Lecture 3
Lecture 3
The 74ALS160-163/74HC160-163
Series
clocked by a PGT applied to CLK.
Two of the counters are MOD-10 counter
while the other two are MOD-16 counter
The 74ALS160-163/74HC160-163
Series
ENT and ENP are essentially ANDed together
to control the count function.
If either or both of the count enable controls is
inactive (LOW), the counter will hold.
The count up with PGT on CLK, all four of the
control inputs must be HIGH.
ENT controls
RCO.
The counter contains four FFs.
– The IC has an active-low asynchronous CLEAR input.
– For these counters to be synchronously cleared, the
CLR input must be LOW and a PGT must be applied to the
clock input.
– The counter can be preset to any value (applied to the A,
B, C, and D inputs) by applying an active-low LOAD input.
– The counter is controlled shown in Figure 7-13c.
Example 1
A 74HC163 has the input signals given in the timing
diagram applied. The parallel data inputs are permanently
connected as 1100. Assume the counter is initially in the
0000 state, and determine the counter output waveforms.
Example 2
A 74HC160 has the input signals given in the
timing diagram applied. The parallel data inputs
are permanently connected as 0111. Assume the
counter is initially in the 0000 state, and
determine the counter output waveforms.
74ALS190 -> 75ALS191 Series
Synchronous Up/Down Counters
To count, the LOAD control input must be
inactive (HIGH) and the count enable control
CTEN must be LOW. The count direction is
controlled by the D/U control input.
Active-LOW Decoding
Using NAND Gates for decoding
Active-HIGH Decoding
How many AND gates are required to decode
completely all of the states of a MOD-32 binary
counter?
1) Control expression