Adaptive Virtual Inertia Control Method Based On Droop Control
Adaptive Virtual Inertia Control Method Based On Droop Control
Droop Control
Lingyu Sun Pengcheng Wang Feng Jiang
Polytechnic Institute College of Electrical Engineering College of Electrical Engineering
Zhejiang University Zhejiang University Zhejiang University
Hangzhou, China Hangzhou, China HangZhou, China
[email protected] [email protected] [email protected]
Abstract—With the increasing proportion of renewable proposed. By adding virtual inertia and damping to the
energy in microgrids, traditional droop control without inertia inverter control, the inverter can simulate the response
2021 IEEE 30th International Symposium on Industrial Electronics (ISIE) | 978-1-7281-9023-5/21/$31.00 ©2021 IEEE | DOI: 10.1109/ISIE45552.2021.9576329
can hardly meet the needs of inverter control. Load changes can characteristics of the traditional synchronous machine
cause sudden changes in the frequency of the microgrid system, [6].However, if the virtual inertia is set too large, the response
which can easily trigger the protection device of the system. The speed of the system will slow down, and it is easy to cause
stable operation of the microgrid is affected. At the same time, system power oscillation. If the virtual inertia is set too small,
if there is a large inertia in the microgrid, it will reduce the sudden changes in frequency will caused in microgrid[7].
response speed of the system and easily cause oscillations. In this
paper, an adaptive inertia control method is proposed. Then, the An low-pass filter is added to the traditional droop control,
stability analysis of the control strategy is carried out. Finally, which has an equivalent control effect with the VSG[5]. By
simulations results verify the correctness and effectiveness of the adjusting the droop coefficient in real time, the virtual inertia
proposed method. of the inverter is dynamically changed to improve the output
characteristics of the inverter in different scenarios. However,
Keywords—droop control, virtual inertia, three-phase inverter, in this type of method, the real-time frequency in the system
rate of change of frequency (ROCOF), virtual synchronous needs to be acquired by the phase-locked loop(PLL) in real
generator (VSG),microgrid time, which requires high speed and accuracy of the phase-
locked loop [8-10].
I. INTRODUCTION
As the proportion of renewable energy in the traditional The frequency change is divided into two states for control
power system increases, it has a negative impact on the stable in[11]. The value of the virtual inertia is set according to the
operation of the power system. In the traditional power frequency offset direction. The value of virtual inertia is set
generation system, the synchronous machine is the main according to the microgrid operation mode[12]. A small
power generation unit. Renewable energy in the power system inertia is used in inverters in the grid-connected mode to
is connected through the inverter. Since there is no inertia in suppress frequency oscillations. In the islanding mode, larger
traditional inverters, the changes of the load will cause the inertia is used to avoid sudden changes in frequency. However,
sudden changes of frequency in the system[1]. The change of these methods lack the analysis of the influence of inertia on
frequency will trigger the protection device in the microgrid the ROCOF, and cannot directly limit the value of the ROCOF.
system, which will have a negative impact on the stable In this paper, an adaptive virtual inertia control method
operation of the system. based on droop control is proposed. The small signal model of
In the microgrid, the inverter adopts droop control, which the inverter with droop control is established. The influence of
has the characteristics of no communication, strong flexibility the change of the time constant in the filter on the stability of
and high redundancy[2-4]. However, traditional droop control the control strategy is analyzed. By designing the parameters
has no inertia. Load changes and power fluctuations will cause of the adaptive virtual inertia, ROCOF in the microgrid is
sudden changes in frequency. Since there are frequency limited. Finally, simulations verify the effectiveness of the
change protection devices in the microgrid, when the proposed control strategy.
frequency change rate exceeds the set threshold, the power
II. COMPARISON OF DROOP CONTROL AND VSG
generation unit will disconnect from the grid [5].
A. Operation principle of droop control
In order to solve the problem of lack of inertia in inverter
control, the concept of virtual synchronous generator(VSG) is The droop control is developed based on the theory of
power flow control. The amplitude and frequency of the
This work was funded by Inner Mongolia Autonomous Region Science output voltage are adjusted by calculating the active and
and Technology Project: 2019GG373, Inner Mongolia Electric Power Group reactive power of the inverter [13].
(Limited) Company Science and Technology Project (issue number:
(Neidian Technology [2020] No. 6)). In addition, we would like to express The circuit topology from the inverter to the AC bus can
our special gratitude to the Microgrid Electrical Equipment and Manufacture be simplified as shown in Fig. 1.
