This presentation covers the basics of Power Transformers used in KSEBL, focusing on common testing methods. Key topics include name plate details, types of cooling, percentage impedance, temperature indicators, Buchholz relay, oil surge relay, pressure relief valve, and aircell applications. Additionally, it discusses the importance of tertiary windings and earthing transformers.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
22 views23 pages
Power Transformer Basics
This presentation covers the basics of Power Transformers used in KSEBL, focusing on common testing methods. Key topics include name plate details, types of cooling, percentage impedance, temperature indicators, Buchholz relay, oil surge relay, pressure relief valve, and aircell applications. Additionally, it discusses the importance of tertiary windings and earthing transformers.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23
Welcome
Power Transformers Basics
22-10-2019 THE PRESENTATION
This presentation will give you some ideas about Power
Transformers used in KSEBL Concentration will be give to Common Testing methods done in field
Brief Flow of the Presentation.
1. General: Name Plate 2. Type of cooling 3. Percentage Impedance 4. WTI and OTI 5. Buchholz Relay 6. OSR 7. PRV Name Plate Details Please Note • MVA capacity depends on type of cooling • ONAN, ONAF, ODAF • There are certain bushing CT s meant for WTI, OTI Etc • There allowable temperature range provided in name plate • Information about aircell shall be given in name plate or separate plate ONAN ONAF Percentage impedance • The percentage impedance of a transformer is the volt drop on full load due to the winding resistance and leakage reactance expressed as a percentage of the rated voltage. It is also the percentage of the normal terminal voltage required to circulate full-load current under short circuit conditions. WTI and OTI • The WTI means winding temperature Indicator and OTI means Oil Temperature Indicator which indicates the winding temperature & oil temperature of the transformer and operates the alarm, trip, and cooler control contacts.This instrument operates on the principle of thermal imaging and it is not an actual measurement. Buchholz relay OSR Relay • It is mainly used to limit the damage to the on load tap changer in case of failure. OSR is placed in between OLTC(On Load Tap Changer) tank and OLTC conservator. • Oil surge relay responds only by rate of rise pressure resulting from internal arcing. When rate of rise pressure oil cross certain value then alarm and trip contacts operate. OSR relay PRV • The working principle of transformer pressure relief device is very simple. If pressure arises inside a transformer and exceeds a pre-set pressure limit, the pressure safety valve opens its valve clap, which is held by a spring and releases the internal pressure until it declines. Aircel Aircel • APPLICATION : • It is fitted in the conservator of oil filled transformer. It is held in a position by connecting flange and two straps on either side. When oil level in conservator increases, air cell gets deflated thereby expelling air out and when oil level drops, air cell inflates and allows air to come in. Thus air cell breathes without allowing outside air to get in contact with transformer oil.These Air Cells are being supplied to many reputed transformer manufacturers in India. • Aircel Transformer Tertiary Winding ⚫ Tertiary Winding : One point of delta connection shall be connected to Ground It is desirable that a three-phase transformer should have one set of three-phase windings connected in delta thus providing a low-impedance path for third-harmonic currents. The presence of a delta connected winding also allows current to circulate around the delta in the event of unbalance in the loading between phases, so that this unbalance is reduced and not so greatly fed back through the system. Earthing transformer (Used in Middle East countries) • If our transformer 110/11 kv is Star Delta , In order to get the benefit of earthing a special transformer with zig –zag winding is used. It offer very less impedance for zero sequence components. • Such delta 11 kv eliminates the use of tertiary winding • Generally has 440 V 3ph secondary used for aux supply.