Aa 038674 004
Aa 038674 004
NOTES:
WELLHEAD GAS COMPOSITION FOR HSBH GAS FIELD 1. ALL DIMENSIONS ARE IN MILLIMETER.
EQUIPMENT LIST LEGEND
GRID 2. ALL ELEVATIONS ARE IN METERS AND REFER TO
PROCESS GAS COMPOSITION (DRY BASIS) PROCESS GAS COMPOSITION (DRY BASIS) LOWEST ASTRONOMICAL TIDE (LAT) DATUM.
CLASS I, ZONE 0, GAS GROUP IIA & IIB, TEMPERATURE
EQUIPMENT NO. DESCRIPTION SIZE (CAPACITY) REMARKS CLASS T3 ( MINIMUM IGNITION TEMP OF 260°C), 3. THIS DRAWING SHALL BE READ IN CONJUNCTION
AUTO IGNITION TEMPERATURE AUTO IGNITION TEMPERATURE
COMPONENT Mol% COMPONENT Mol% L x W x H ELECTRICAL AREA AS PER API 505. WITH ELECTRICAL AREA CLASSIFICATION SCHEDULE
CLASS CLASS DOC. NO. AA-038675.
PLT CLASS I, ZONE 1, GAS GROUP IIA & IIB, TEMPERATURE
D-2003 FLARE KO DRUM ID 1270 x T/T 2845
OF
NTH H2O 0 - - H2O 0.00 - - CLASS T3 ( MINIMUM IGNITION TEMP OF 260°C), 4. FOR THE PURPOSE OF ELECTRICAL AREA
L-2001 FLOWLINE SCRAPER LAUNCHER (22"X16") 8635 x OD 559 x 406 -
N2 11.41 - - N2 6.26 - - ELECTRICAL AREA AS PER API 505. CLASSIFICATION, ALL THE DECKS ARE CONSIDERED
CONSENT
PREVAILING WIND G-2001A/B MEG INJECTION PUMPS 6225 x 2220 x 2804 - GRATED AND AREA CLASSIFICATION IS EXTENDED
CO2 7.07 - - CO2 7.53 - - CLASS I, ZONE 2, GAS GROUP IIA & IIB, TEMPERATURE
TO BELOW DECKS BASED ON THE HAZARD RADIUS.
CLASS T3 ( MINIMUM IGNITION TEMP OF 260°C),
H2S 4.77 260 T3 H2S 4.02 270 T3 U-2004 A/B NITROGEN BOTTLES RACK 1322 x 1020 x 2200 -
ELECTRICAL AREA AS PER API 505. 5. TEMPERATURE CLASS OF ALL THE ELECTRICAL AND
C1 73.24 595 T1 C1 81.88 630 T1 U-2006 MONORAIL HOIST 1350 x 1250 x 1000 (10 MT) - INSTRUMENTATION EQUIPMENT SHALL MEET THE
CLASS I, ZONE 1, GAS GROUP IIA & IIB, TEMPERATURE
TEMPERATURE CLASS (MINIMUM T3) OF THE AREA
C2 2.29 515 T1 C2 0.22 472 T1 TR-001 ICCP TRANSFORMER RECTIFIER-1 2985 x 1162 x 1360 - CLASS T3 (MINIMUM IGNITION TEMPERATURE OF 260°C),
TTEN
WHERE THEY ARE INSTALLED.
C3 0.5 470 T1 C3 0.03 450 T1 HAZARDOUS AREA AS PER API-RP-505 - EXPECTED
TR-002 ICCP TRANSFORMER RECTIFIER-2 2985 x 1162 x 1360 - 6. PRODUCTION GAS IS LIGHTER THAN AIR (DENSITY TO
DURING WIRE LINING OPERATION.
i-C4 0.11 - - n-C4 0.01 288 T3
WRI
AIR IS ABOUT 0.7) THEREFORE HAZARDOUS AREA
K-2001A HVAC UNIT A 3023 x 2235 x 2387 -
CLASS I, ZONE 2, GAS GROUP IIA & IIB, TEMPERATURE CLASSIFICATION ENVELOPES ARE NOT EXTENDED
n-C4 0.16 365 T2 C6 0.01 235 T3
3023 x 2235 x 2387 - CLASS T3 (MINIMUM IGNITION TEMPERATURE OF 260°C), DOWN TO THE FIRST SOLID DECK BELOW THE LEAK
K-2001B HVAC UNIT B
i-C5 0.08 - - C7+ 0.01 204 T3 HAZARDOUS AREA AS PER API-RP-505 - EXPECTED
THE
SOURCE AS GAS IS NATURALLY BUOYANT. HAZARDOUS
n-C5 0.06 - - GAS MIXTURE 100 270 T3 CP-003 HYDRAULIC ESD PANEL - - DURING WIRE LINING OPERATION. AREA ENVELOPES EXTENSION IS LIMITED TO THE
JB-003 NEGATIVE JUNCTION 525 x 260 x 1675 - HAZARDOUS RADIUS DEFINED BY API 505 STANDARD
C6 0.08 230 T3 CLASS I, ZONE 2, GAS GROUP IIA & IIB, TEMPERATURE
THOUT
ONLY.