Platform (MEEMP) in the Polytechnic Institute of Zhejiang University, on
which many valuable tests in our paper were performed.
UE
P Z
Q U ( E U )
Z
Authorized licensed use limited to: Universidad Nacional Autonoma De Mexico (UNAM). Downloaded on September 23,2024 at 18:55:50 UTC from IEEE Xplore. Restrictions apply.
1 Fig. 5. Improved adaptive inertia droop control structure
Let J , D , P Pm Pe , formula (6) can be
m0 m The time-domain expression of droop control with low-
expressed as pass filter is shown in equation (9).
d ref P d
J 0
dt
m
Pe D ref
dt
mP
Therefore, the active power droop control equation with a Where: =ref - .
low-pass filter is similar to the active power control equation
of the VSG. The inertia of the inverter can be changed by From ordinary differential equation (9), the relationship
adjusting the parameters of the low-pass filter in the droop between transient output angular frequency and output power
control. can be obtained, as shown in equation (10).
t t
III. ADAPTIVE VIRTUAL INERTIA CONTROL
0 e mP (1 e )
In the microgrid system, the design of virtual inertia
determines the transient response effect of the system and the
stability of the system. Where: 0 is the initial value of the frequency offset.
If the virtual inertia setting in the droop control with a low-
Differentiate to get the relevant influencing factors of
pass filter is too large, it will cause the system's dynamic
response speed to be slow, and may cause power oscillations; ROCOF.
If the virtual inertia is set too small, it will cause large ROCOF,
which will affect the stable operation of the system. Therefore, d mP t t
e e
while suppressing the ROCOF of the system, power dt
oscillation should be avoided. Based on the traditional droop
control strategy, this paper proposes an adaptive virtual inertia Combining formula (8) and formula (11) can be obtained
control strategy.
The topology and control structure of the three-phase d mP 0 -
t
mP m
0
0 KP K
0 0
0
0 +KP 0
0 KP 0 d m
0 dt K
In (7), τ0 is the initial value of the time constant, and K is
the adaptive inertia coefficient. The improved adaptive inertia The design of the parameters m, K and ω0 can realize the
droop control structure is shown in Fig. 5. control of ROCOF in the microgrid system. The inverter
adaptively adjusts the value of inertia according to the output
power to improve the stability of the microgrid system. As the
output power change rate increases, the frequency change rate
gradually increases, and the absolute value approaches m/K
and 0 /τ. The specific parameter design method is
explained in IV.
Authorized licensed use limited to: Universidad Nacional Autonoma De Mexico (UNAM). Downloaded on September 23,2024 at 18:55:50 UTC from IEEE Xplore. Restrictions apply.
IV. STABILITY ANALYSIS AND PARAMETER DESIGN From equation (21), the characteristic equation of control
can be obtained as
A. Output power modeling and stability analysis of the
inverter
s3 As2 Bs C 0
The equivalent circuit of the inverter connected to the
microgrid is shown in Fig. 6. In the figure, output voltage of
the inverter is E∠δ, the line impedance value is XL=R+jωL=X In the formula(22), A, B, C are respectively
∠θ, the AC bus current flowing into the inverter is I, and the
AC bus voltage is U∠0. 2 mU cos
A
X
mU cos nU cos 1
B= 2
X 2X
X m
Active power droop
0.000628
coefficient
Q 1
[( EU cos U 2 )sin EU sin cos ] n
Reactive power droop
0.00311
X coefficient
Time constant of low pass
τ -1~1
filter
When the line impedance is approximately inductive, it
can be approximated as sinθ=1 and cosθ=0. (18) can be
simplified to
EU
P X sin
2
Q EU cos U
X
Authorized licensed use limited to: Universidad Nacional Autonoma De Mexico (UNAM). Downloaded on September 23,2024 at 18:55:50 UTC from IEEE Xplore. Restrictions apply.
L Filter inductance 0.5mH
C Filter capacitor 20μF
m Active power droop coefficient 0.000628
n Reactive power droop coefficient 0.00311
τ0 Initial value of time constant 0.02
K Adaptive inertia coefficient 0.0002
Ri Line resistance 0.1Ω
Li Line inductance 0.5mH
Z load1 Load1 10kW
Z load2 Load2 5kW
Z load3 Load3 5kW
In the initial state, all the switches are in the off state, and
Fig. 8. Droop control characteristic curve the inverters 1 and 2 are in the no-load start state; At 0s, close
switch S1, and put in 10kW load 1. At 1s, inverter b starts to
It can be seen from equation (16) that ROCOF is
perform pre-synchronization until the voltage amplitude,
determined by m and K. In this method, the design of m
frequency and phase of inverter a and b are consistent. At 2.35
determines the power sharing effect of the parallel system and
seconds, inverter 2 completes the pre-synchronization and
the static frequency deviation
closes switch SP at the same time, and inverter 2 is put into
Then by designing the K value, the maximum ROCOF operation in the system. At 4s, the switches S2 and S3 are
during the dynamic change of the load is limited. The design closed at the same time, and the load in the microgrid becomes
of K restricts the maximum value of ROCOF. 20kW. At 7s, the switches S1 and S2 are turned off, and the
load running in the system becomes 5kW.
