AB Capacity Calculations
AB Capacity Calculations
Anchor bolt capacities are based on the anchor bolt assemblies as detailed on Technical Standard
C17-2TS and recommendations of ASCE’s “Wind Loads and Anchor Bolt Design for Petrochemical
Facilities.”
• Anchor bolt capacities shall NOT be increased for wind or earthquake conditions.
• Loading for the design of anchoring systems shall be service (non factored) loads.
SHEAR
2. Frictional resistance shall be considered as the primary mechanism to transfer shear providing
that a compressive load exists under all loading combinations. The resistance on concrete or
grout shall be calculated as 0.55 times the minimum compressive load. Frictional resistance
shall not be utilized in seismic areas.
3. When the design shear exceeds the frictional capacity, all shear should be assumed to be
carried by the anchor bolts. Each bolt should carry shear in proportion to its cross sectional
area. Anchor bolts whose capacity are limited by edge distance may be neglected.
4. When shear keys are used, they should be sized to carry the entire anchorage shear, because
shear keys are stiffer than anchor bolts in shear.
5. The allowable shear load on unreinforced
concrete, Vs, for all types of anchor bolts is
based on the projected shear wedge area.
Aw = Ed²
When the shear wedge is limited
by bolt spacing (i.e. Ed > ½ Bs)
deduct the following for each
limited side.
½(Ed - ½Bs)²
TENSION
1. The allowable tension strength on unreinforced concrete for all types of anchor bolts is based
on the projected area of the tensile pyramid.
2. The projected area is based on the edge distances and half the bolt spacings but not to
exceed the embedment length. Also see Design Manual Section 2.2.6 “Anchor Bolt Pattern
Arrangement”
5. The absolute maximum tension is based on the bolt material and shall not be exceeded, see
Design Manual Section 2.2.8 “Material Properties”
For bolts subject to both tension and shear the following condition should be met.