Deaerator
Deaerator
BOILERMATE DEAERATORS
CONTENTS
FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-3
PRODUCT OFFERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-4
DIMENSIONS AND RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-6
RETURN ON INVESTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-9
SAMPLE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-10
ILLUSTRATIONS
Figure H3-1. Boilermate Deaerator Dimensions and Ratings - Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-6
Figure H3-2. Boilermate Tank Supports and Saddles, Details and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-8
TABLES
Table H3-1. Cleaver-Brooks Boilermate Deaerator Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-5
H3-1
02-02
Boilermate Deaerators Feedwater Systems
The Cleaver-Brooks designed deaerator assures high purity effluent by removing oxygen and other dissolved gases in boiler feed.
Thus, it is the answer to long-lasting boiler equipment for industrial and commercial boiler users. Built of corrosion-resistant
alloys for lifetime service, the deaerator employs those basic principals of gas removal proven most effective and economical to
every boiler owner. Contact your local Cleaver-Brooks authorized representative for component and sizing information.
H3-2
02-02
Feedwater Systems Boilermate Deaerators
The following features and benefits apply to the Boilermate • Atmospheric contamination virtually eliminated for
Deaerator product line. The Boilermate design uses a packed incoming water.
column to deaerate the water.
Exceeds ASME Recommendations for Oxygen Level:
Less Mechanical Movement of Deaerator Components: • Cleaver-Brooks deaerator is guaranteed to remove oxygen
• The water spray valve is the only internal moving concentrations to 0.005 cc/liter while operating between 5
component within the deaerator vessel. and 100%capacity.
• Carbon dioxide concentration is practically reduced to a
Two-Stage Deaeration in a Common Vessel: zero.
• Recycle pumps are not required.
Integral Level Control Automatically Introduces Cold Water
• Packaged for easy maintenance. Make-Up to Supplement Condensate Only When Necessary to
Meet Boiler Demand:
ASME Code Design (Section VIII):
• Saves Btu’s by accepting condensate before cold make-up
• Assures deaerator vessel quality in materials and fabrication water. Maintains a minimal water level within the deaerator
to meet safety requirements. vessel to prevent damage to the boiler feedpumps, and to
maintain system operation.
Internal Stainless Steel Vent Condenser:
• Protects deaerator vessel against corrosive gases while Variety of Tank Sizes to Handle Volume-Swings in Conden-
providing a means for removal of corrosive gases from sate Return:
boiler feedwater. • Provides flexibility for selecting a tank for specific
applications to limit the loss of hot condensate to drain.
Self-Cleaning Water Spray Valve:
• Maintains deposit-free surface. Packaged Units for Cost Effective Installation:
• Reduces maintenance requirements. • Complete packages are pre-fabricated in the Cleaver- Brooks
manufacturing facility to ensure piping alignment and
control wiring function. The unit is partially disassembled,
Internal Automatic-Check Valve Prevents Steam Back-Flow:
match marked for efficient field re-assembly.
• The water spray valve is normally closed at no flow.
• Prevents steam back flow through the water spray valve at no Internal Pump Suction Vortex Breakers:
flow conditions. • Eliminates the problems of loss in NPSHA and cavitation
associated with the creation of vortices within pump suction
Removable Water Spray Inlet Assembly: piping.
• Flanged assembly allows easy access for maintenance and/
or inspections. Vessel Corrosion Protection When Off-Line:
• Optional epoxy lining.
Stainless Steel Deaeration Assembly:
• Ensures a longer life of wetted materials in intimate contact
with corrosive liquids and released corrosive gases.
H3-3
02-02
Boilermate Deaerators Feedwater Systems
PRODUCT OFFERING • Steam pressure gauge.
The packed column design is best for handling high-tempera- • Low water pump cut off.
ture returns. The column is constructed of a carbon steel cas- • High-temperature condensate diffuser tube (over 227
ing with a stainless steel liner. Built into a flange on top of the °F).
column is a spring loaded self-cleaning water spray nozzle and
an automatic and manual vent valve. • Boiler feed pump and motor sets.
