Conventional FA initiating
device circuits and Supervised, non-
notification device circuits supervised, alarm, and
fall under which classes trouble
(4)?
-Heat Detector
Four common FA -Smoke Detector
initiating devices. -Manual Station
-Flame Detector
Notification appliances
can be considered to be output
----- devices.
Supervisory switches
mounted on a sprinkler
stand pipe must cause a
within the first 2 turns
supervisory signal at the
panel within how many
turns of the hand wheel?
Activation of a
suppression system
connected to a FA system Alarm
must cause what type of
signal?
NFPA 72 recommends
using a distance of ----- as
30 feet
a guide for spacing
smoke detectors.
No FA system of FA
devices may be installed Underwriters
in Nevada unless they are Laboratory (UL)
listed by?
A contractor or licensee
must employ at least one
qualified person who
holds a ----- to install and Certificate of
service protective Registration
signaling systems in order
for their license to remain
valid.
When a combination
system is installed, FA
take precedence
signals must ----- over any
other signal.
Location of initiating
devices, shall consider
conditions such as high or
low temperatures, True
humidity or sources of
smoke that can lead to
nuisance alarms. T/F?
An area covered by
notification appliances
that are activated notification zone
simultaneously is called a
------
Automatic Extinguishment
is a function of a FA False
system. T/F?
A distributor or installer of 24
a protective signaling
system must present the
Atate Fire Marshal with
evidence of his/her ability
to respond for any
needed repair and
restoration within -----
hours of being notified by
the fire department.
Actuation of alarm
notification appliances or
emergency voice
communications and
annunciation at the 10 seconds
protected premises shall
occur within ----- after the
activation of an initiating
device.
100,000 sq ft is the
largest area any one zone True
shall be. T/F?
If an intermittent trouble
signal is used, it shall
sound at least every 10
True
seconds with a minimum
duration of 1/2 second.
T/F?
A public FA reporting
system is called a ----- FA Municipal
system.
If an intermittent signal is
used, it shall sound at
least once every 10
seconds, with a 1/2 trouble
second minimum
duration, this applies to
----- signals.
A ----- is a publicly
accessible FA box that
can also be operated by 1
or more remote initiating
devices or an aux. fire Master box
system used to send an
alarm to the public fire
service communiciations
center.
A ----- is a detector
comprising of an
assembly that
incorporates a sensor,
control components, and
Single Station Alarm
alarm notificaton
Device
appliance in one unit that
is operated from a power
source either located in
the unit or obtained at the
point of installation.
----- is an audible or
visible signal that conveys
Coded
several discrete bits or
units of information.
-Added or deleted
system components
Reacceptance testing
-Modification, repair or
shall be performed after
adjustment to system
any of the following (3)
hardware or wiring,
-----
-Any change to site
specific software
In order to perform
service work on a
protective signaling
system, the company
True
must obtain a state
contractor's license which
covers this type of work.
T/F?
The number of
supervisory devices
permitted to be connected
20
to a signal initiating
device circuit shall not
exceed -----
A distributor or installer of
protective signaling
systems may install a
False
system without a license
issued by the State Fire
Marshall. T/F?
Location of initiating
devices, shall consider
conditions such as high or
low temperatures, True
humidity or sources of
smoke that can lead to
nuisance alarms. T/F?
A device or system
having materials different
from those detailed in
True
applicable standards may
be approved if found to
be equivalent? T/F?
A permanent record of
the time, date and
location of a signals and
restorations received and
1 year
the action taken shall be
maintained for at least
----- and shall be made
available to the AHJ.
A FA system in which
components are used, in
whole or in part, in
Combination System
common with a non-fire
signaling system is called
a -----
An area covered by
notification appliances
that are activated notification zone
simultaneously is called a
-----
A distributor or installer of
a protective signaling
system must present the
State Fire Marshall with
evidence of the ability to
24 hours
respond for any needed
repair and restoration
within ----- hours of being
notified by the fire
department.
FA systems shall be
provided with at least 2
independent and reliable
power supplies, one
primary and one True
secondary, each of which
shall have adequate
capacity for the
application. T/F?
Actuation of alarm
notification appliances or
Emergency voice
communications and
annunciation at the 10
protected premises shall
occur within ----- seconds
after the activation of an
initiating device.
A ---- is a municipal FA
box that can also be
Master Box
operated by remote
means.
Smoke detectors in
rooms with ceiling slopes
greater than ----- rise per -1 foot
----- horizontally shall be -8 feet
located at the high side of
the room.
Smoke detector
sensitivity cannot be
tested or measured using
any spray device that
True
administers an
unmeasured
concentration of aerosol
into the detector. T/F?
In a proprietary system,
when the runner is not in
attendance at the central
supervising station, the
runner shall establish 15
two-way communication
with the central station at
intervals not exceeding
----- minutes.
