Technical sheet-UCA

The document provides technical specifications for various models of cooling units, detailing their performance metrics such as air volume, total and sensible cooling capacities at different return air temperatures and humidity levels. It includes data for models UC*0221, UC*0281, UC*0341, UC*0401, and UC*0481, highlighting parameters like ESP, Pvent, and cooling capacities gross of fan motor gains. The note emphasizes that to obtain net values, Pvent should be deducted from the indicated total and sensible capacities.

Uploaded by

Yalcin Dogrul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views2 pages

Technical sheet-UCA

The document provides technical specifications for various models of cooling units, detailing their performance metrics such as air volume, total and sensible cooling capacities at different return air temperatures and humidity levels. It includes data for models UC*0221, UC*0281, UC*0341, UC*0401, and UC*0481, highlighting parameters like ESP, Pvent, and cooling capacities gross of fan motor gains. The note emphasizes that to obtain net values, Pvent should be deducted from the indicated total and sensible capacities.

Uploaded by

Yalcin Dogrul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

35ºC (Text) 0% Glycol

Model UC*0221, MRA0221 UC*0281, MRA0281 UC*0341, MRA0341


ESP – Pa 0 50 100 0 50 100 0 50 100
Pvent – kW 0.34 0.34 0.34 0.34 0.34 0.34 0.44 0.44 0.44
Air Volume
l/s 514 475 430 610 470 430 610 575 536
3
m /h 1850 1710 1550 2200 1710 1550 2200 2070 1930
cfm 1089 1007 912 1295 1007 912 1295 1218 1136
24°C Return Air Temperature 40% RH
Total – kW 6.4 6.3 6.1 7.6 7.5 7.4 8.7 8.6 8.5
Sensible – kW 6.4 6.3 6.1 7.6 7.5 6.0 8.7 8.6 8.3
24°C Return Air Temperature 50% RH
Total – kW 5.7 5.6 5.5 7.0 6.9 6.8 8.0 7.9 7.8
Sensible – kW 5.7 5.6 5.2 6.3 6.0 5.8 7.3 7.0 6.8
26°C Return Air Temperature 50% RH
Total – kW 5.9 5.8 5.7 7.2 7.1 7.0 8.2 8.1 8.0
Sensible – kW 5.9 5.8 5.7 6.9 6.6 6.3 8.0 7.7 7.4
28°C Return Air Temperature 50% RH
Total – kW 6.2 6.1 5.9 7.4 7.2 7.1 8.4 8.3 8.2
Sensible – kW 6.2 6.1 5.9 7.4 7.2 6.9 8.4 8.3 8.2
ESP: Delivery pressare
Pvent: Fan absorbed power
T ext: Outdoor temperature
Note: The cooling capacities of the units are gross of fan motor gains; to obtain net values deduct Pvent from the Total and Sensible
capacities indicated.

Model UC*0401, MRA0401 UC*0481, MRA0611


ESP – Pa 0 65 0 65
Pvent – kW 0.65 0.65 0.97 0.97
Air Volume
l/s 720 610 1080 900
3
m /h 2600 2200 3900 3250
CFM 1530 1295 2296 1913
24°C Return Air Temperature 40% RH
Total – kW 9.9 9.5 13.8 13.2
Sensible – kW 9.9 9.5 13.8 13.2
24°C Return Air Temperature 50% RH
Total – kW 10.1 10.0 13.9 13.6
Sensible – kW 9.2 8.5 13.5 12.2
26°C Return Air Temperature 50% RH
Total – kW 10.4 10.2 14.4 14.0
Sensible – kW 10.1 9.2 14.4 13.3
28°C Return Air Temperature 50% RH
Total – kW 10.8 10.4 15.1 14.4
Sensible – kW 10.8 10.1 15.1 14.4
ESP: Delivery pressare
Pvent: Fan absorbed power
T ext: Outdoor temperature
Note: The cooling capacities of the units are gross of fan motor gains; to obtain net values deduct Pvent from the Total and Sensible
capacities indicated.

NOTE: * may be A (mechanical cooling) or F (mechanical cooling and free-cooling).

990-5081A-001 Uniflair UCA, UCF, UWA, UWF, MRA Technical Specifications 17


06ME012@00B0120
40ºC (Text) 0% Glycol
Model UC*0221, MRA0221 UC*0281, MRA0281 UC*0341, MRA0341
ESP – Pa 0 50 100 0 50 100 0 50 100
Pvent – kW 0.34 0.34 0.34 0.34 0.34 0.34 0.44 0.44 0.44
Air Volume
l/s 514 475 430 610 470 430 610 575 536
3
m /h 1850 1710 1550 2200 1710 1550 2200 2070 1930
CFM 1089 1007 912 1295 1218 1136 1089 1007 912
24°C Return Air Temperature 40% RH
Total – kW 5.5 5.4 5.3 6.6 6.4 6.3 7.5 7.4 7.3
Sensible – kW 5.5 5.4 5.3 6.6 6.4 6.3 7.5 7.4 7.3
24°C Return Air Temperature 50% RH
Total – kW 5.5 5.4 5.3 6.7 6.6 6.5 7.6 7.6 7.5
Sensible – kW 5.5 5.4 5.2 6.2 5.9 5.6 7.1 6.9 6.6
26°C Return Air Temperature 50% RH
Total – kW 5.7 5.6 5.5 6.8 6.8 6.7 7.8 7.7 7.7
Sensible – kW 5.7 5.6 5.5 6.8 6.5 6.2 7.8 7.7 7.3
28°C Return Air Temperature 50% RH
Total – kW 6.0 5.9 5.9 7.1 7.0 6.8 8.1 8.0 7.9
Sensible – kW 6.0 5.9 5.8 7.1 7.0 6.8 8.1 8.0 7.9
ESP: Delivery pressare
Pvent: Fan absorbed power
T ext: Outdoor temperature
Note: The cooling capacities of the units are gross of fan motor gains; to obtain net values deduct Pvent from the Total and Sensible
capacities indicated.

Model UC*0401, MRA0401 UC*0481, MRA0611


ESP – Pa 0 65 0 65
Pvent – kW 0.65 0.65 0.97 0.97
Air Volume
l/s 720 610 1080 900
3
m /h 2600 2200 3900 3250
CFM 1530 1295 2296 1913
24°C Return Air Temperature 40% RH
Total – kW 9.6 9.2 13.3 12.7
Sensible – kW 9.6 9.2 13.3 12.7
24°C Return Air Temperature 50% RH
Total – kW 9.7 9.6 13.3 13.0
Sensible – kW 9.1 8.3 13.3 11.9
26°C Return Air Temperature 50% RH
Total – kW 10.0 9.9 13.9 13.2
Sensible – kW 10.0 9.1 13.9 13.2
28°C Return Air Temperature 50% RH
Total – kW 10.4 10.0 14.5 13.8
Sensible – kW 10.4 10.0 14.5 13.8
ESP: Delivery pressare
Pvent: Fan absorbed power
T ext: Outdoor temperature
Note: The cooling capacities of the units are gross of fan motor gains; to obtain net values deduct Pvent from the Total and Sensible
capacities indicated.

NOTE: * may be A (mechanical cooling) or F (mechanical cooling and free-cooling).

18 Uniflair UCA, UCF, UWA, UWF, MRA Technical Specifications 990-5081A-001


06ME012@00B0120