From experience, large industrial plants and utilities have • Recirculation orifice or relief valve.
learned that the most practical and economical way to remove • Suction shutoff valve.
oxygen from feedwater is through mechanical deaeration. The
Boilermate deaerator economically effects oxygen removal • Suction strainer.
through a design that is trouble free in performance. • Suction flexible fitting.
Raw water, untreated and not deaerated, contains as much as • Discharge check valve.
ten cubic centimeters of corrosion-causing oxygen per liter.
Oxygen in water corrodes and shortens the life of boiler feed • Discharge shutoff valve.
lines, boilers and condensate return lines. • Discharge pressure gauge.
The Cleaver-Brooks designed deaerator assures high purity • Discharge manifold.
effluent by removing oxygen and other dissolved gases in
boiler feed. Thus, it is the answer to long-lasting boiler equip- • Overflow drainer.
ment for industrial and commercial boiler users. Built of cor- • Control panel.
rosion-resistant alloys for lifetime service, the deaerator
employs those basic principals of gas removal proved to most • Chemical feed quill.
effective and economical to every boiler owner. Contact your • Vacuum breaker.
local Cleaver-Brooks authorized representative for component
and sizing information. • Insulation and lagging.
The design of the Boilermate deaerator offers simplicity in • Sentinel relief valve.
both operation and service. The exchange packing, the heart of • Tank drain valve.
the deaerator, requires no maintenance. There are no moving
parts to adjust or maintain. Installation is simple and quick. • Back pressure relief valve.
• Deaerator water inlet atomizing valve. • Fully packaged, factory piped and wired.
H3-4
02-02
Feedwater Systems Boilermate Deaerators
140 140
120 120
42
100
INLET CAPACITY - LBS/HR X 1000 WATER
100
80 36
80
MODEL
60 60
30
40 40
24
20
20 20
16
12
8
50 70 90 110 130 150 170 190
FEEDWATER MIX TEMPERATURE - °F
*DEARERATOR CAPACITY LBS/HR
MODEL NO
BM-8 BM-12 BM-16 BM-20 BM-24 BM-30 BM-36 BM-42
H3-5
02-02
Boilermate Deaerators Feedwater Systems
B
2" NPT. INSPECTION
"C"
PORT (PLUGGED) 3 5 1 1 1
(1.5" NPT. FOR
MODELS 8 & 12)
"S" 0 "T" "E" "F" "G" "J" "H" "K" "L"
2 DIA. HOLE
IN LIFTING LUGS 6
"A"
(NOTE 18)
"R" 12
20 13
(NOTE 12) 2
TANK "P"
DIA.
21
8 9 10
14
"M"
(NOTE 1) 6
15 11 (NOTE 2) 4 7
18
19 (NOTE 4)
"D4" "B2"
(4) "E5"E HOLES
"C3" FOR "F6" E BOLTS "A1"
FRONT VIEW SIDE VIEW
1. Mounted at dim. "M" (top of tank) on non-packaged units.
2. Tank mounted on non-packaged unit.
3. Packaged units only. Mounted on left end, right side of stand on 48" dia. 1070 gal 54" dia. 1500 gal as shown.
4. Suction piping includes strainer, gate valve and flexible connector.
5. All couplings are 3000# F.S.
6. All flanges are 150# F.F. except as noted.
7. Customer to plug all fittings not being used.
8. Mount tank above pump at elevation necessary for static head including safe allowance for piping friction as approved by pump manufacturer.
9. Tank is built to ASME Code.
10. Accompanying dimensions, while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints.
11. Add suffix "P" to Model no. for packaged units (BMP-24).
12. Dimension "R" will change depending on controls required- contact your local Cleaver-Brooks authorized representative.
13. No interconnecting piping or wiring furnished on non-packaged units unless specified, contact your local Cleaver-Brooks authorized representative
for specific piping or wiring furnished on packaged assemblies.
14. Weights shown are without controls or packaging - contact your local Cleaver-Brooks authorized representative for additions.
15. Capacities other than shown as standard available by using two columns - contact your local Cleaver-Brooks authorized representative.