CLASS T3 (MINIMUM IGNITION TEMPERATURE OF 260°C),
C7 0.08 204 T3 JP-004 NEGATIVE JUNCTION 525 x 260 x 1675 -
HAZARDOUS AREA AS PER API-RP-505 (FUTURE). 7. THE AREA SURROUNDING SAMPLE AND INSTRUMENT
C8 0.05 - - LP-002 LIGHTING PANEL 2200 x 450 x 1700 - DRAIN VALVES, GAUGE VALVES SHALL BE
WI
UNCLASSIFIED AREA. UNCLASSIFIED AS PER SECTION 10.15.3.1 OF API
C9 0.03 - - -
PP-001&005 480V AC POWER PANEL 2200 x 450 x 1700
RP 505.
NG
C10+ 0.07 - -
PP-008&009 400/230V AC POWER PANEL 2200 x 450 x 1700 - 8. THE AREA SURROUNDING THE FINAL DISCHARGE
DRAWI
GAS MIXTURE 100 260 T3 POINTS OF SAMPLE AND INSTRUMENT DRAIN VALVES,
SW-003&004 LIGHTING SWITCH - -
GAUGE VALVES SHALL BE CLASSIFIED ZONE 2 FOR
1.5 METERS AS PER SECTION 10.15.3.2 OF API
RP 505.
S
THI
9. A ZONE 2 WITH HAZARD RADIUS OF 2000 MM SHALL
BE CONSIDERED AROUND FLANGES AND VALVES
HANDLING HYDROCARBON AT HIGH PRESSURE.
FROM
10.A ZONE 1 WITH HAZARD RADIUS OF 1500 MM AND
ZONE 2 WITH HAZARD RADIUS OF 3000 MM SHALL
BE CONSIDERED AROUND LAUNCHER DOOR AND VENT.
NED
B A 11.THE DRIP PAN/DRAIN TROUGH SHALL BE CLASSIFIED
ZONE 1 INSIDE AND ZONE 2 FOR 0.5 METERS FROM
OBTAI
THE EDGE.
BE
SCRAPER LAYDOWN
PART,SHALL
R3000
AREA REFERENCE DRAWINGS
R1500
U-2006 EQUIPMENT LAYOUT FOR MAIN DECK AA-038483
DRAIN GUTTER TR-001
R2000 MONORAIL-10MT DRIP PAN
R2000 R2000 R2000 R2000 R2000
R2000 R2000
HANDLING/ESCAPE WAY
ACCESS W AY
ACCESS W AY
N
R2000
I
JB-004
FULL,OR
TR- 002
L-2001
4600
N
I
R3000 R2000
ACCESS WAY
ACCESS WAY
ON
REPRODUCTI
2
ACCESS W AY
D- 2003
R2000
REMOVABLE HANDRAIL R3000
R3000
K- 2001A
ACCESS W AY
5350
ACCESS W AY
ACCESS W AY
ACCESS W AY
ACCESS W AY
ACCESS W AY
(FUTURE) KEY PLAN
MAIN DECK
SAUDIARAMCO.NO
SLOPE
ACCESS W AY
NG/ESCAPE W AY
X-2001/2002 SPARE 1
C
ACCESS W AY
L X-2002 X-2001
WELLHEAD XTREE
100
PLT
1:
NG/ESCAPE W AY
NTH
R2000
DRILL DECK R2000
PREVAILING WIND
SLOPE
K- 2001B
HANDLI
100
R2000
B A
1:
R3000
OF
ACCESS WAY
DECK
HANDLI
C
PROPERTY
X-2004 X-2003
5350
WELLHEAD XTREE
R2000
AREA (5000x1500)
(FUTURE)
CP-003 R2000 2
SW-003&004
ACCESS WAY
UP
DATUM POINT CELLAR DECK MAIN DECK
UP
DRILL DECK STAIRS TO
SOLE
FRAME MEZZ DECK
E 200000
1 1
ACCESS W AY
R3000 PP
THE
R3000
HANDLING/ESCAPE WAY -008&009
ARE
4600
G-2001B G-2001A
THIS DRAWING
N
HEREI
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0
LAYDOWN AREA
U-2004A/B
2.7m X 2.0m
METERS
ACCESS WAY
HANDLING/ESCAPE WAY
NED
SCALE: 1 :75M
CONTAI
DRAIN GUTTER
100000
REVISION VALIDATION
ON
N
30004827-1018-105
NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) x REQUIRED (SAUDI ARAMCO)
I
00 09/30/18 NEW STANDARD DRAWING
THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
30004827 CONSTRUCTION UNTIL CERTIFIED AND DATED
AND
DRAWING TYPE
NG
MAIN DECK
DRAWI
ALL EQUIP, INSTRUMENT 4 WELL STD. GAS PLATFORM-HSBH/ARBI
AND PIPING TAG
NUMBERS ARE PRECEDED
BY PREFIX NO. STD. DWG. SAUDI ARABIA
S
PLATFORM PREFIX NO. PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
THI
XX 990 B AA-038674 004 00
Saudi Aramco 2615 ENG. (05/05)