S. SABOCOJAN ROMA GRACE B. ROMERO
SCHOOL OF ENGINEERING LOAD COMPUTATION
ELECTRICAL NOTES INSTRUCTOR CE 313 ENGINEERING UTILITIES 1 BSCE 3B A-5
BS IN CIVIL ENGINEERING