A system in which
transponders are
employed to transmit
status signals of each Active multiplex system
initiating device circuit
within a prescribed time
interval is a -----.
Where required by
applicable laws, codes or all sleeping rooms/guest
standards for a specific rooms
type of occupancy, outside each dwelling
approved single and unit sleeping area within
multiple station smoke 25 ft. of door
alarms shall be installed in the living areas of a
in the following locations guest suite
(3) -----
A ----- is a radiant-energy
sensing detector that
detects the radiant flame detector
energy emitted by a
flame.
The location of
equipment needed to
relay signals between the
protected premises and Repeater station
central supervising
station is defined as a
-----.
dispatch personnel to
Upon receipt of a trouble
arrive within 4 hours to
signal, the central station
initiate maintenance if
will
necessary
Additional manual FA
boxes shall be provided
so that travel to the 200 feet
nearest box shall not be
in excess of -----
A non-restorable initiating
device is a device whose
sensing element is
True
designed to be destroyed
by the process of
detecting a fire. T/F?
Proprietary supervising
stations shall be operated
by trained, competent
personnel, who are ----- in constant attendance
and responsible to the
owner of the protected
property.
In guards tour
supervisory service, the
number of guards tour
reporting stations, their
locations, and the route
to ve followed by the
True
guard for operating the
stations shall be
approved for the
particular installation in
accordance with NFPA-
601. T/F?
A switch for silencing the
alarm signal sounding located within a locked
appliances shall be cabinet
permitted only if it is key operated
either (2) -----
Failure of AC power
On one-way private radio
supplying the radio
alarm systems, which of
equipment
the following conditions
Malfunction of the RF
shall be supervised at the
receiver
central supervising
Indication of automatic
station? (3) -----
switchover
An automatic sequence
that results in an alarm
signal, even if manually
positive alarm sequence
delayed for investigation,
is defined as ----- unless
the system is reset.
A SLC interface is a
system component that
connects a SLC to any
combination of initiating
devices, inititating device True
circuits, notification
appliances and circuits,
system control outputs
and other SLCs. T/F?
A body or stream of
gaseous material is
involved in the
combustion process and
emitting radiant energy at
specific wavelengths Flame
bands. In most cases,
some portion of the
emitted radiant energy is
visible to the human eye
as -----.
Detectors shall be
supported, in all cases,
independently of their True
attachment to the circuit
conductors. T/F?
A device designed to
detect the presence of a
an automatic fire detector
fire signal and initiate
action is called -----
A transmitter is a system
component that provides
as interface between
SLCs, initiating device True
circuits, or control units
and the transmission
channel. T/F?
Standard NFPA-72
recognizes only those
heat detectors with 50
ratings of ----- feet or
more.
Public FA reporting
systems shall in their
a complete operational
entirety, be subject to -----
acceptance test
upon completion of the
system installation.
cloud chamber
3 examples of a smoke-sensing fire
photoelectric
detector.
ionization
If a license or certificate of
Notify the state fire marshal in
registration is lost or destroyed, a
writing attesting that the original
replacement may be obtained by
license was lost or destroyed.
what method?
Area to be protected by a
combination paging alarm must be
covered with sufficient loudspeakers
80 decibels
to achieve at least ------ of sound
measured at any place within the
protected property.
Who is responsible
for insuring that the
number and
placement of
loudspeakers
The architect or
installed in a
designer
combination paging
alarm system meet
the standards
adopted by the state
fire marshal?
In a combination paging
alarm system all
sleeping rooms in the
True
protected premises
must be equipped with a
loudspeaker. T/F?
In a combination paging
alarm system where
environmental
Use a horn type
conditions are
loudspeaker
detrimental to cone type
speakers what action
must be taken?
An annunciator panel is
provided at the central
station for control
Combination paging All components of the
alarm systems must be system must be
designed so that (3) ---- continuosly supervised
A paging microphone
must be provided at each
annunicator panel
Combination paging
alarm systems must be
maintained in proper
operating condition. An False
actual test of the system
is required once every 6
months. T/F?
A firm or company
providing a maintenance
agreement for a FA
system must provide a
proof of liability insurance
copy of the agreement,
and ----- to the local fire
department having
jurisdiction.
Amplifiers, tone
generators, ans
addociated equipment
used in a combination
paging an alarm system
must be installed to
Opens, shorts, grounds
provide a completely
mechanical damage
independent operating
power loss
system and must
include a fail-safe paney
which will monitor the
system against (5) -----
while the equipment is
in use or on standby.
Can an annunciator
panel installed in the
combination paging
alarm system be no
compatible with the fire
system but of a different
brand?
Who is responsible to
ensure that the
equipment for the FA
The engineer who
system meets the
designed the system
requirements set forth
by the state fire
marshal?
