Single Line Riser Diagram: Watts Volts
Single Line Riser Diagram: Watts Volts
1
2. ALL WIRES SHALL BE COPPER & THERMOPLASTIC
2 - 3.50 SQ.MM 15 MMØ PVC
9 SPARE 1500 220 6.82 30 2
INSULATEDTYPE "THHN" UNLESS OTHERWISE
TOTAL 12300 220 55.91 60 2 2 - 5.50 SQ.MM 25 MMØ PVC INDICATED. USE PHELPS DODGE OR COLUMBIA
BRAND.
TOTAL COMPUTED CURRENT (I) = 55.91 AMPERES @ 85%DF
= 47.52 AMPERES
3. THE CONTRACTOR SHALL VERIFY & ORIENT THE
ACTUAL LOCATION OF SERVICE ENTRANCE FOR
USE : 2 - 5.5 SQ.MM (#10 AWG), THHN COPPER WIRE IN 25 MM (1 " DIA.) PVC PIPE CONNECTION TO THE POWER SUPPLY.
WITH 60 AT MAIN CIRCUIT BREAKER, 100 AF, SINGLE PHASE, 220 V, 60 HZ
4. ALL FEEDERS & BRAND CIRCUIT HOMERUNS
SHALL BE INSTALLED AS INDICATED ON THE PLANS.
BRAND CIRCUIT HOMERUN WIRES SHALL BE
INSTALLED IN INDIVIDUAL HOMERUN CONDUITS.
5. ANY DISCREPANCY IN LOCATION & RAINGS OF
EQUIPMENT AND/OR APPARATUS TO BE INSTAALED
HSALL BE VERIFIED ITH THE OWNER OR HIS
POWER SUPPLY
SINGLE PHASE
AUTHORIZED
220 VOLTS, 60 HZ REPRESENTATIVE, & CHANGES SHALL BE AMDE
ACCORDINGLY.
2-5.50MM² (#10 AWG) THHN COPPER
WIRE IN 25MM (1 " DIA.) PVC PIPE
6. ALL MATERIALS & EQUIPMENT TO BE USED &
INSTALLED SHALL BE BRAND NEW, OF THE
60 AT
LIGHTING OUTLET
APPROVED TYPE FOR THE LOCATION AND
LIGHTING OUTLET
15AT
CONVENIENCE OUTLET
1
PURPOSE INTENDED.
2 15AT 20AT 3 7. ALL POWER & CONVENIENCE OUTLETS SHALL BE
4
CONVENIENCE OUTLET AIRCON OUTLET
5
GROUNDING SUPPLY.
20AT 20AT
AIRCON OUTLET
SPARE
7
6 20AT 30AT
(Water Pump Motor Outlet)
8. ENTRANCE SERVE SHALL BE INSTALLED IN
8
SPARE
30AT 30AT
SPARE
9 ACCORDANCE WITH THE REGULATION OF THE
LOCAL POWER CO.
GROUND
9. INCOMING POWER SHALL BE 220V. 60CYCLE
SINGLE PHASE , 2- WIRES