The specific design method of m and K is shown in
formula(26) and (27). Frequency Hz
)
max min
m
Pmax
m
K
2 rmax Pre-synchronization Parallel Add 10kW load Reduce 15kW load
Time (s)
Where: ωmax is the upper limit of angular frequency, ωmin Fig. 10. Frequency variation waveform of islanded microgrid
is the lower limit of angular frequency. Pmax is the maximum
output power. rmax is the maximum ROCOF of the inverter. ROCOF(Hz/s)
Reduce 15kW load
At the same time, the design of K should verify the Add 10kW load
V. SIMULATION RESULTS
In order to verify the above control strategy, the simulation
software PLECS is used to build a microgrid simulation model ROCOF Hz/s
Time (s)
ROCOF Hz/s
(
Authorized licensed use limited to: Universidad Nacional Autonoma De Mexico (UNAM). Downloaded on September 23,2024 at 18:55:50 UTC from IEEE Xplore. Restrictions apply.
Active power w
established, and stability analysis is carried out. Finally, the
(
)
simulation results verify the effectiveness of the proposed
control strategy.
REFERENCES
[1] J. Driesen and K. Visscher, "Virtual synchronous generators," 2008
IEEE Power and Energy Society General Meeting - Conversion and
Delivery of Electrical Energy in the 21st Century, Pittsburgh, PA, USA,
2008, pp. 1-3.
Pre-synchronization Parallel Add 10kW load Reduce 15kW load
Time (s) [2] M. Gao, M. Chen, C. Wang and Z. Qian, "An Accurate Power-Sharing
Control Method Based on Circulating-Current Power Phasor Model in
Fig. 12. Output power of each inverter Voltage-Source Inverter Parallel-Operation System," in IEEE
Transactions on Power Electronics, vol. 33, no. 5, pp. 4458-4476, May
Current (A) 2018.
[3] W. Yao, M. Chen, J. Matas, J. M. Guerrero and Z. Qian, "Design and
Analysis of the Droop Control Method for Parallel Inverters
Considering the Impact of the Complex Impedance on the Power
Sharing," in IEEE Transactions on Industrial Electronics, vol. 58, no.
2, pp. 576-588, Feb. 2011.
[4] M. Gao, C. Zhang, M. Qiu, M. Chen and A. Levy, "Design of control
(s)
system for smooth mode transfer in smart microgrid application," 2016
IEEE Applied Power Electronics Conference and Exposition (APEC),
Time (s) Long Beach, CA, USA, 2016, pp. 138-142.
Current (A) Current (A)
[5] Soni N, Doolia S, Chandorkar M C. Improvement of Transient
Response in Microgrids Using Virtual Inertia[J]. IEEE Transactions on
Power Delivery, 2013, 28(3): 1830–1838 .
Waveform at parallel time (s) Load current waveform [6] Q. Zhong and G. Weiss, "Synchronverters: Inverters That Mimic
Time (s) Synchronous Generators," in IEEE Transactions on Industrial
Electronics, vol. 58, no. 4, pp. 1259-1267, April 2011.
(a)
[7] Meegahapola L, Flynn D. Impact on transient and frequency stability
Current (A) for a power system at very high wind penetration[C]//IEEE PES
General Meeting.
[8] Rolim L, Alves M, Assis T M L, et al. Virtual inertia impact on
microgrid voltage and frequency control[C]//2018 Simposio Brasileiro
de Sistemas Eletricos (SBSE).
[9] Alipoor J, Miura Y, Ise T. Power System Stabilization Using Virtual
Synchronous Generator With Alternating Moment of Inertia[J]. IEEE
Journal of Emerging and Selected Topics in Power Electronics, 2015,
Time (s) 3(2): 451–458.
Current (A) Current (A)
Authorized licensed use limited to: Universidad Nacional Autonoma De Mexico (UNAM). Downloaded on September 23,2024 at 18:55:50 UTC from IEEE Xplore. Restrictions apply.