16. Optional tank sizes available - contact your local Cleaver-Brooks authorized representative.
17. Lifting lugs are for lifting empty tank only.
18. Manway is standard. Manufacturing may require a larger manway for fabrication. See dimensional diagram for actual size.
RATINGS
Cap (Gal to Overflow) 110 330 430 800 1070 1500
Tank Weight (Dry) (lb) 750 1200 1400 1900 2500 2750
Tank Weight (Flooded) (lb) 1850 4250 5300 9100 12700 15600
Tank Size (Dia x Length) 24 x 70 36 x 86 36 x 110 48 x 114 54x 127 60 x 129
TANK DIMENSIONS
E Steam Inlet 29 33 53 60
F Level Alarm 23 26 45 50
G High Temp Return 35 21 39 43
H Level Control 42 41 61 69
J Relief Valve 48 50 69 77
K Relief Valve N/A 60 79 86
L Relief Valve N/A N/A N/A 95
M Drain 36 47 76 93
P Overflow Rear Hd 60 10 10
R Overall Width 39 51 51 69 69 75
S Front Head 6 8 8 10 11
T Column 8.5 8.5 22 12
STANDARD DIMENSIONS
A1 Overall Length 54 61 86 101
B2 C/L to C/L Bolt Holes 49 56 80 95
C3 Overall Width 42 49 64 71
D4 C/L to C/L Bolt Holes 39 46 61 68
E5 Hole Size 0.75 1 1 1.125
F6 Anchor Bolt Size 0.625 0.875 0.875 1
CONNECTIONS & TRIM
1 Relief Valve Size Contact your local Cleaver-Brooks authorized representative
2 Overflow Size 1.25" NPT 2" NPT 3" NPT 3" NPT
3 Steam Inlet Size 2" NPT 3" NPT 4"-150# FF 6"-150# FF 6"-150# FF
4 Suction Size 3" NPT 3" NPT 3" NPT 4"-150# FF
5 High Temp Return Size 1" NPT 1.5" NPT 2" NPT 3" NPT
6 Drain Size 2" NPT 2" NPT 2" NPT 2" NPT
7 Recirc (1" NPT)
8 Thermometer (.75" NPT)
9 Sample (.5" NPT)
10 Chem Feed (1" NPT)
11 Thermometer
12 Gauge Glass Assy
13 Level Controller
14 Make-Up Valve
15 Pressure Gauge
16 Overflow Drainer (Opt)
17 Control Panel (Opt)
18 Feed Pump/Motor (Opt)
19 Suction Piping, (Opt)
20 Manway, 12 x 16
21 Level Alarms (Opt)
H3-7
02-02
Boilermate Deaerators Feedwater Systems
TANK SUPPORT LEGS STANDARD ON 110, 330, SADDLES STANDARD ON 1070 &
430 & 800 GALLON TANKS 1500 GALLON TANKS
FRONT HEAD FRONT HEAD
"E" "A" "E" "A"
"H"
"F"
6
"B" "B"
"F" "G"/2
"G"
LEGS SADDLES
A 48.5 55.5 80 95
E 11 15 15 17 16 17
H 7 7 7 9.75 N/A
Figure H3-2. Boilermate Tank Supports and Saddles, Details and Dimensions
H3-8
02-02
Feedwater Systems Boilermate Deaerators
Exhaust Steam
Exhaust steam cannot be recovered in an atmospheric vessel
application. This exhaust steam loss can be converted to
energy loss and associated fuel cost. An example would be
steam turbine exhaust.
Surface Blowdown
Increased makeup water is required because of lost flash and
exhaust steam. This increase in makeup water requires an
increase of surface blowdown. This is directly related to cycles
of concentration in the boiler. The additional blowdown loss
can be converted to an energy loss and associated fuel cost.
The additional surface blowdown may also result in an
increase in capital expenditure for a larger blowdown heat
recovery system.
