Electrical Plan

The document outlines the electrical plans for a proposed two-storey residential house, including a single line diagram, service drop conductor specifications, and general notes on electrical work compliance. It details the power source, circuit breakers, and various electrical symbols used in the layout. Additionally, it emphasizes adherence to the Philippine Electrical Code and specifies minimum wire sizes and installation guidelines.

Uploaded by

anjieaquino29
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views3 pages

Electrical Plan

The document outlines the electrical plans for a proposed two-storey residential house, including a single line diagram, service drop conductor specifications, and general notes on electrical work compliance. It details the power source, circuit breakers, and various electrical symbols used in the layout. Additionally, it emphasizes adherence to the Philippine Electrical Code and specifies minimum wire sizes and installation guidelines.

Uploaded by

anjieaquino29
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

1 2 3 4 1 2 3 4 SINGLE LINE DIAGRAM

SERVICE DROP CONDUCTOR:


1375 7000 1375 7000 TWO 38.0mm² THW WIRE
POWER SOURCE:
230V, SINGLE PHASE, 60HZ
3500 3500 3500 3500 LINE TO LINE
M
SERVICE ENTRANCE CONDUCTOR:
NEMA 1 ENCLOSURE WITH TWO 38.0mm² THHN WIRE IN
CENTER MAIN 40mmØ PVC CONDUIT
c d e
MAIN
125 AT, 2P (BOLT-ON TYPE CIRCUIT BREAKER)
15 AT 15 AT

L.O. 1 2 L.O.
15 AT 15 AT

L.O. 3 4 L.O.
15 AT 15 AT

L.O. 5 6 L.O.
15 AT 15 AT

L.O. 7 8 L.O.
15 AT 15 AT
e d c L.O. 9 10 L.O.
20 AT 20 AT

b f
E j
E C.O. 11 12 C.O.
g i f b 20 AT 30 AT
h S2 C.O. 13 14 ACU
c d i h 30 AT 30 AT

ACU 15 16 ACU
f b 9 30 AT 30 AT
5
g h i ACU 17 18 ACU
a a j
4055

4055

4055

4055
30 AT 30 AT
e
f
ACU 19 20 ACU
20 AT 30 AT
e c
S3 WATER PUMP 21 22 SPARE
4 e g
b f 1 - 14.0mm² THHN WIRE (G)
c 16mmØ x 3m, GROUNDING ROD
d S2 a b d COPPER WELD
a S2 S2
D S3 D
S3W d e
g g S3W a ELECTRICAL SYMBOLS:
j j PANEL BOARD ENCLOSURE
2nd
10
2531

2531
c f i SINGLE PHASE POWER SOURCE / NORMAL SOURCE
S1
CIRCUIT BREAKER
a h

4161

4161
12436

12436
S3 S2 l
S3W k M KILOWATT-HOUR METER
b 3 8
C' S1 C' CONDUIT
h g
h g
i UNDERGROUND/CONCEALED
1630

1630
1
15475

15475
k S1 e f SWITCH LINE
i S1
C S3 C 1 CIRCUIT HOMERUN
c S3 S3 n DUPLEX CONVENIENCE OUTLET/RECEPTACLE (GROUNDING
j h
TYPE)
b a
WEATHER PROOF DUPLEX CONVENIENCE OUTLET (GROUNDING
6 b d WP
TYPE)
h d
WP WATER PUMP OUTLET
i b c c b CONVENIENCE OUTLET WITH GROUNDING FAULT CIRCUIT
GFCI
4220

4220

4220

4220
INTERRUPTER (FOR LAUNDRY & WATER HEATER)
a c
ACU AIR CONDITIONING UNIT OUTLETSAMPLE

S1 1 GANG, SPST, FLUSH TYPE SWITCH


g a
e d e
S3 7 S2 2 GANG, SPST, FLUSH TYPE SWITCH
h d m
S3 3 GANG, SPST, FLUSH TYPE SWITCH
S3 S3 k S1
B 2 B i
1 GANG, THREE WAY SWITCH, FLUSH TYPE
S3w
f
SURFACE TYPE LED LIGHT
a f j k l
CHANDELIER LIGHT
3039

3039

3039

3039
g
e CIRCULAR LED LAMP, DAYLIGHT, SURFACE TYPE

LED PINLIGHT, DAYLIGHT, RECESSED TYPE

LED PINLIGHT, DAYLIGHT, SURFACE TYPE


f g
j
A A LED ROPE LIGHT

h i CHANDELIER LIGHT WITH CEILING FAN

3520 2445 2410 3520 2445 2410 GROUNDING ELECTRODE

WALL LAMP (OUTDOOR)


1 2' 3' 4 1 2' 3' 4
WALL LAMP (TRACK LIGHT)
- GROUND FLOOR LIGHTING LAYOUT - SECOND FLOOR LIGHTING LAYOUT LED LIGHTING FIXTURE ( FOR SINK)
- SCALE: 1:90 mtrs. - SCALE: 1:90 mtrs.