In a supervisory panel
for a protective signaling
emit audible and visual
system, when a fault
indications of the fault
has been detected it
must automatically -----
Prior to installing a FA
system in any building in
the state, plans of the AHJ/Fire Department
system must be
submitted to the -----
Maintenance or
installation of a
protective signaling
system can be done False
without license issued
by the State Fire
Marshal? T/F?
Which standard
published by the NFPA
NFPA 72
must FA systems
comply with?
Within a protected
premise, areas to be
covered by audible FA
system must achieve 80 db
----- level of decibels at
any location within the
property covered.
A contractor licensed
with the State Fire
Marshals office must
employ a qualified
individual to perform
True
installation and service
work on protective
signaling systems for
their license to remain
valid. T/F?
Household smoke
alarms and smoke
detectors installed witin
a ----- horizontal path of
a cooking appliance 20 feet
shall be equipped with
an alarm-silencing
means or be of the
photo electric type.
In a combination
system, a ----- signal
shall take precedence or fire alarm
be clearly recognizable
over any other signal.
Spot-type smoke
detectors mounted on
the side wall should
4 to 12
have the top of the
detector between -----
inches from the ceiling.
Household FA systems
shall have 2
independent power
sources consisting of a
primary source that rechargeable batteries
uses commercial light
and power, and a
secondary source
consisting of -----
A ----- is a local
signaling system for FA,
supervisory or guard's
tour supervisory
services for household
fire warning systems, combination system
whose components may
be used in whole or in
part in common with a
non-fire signaling
system.
Local protective
systems of the electrical
True
type must test free of
grounds. T/F?
Audible signal
appliances intended for
use in special outdoors vs. indoors
environments such as high humidity
(3) ----- or where subject dusty/hazardous
to tampering shall be locations
listed for the intended
application.
Manually actuated
alarm-initiating devices
do not need to be
located so that the travel 125 feet
distance to the nearest
FA box is not in excess
of -----
In a protected premises
FA system the
secondary power supply
shall automatically
supply the energy to the 10 seconds
system within -----
whenever the primary
power supply is
incapable.
All means of
interconnecting
equipment, devices and
appliances and wiring
connections shall be
------ of the
interconnecting
conductors or equivalent
path so that the
Monitored for integrity
occurrence of a single
ground fault condition in
the installation
conductors or other
signaling channels and
their restoration to
normal shall be
automatically indicated
within 200 seconds.
Shunt-type auxiliary
systems shall be so
arranged that one
auxiliary transmitter 100,000
does not serve more
than ----- sq. ft total
area.
Where signal
conductors and electric
light and power wires
are run in the same
shaft, they shall be
2 inches
separated by at least
-----, or either system
shall be encased in a
noncombustible
enclosure.
Conductors of the
shunt circuits shall not
14
be smaller than -----
AWG and shall be
insulated.
Protected premises FA
systems that serve the monitoring of abnormal
general FA needs of a conditions in a fire
building shall include suppression system
these 2 functions related Activiation of fire
to fire suppression suppression systems
systems...
Protected premises FA
systems that serve the
leak detection of fire
general FA needs of a
suppresion systems
building does not need to
include ----
When a remote
the fire station
supervising station
a similar governmental
connection is used to
agency
transmit an alarm signal,
the public fire service
the signal shall be
commuication center
received at (3) -----
In a household FA
system, fixed temperature
detectors or alarms shall
have a temperature rating
at least 25F above the
normal ambient
50F
temperature and shall not
be rated ----- higher than
the max anticipated
ambient temperature in
the room or space where
installed.
In a household FA
system, all electrical
systems designed to be
installed by other than a
qualified electrician shall
30 V
be powered from a
source not in excess of
----- volts that meets the
requirements for power
limited FA circuits.
A signal indicating an
emergency requiring
immediate action, such as
alarm signal
an alarm for fire from a
manual box is defined as
a -----
Actuation of alarm
notification appliances or
emergency voice
communications, fire
safety functions, and
10 seconds
annunciation at the
protected premises shall
occur ----- after the
activation of an initiating
device.
Initiation of an alarm
signal due to waste,
surges or variable
pressure shall be allowed
only if the waste, surges
False (no alarm)
or variable pressure
results in water
movement that exceeds
normal by 175% or more.
T/F?
----- is a body or stream of
gaseous material involved
in the combustion Flame
process, emitting radiant
energy.
On a sloping ceiling,
detectors shall first be
spaced and located within 3
----- feet of the peak,
measured horizontally
Records of all
inspections, tests and
maintenance shall be 1 year
retained until the next test
and for ----- thereafter.
A rate-of-rise detector is a
device which will respond
False (it must exceed
when the temperature
that level)
rises to a predetermined
level. T/F?
A typical example of a
fixed temperature sensing bimetallic
element is -----
To avoid nuisance
alarms, the location of
dust
smoke detectors shall
moisture
take into consideration
smoke
normal sources of (4) -----
fumes
and electrical or
mechanical influences