Chemical Treatment
Dissolved oxygen content in an atmospheric boiler feedwater
system relates to the water temperature. Lowering the dis-
solved oxygen content below what is naturally present, based
on mix water temperature at atmospheric pressure, requires the
addition of a chemical treatment program. The most common
oxygen scavenger used is sodium sulfite. Sodium sulfite reacts
with dissolved oxygen as follows:
2Na2SO3 + O2 2Na2SO4
H3-9
02-02
Boilermate Deaerators Feedwater Systems
SAMPLE SPECIFICATIONS
The following sample specifications are provided by Cleaver-Brooks to assist you in specifying your customer’s specific needs and
application.
1.0 Deaerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-10
2.0 Make Up Valve and Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-11
3.0 Steam Pressure Reducing Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-12
4.0 Boiler Feedwater Pump And Motor Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-12
5.0 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H3-13
1.0 Deaerator
Cleaver-Brooks Model _________ packed column type, pressurized, horizontal deaerator is rated at _____ pounds per hour at ____
°F mixed inlet water temperature. The system shall be of the single tank design and guarantee oxygen removal to not more than
0.005 CCS/liter in the effluent throughout all load conditions between 5 and 100 percent. Tray-type designs are not acceptable. The
deaerator shall be designed for operation at 5 psig, but shall be suitable for use from 2 to 15 psig. Atmospheric operating designs
are not acceptable.
Feedwater and condensate shall be admitted to the deaerator through a single spring-loaded, self-cleaning, adjustable stainless steel
spray valve, which shall provide proper internal vent condensing and water distribution at any load between 5 and 100 percent of
rated capacity. The water temperature in the primary heating and vent concentrating section is to be raised within 2 or 3 °F of steam
temperature and most of the gases released. The water is then to drop down through the column’s stainless steel exchange packing
counterflow to the steam, which enters at the top of the storage tank and rises up through the column. The column is to be ____" in
length and ____ " in diameter. The column shall have a stainless liner and grid support. Hot, gas-free water is to then drop to the
storage compartment to complete the cycle. The steam and non-condensables are to flow upward, through the primary heating
spray, into the internal vent concentrating section, where they contact the cold influent water. Here, the steam is to be condensed to
continue the cycle. Released gases are discharged to atmosphere through the vent outlet. All internal surfaces, which come in con-
tact with un-deaerated water, shall be constructed of Type 316 stainless steel.
Automatic vent valve shall be thermostatically controlled to provide a fast means of venting when a sudden buildup of gases
occurs, such as seen at start up. The manual vent valve shall have an orifice for continuous minimum venting. Venting rate shall not
exceed 0.1 of 1% of the rated deaerator capacity at 5 psig.
The deaerated water storage tank shall have _____ minutes of storage and have a capacity of _____ gallons measured to overflow.
The tank shall be _____ diameter x _____ long. An 11" x 15" elliptical manhole shall be provided for access. All nozzles 3" and
under shall be 3000 lbs forged steel couplings and over 3" shall be 150 lbs flat face flanges. Heads to be ASME torispherical type
constructed of ASTM A516 GR 70 carbon steel with a minimum thickness of 0.25 inches. Shell plate to be fabricated of ASTM
A36 carbon steel with a minimum thickness of 0.25 inches. The tank and column shall be designed in accordance with ASME, Sec-
tion VIII of the Pressure Vessel Code for 50 psig at 650 °F and stamped accordingly. Certification shall be required. Joint efficien-
cies to be 70% circumferential per table UW-12, which does not require stress relieving or nondestructive examination.
The deaerator loads shall be as specified in the table below. Low temperature returns are defined as condensate with a temperature
below that of the deaerator operating temperature. High temperature returns are defined as condensate with a temperature above
that of the deaerator operating temperature.
1.1 Optional
The tank and column shall be factory-insulated and lagged with blanket insulation, pins, clips, and a durable steel jacket. Block-
type insulation is not acceptable. The blanket insulation is to be fiberglass, 2" thick, 1 lb/cubic foot, and have a rating of R3.85. Pins
Load Specifications
H3-10
02-02
Feedwater Systems Boilermate Deaerators
are to be located on 18" centers and holding clips attached. The steel jacket or lagging shall have a shell thickness of 22 gauge
(0.299") minimum and head thickness of 12 gauge (0.1046") minimum.