PRC REG. No.: PROJECT: APPROVED: SHEET CONTENTS: SHEET NO.

- GROUND FLOOR LIGHTING LAYOUT


PTR No.:

PROPOSED TWO STOREY RESIDENTIAL HOUSE


- SECOND FLOOR LIGHTING LAYOUT E-1
ISSUED IN:
MR. & MRS. ANJIE P. AQUINO
ELECTRICAL ENGINEER / MASTER ELECTRICIAN
ISSUED ON: LOCATION:
- OWNER 1 3
1 2 3 4 1 2 3 4
1375 7000 1375 7000 GENERAL NOTES:
3500 3500 3500 3500
1. ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH
THE PROVISION OF THE LATEST EDITION OF THE PHILIPPINE
ELECTRICAL CODE, EXISTING APPLICABLE ORDINANCES,
RILES AND REGULATIONS OF THE LOCAL GOVERNMENT AND
THE REQUIREMENTS OF THE LOCAL POWER COMPANY.

2. THE TYPE OF SERVICE POWER SUPPLY TO BE USED SHALL


BE SINGLE-PHASE, 2-WRE GROUND, 230V, 60HERTZ, A.C.

3. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL


LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO THE
POWER COMPANY.

4. UNLESS OTHERWISE SPECIFIED, THE MINIMUM SIZES OF


WIRE AND GALVANIZED RIGID STEEL CONDUIT TO BE USED
E E SHALL BE 3.5mm², THHN AND 15mm NOMINAL DIAMETER,
GFCI RESPECTIVELY. LIKEWISE ALL ELECTRICAL WIRES SHALL BE
ACU WP ACU ACU COLOR CODED.
14 21
13 5. ALL LIGHTING CIRCUIT HOMERUNS AND CONVENIENCE
REF RH 17 18 OUTLETS SHALL BE WIRED WITH NOT LESS THAN 2.0mm² IN
SIZE.
4055

4055

4055

4055
6. WHEREVER REQUIRED AND NECESSARY, PULL OR JUNCTION
BOXES SHALL BE INSTALLED AT CONVENIENT AND
11 INCONSPICUOUS LOCATION, ALTHOUGH SUCH BOXES ARE
NOT SHOWN ON THE PLAN NOR MENTIONED IN THE
SPECIFICATIONS.

D D 7. ALL NON-CURENT CARRYING METAL PARTS OF ELECTRICAL


ACU EQUIPMENT SHALL BE PROPERLY GROUNDED IN
15 ACCORDANCE WITH THE PROVISIONS IN ARTICLE 2.50
:GROUNDING" PHILIPPINE ELECTRICAL CODE, VOLUME 1, 2017
2531

2531
WP EDITION.

8. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF

4161

4161
12436

12436
WP
THE APPROVED TYPE FOR LOCATION AND PURPOSE.
ACU
C' C'
9. STANDARD TYPE OF ACCESSORIES, SPLICING DEVICES,
WP TERMINATIONS AND OTHER APPURTENANCES FOR THE
19
1630

1630
WP ENTIRE ELECTRICAL INSTALLATION SHALL BE USED.
15475

15475
10. ALL WALL OUTLETS SHALL BE INSTALLED AT THE FOLLOWING
C C HEIGHTS ABOVE THE FINISH FLOOR LEVEL UNLESS NOTED IN
ACU
16 ACU THE PLANS.
20 a.) WALL SWITCHES @ 1200mm
b.) WALL CONVENIENCE OUTLETS @ 300mm OR 150mm ABOVE
12 WORKTABLE/COUNTER

11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT


4220

4220

4220

4220
AND IMMEDIATE SUPERVISION OF A DULY REGISTERED
ELECTRICAL ENGINEER.

B B

WP
3039

3039

3039

3039
A A

3520 2445 2410 3520 2445 2410

1 2' 3' 4 1 2' 3' 4

- GROUND FLOOR POWER LAYOUT - SECOND FLOOR POWER LAYOUT


- SCALE: 1:90 mtrs. - SCALE: 1:90 mtrs.

PRC REG. No.: PROJECT: APPROVED: SHEET CONTENTS: SHEET NO.

- GROUND FLOOR POWER LAYOUT


PTR No.:

PROPOSED TWO STOREY RESIDENTIAL HOUSE


- SECOND FLOOR POWER LAYOUT E-1
ISSUED IN:
MR. & MRS. ANJIE P. AQUINO
ELECTRICAL ENGINEER / MASTER ELECTRICIAN
ISSUED ON: LOCATION:
- OWNER 2 3
LOAD CALCULATION USING LOAD SCHEDULE:

PRC REG. No.: PROJECT: APPROVED: SHEET CONTENTS: SHEET NO.

- ELECTRICAL LOAD COMPUTATION


PTR No.:

PROPOSED TWO STOREY RESIDENTIAL HOUSE E-1


ISSUED IN:
MR. & MRS. ANJIE P. AQUINO
ELECTRICAL ENGINEER / MASTER ELECTRICIAN
ISSUED ON: LOCATION:
- OWNER 3 3