Method Statement For Fire Alarm System Installation
Method Statement For Fire Alarm System Installation
1. The correct size and type of cable should be identified and cut to the
required length.
5. The junction boxes and back boxes to the outstations such as smoke
detectors, manual call points and modules should be installed as per
the approved shop drawings.
9. All the Fire Alarm control Panels such as Main Control Panels, Mimic
Panels, Repeater Panels should be installed as per approved shop
drawing.
17. The speakers & speaker with strobes are connected in Class A
circuit with the Control panels.
18. 2 Core 1.5mm2 FP 200 cable to be used for cabling the Initiating
Device Circuits (IDC) to the panel, additional 2c x 2.5mm2 FP200 cable
is required for the smoke detector with sounder base for the activation
of the sounders units.
19. 2 core 1.5mm2 FP 200 cable to be used for cabling the Speakers
with the panel, additional 2c x 2.5mm2 FP200 cable is required from
the FACP for the speaker with strobe for the activation of the strobe
unit allied in vertical walls the run of conduit will be kept straight.
Comply with NFPA 72, “Smoke-Sensing Fire Detectors” & “Heat-Sensing Fire
Detectors”.
Fire-Alarm Control Unit: Surface mounted, with tops of cabinets not more
than 72 inches (1830 mm) above the finished floor.
Annunciator: Install with top of panel not more than 72 inches (1830 mm)
above the finished floor.
Verify that hardware and devices are NRTL listed for use with fire-alarm
system before making connections.
Install the interface device less than 3 feet (1 m) from the device controller.
Battery Charger Faults that can arise during the operational lifetime of a
panel. You may observe one of the following Faults;
To prevent damage to the system, disconnect the batteries & power down
the system, disconnect the power & harnesses from the Power Supply.
Calculate the difference between the measured voltage & 27.6v. NOTE: After
90 seconds, the voltage will drop to <24v. If this happens, power down &
start again.
Fire Panels have the ability to detect positive or negative Earth Ground
Faults. An Earth Ground Fault occurs when an electrical circuit is shorted to
ground
All inspection and testing for fire alarm system shall be carried out in
accordance with specifications.
Work shall be carried out by the experienced site team under the guidance of
engineer and shall further be checked and approved by quality engineer.
FA System Testing:
Comply with “Test Methods” Table in the “Testing” Section of the “Inspection,
Testing and Maintenance” Chapter in NFPA 72.
Test audible appliances for the public operating mode according to
manufacturer’s written instructions. Perform the test using a portable
sound-level meter complying with Type 2 requirements in ANSI S1.4.
Check the detectors with the artificial test smoke spray. Use forms
developed for initial tests and inspections.