1.2 Optional
The tank shall be factory-lined with a high quality baked-on epoxy lining. The lining is to be applied to a sandblasted (SSPC-SP-5-
63) white metal surface. Spray-apply 4 to 6 coats with each dry coat being approximately 1.5 mils dry for a total thickness of 6 mils
dry minimum. Baking schedule for intermediate coats to be 10 to 20 minutes at 250 to 300 °F and final baking to be 1-1/2 hours at
350 to 400 °F. Lining to be Holliday spark tested using low voltage and a wet sponge to ensure uniform coating free of pin holes.
Magnesium anodes shall not be acceptable in this application. The lining is to meet requirements of FDA and MID of the USDA.
The lining is to be suitable for temperatures up to 250 °F.
1.3 Optional
The magnesium or sacrificial anode shall provide cathodic protection against galvanic corrosion. This rod shall be 1-5/16" diameter
with a 1/4" steel core to assure a good electrical contact and added strength. The design shall have a small weep hole to signal it has
been consumed. Linings shall not be acceptable in this application.
1.4 Optional
The high temperature diffuser or sparge tube shall be located beneath the normal tank water level. The tube shall be constructed of
2 inch pipe. This tube shall provide even distribution and blending of high-temperature condensate returns.
1.5 Optional
The chemical feed quill shall be located beneath the normal tank water level. The quill material shall be constructed of stainless
steel. The tube shall provide even distribution and blending of chemical.
1.6 Optional
The basic deaerator shall be equipped with the following trim and accessories. Piping on packaged units shall comply with ASME
Power Piping Code B31.1.
H3-11
02-02
Boilermate Deaerators Feedwater Systems
controller manufacturer shall be _________ , Model ______. A filter regulator is to be provided to reduce 50 psig instrument air
supply to 3 - 15 psig for proper operation.
2.4. Optional
The make up valve shall include a ANSI Class 125 lb three-valve bypass with inlet Y-type cast iron strainer. Strainer screen to be
removable and of stainless steel construction.
H3-12
02-02
Feedwater Systems Boilermate Deaerators
struction and have ______ seals for a maximum water temperature of 250 °F. Pump impeller to be hydraulically balanced. The
pump shall be mounted on a steel baseplate and flexibly coupled with an OSHA type coupling guard to a ____ hp, _____ phase,
______ Hz, ______ Volt, _______ rpm, ________enclosure motor. Motor to be non-overloading at the rated condition without
using any portion of the service factor. Pump and motor set to be factory aligned prior to shipment. Pump manufacturer to
be_____________, Model ________, size ____ " x _______".
4.2 Option - Continuous
Quantity ______, centrifugal type boiler feedwater pump and motor set. Turbine type pumps are not acceptable in this application.
Pump to be rated for _____ gpm at ______ feet TDH with ____ feet NPSH required. Pump to be _______ materials of construction
as defined by the Hydraulic Institute and have _______ seals for a maximum water temperature of 250 °F. Pump impeller to be
hydraulically balanced. The pump shall be mounted on a steel baseplate and flexibly coupled with an OSHA type coupling guard to
a _____ hp, ______ phase, _______ Hz, ______ Volt, _____ rpm, _______ enclosure motor. Motor to be non-overloading at the
rated condition without using any portion of the service factor. Pump and motor set to be factory aligned prior to shipment. Pump
manufacturer to be _________, Model _______, size _____ " x _______ ". A stainless steel recirculation orifice is to be supplied
with the pump and shipped loose for field installation to provide minimum bypass flow.
4.3 Optional
The stand shall elevate the deaerator tank to provide the net positive suction head required by the pump at the rated condition to
prevent cavitation plus a 1-1/2 foot safety factor. The stand shall be constructed of heavy square steel tubing for the legs and 1/4"
steel plate covering the floor.
H3-13
02-02
Boilermate Deaerators Feedwater Systems
NOTES
H3-14
02-02