Automatic Generation Control
Automatic Generation Control
LITERATURE REVIEW
In case of the mains supply, the controller maintains the predefined power
factor. According the arrangement of the field and armature windings, synchronous
machines may be classified as rotating armature type or rotating field type. According
to the shape of the field, synchronous machines be classified as non-silent pole
machines and salient-pole machines.
provide an additional stabilizing force for the machine during certain periods of
operation. When a synchronous generator supplies electric power to a load, the
armature current creates a magnetic flux wave in the air gap which rotates at
synchronous speed. This flux reacts with the flux created by the field current, and
electromagnetic torque results from the tendency of these two magnetic fields to
align. In a generator this torque opposes rotation and mechanical torque must be
applied from the prime mover to substain rotation. As long as the stator field rotates at
the same speed as the rotor and no current is induced in the damper windings.
However, when the speed of the stator field and the rotor become different, currents
are induced in the damper windings. Currents generated in the damper windings
provide a counter torque. In this way the damper windings con keep the two speeds.
Load frequency control (LFC) is the basic control mechanism in the power
system operation. Whenever there is a variation in load demand on a generating unit,
there is momentarily an occurrence of unbalance between real-power input and
output. The difference is being supplied by the stored energy of any units is given by
1
KE= Iω2
2
Where, I is the moment of inertia of the rotating part and ω is the angular speed of the
rotating part.
If KE reduces, ω decreases; then the speed falls, hence the frequency reduces.
The change in frequency Δf is sensed and through a speed-governor system, it is fed
back to control the position of the inlet valve of the prime mover, which is connected
to the generating unit. It changes the input to the prime mover suitable and tries to
bring back the balance between the real-power input and output. Hence, it can be
stated that the frequency variation is dependent on the real-power balance of the
system. The LFC also controls the real-power transfer through the interconnecting
transmission lines by sensing the changing in power flow through the tie-lines.
The LFC, also known as generation control or p-f control, deals with the
control of loading of the generating units for the system at normal frequency. The
load in a power system is never constant and the system frequency remains at its
normal value only when there is a match between the active power generation and the
active power demand. During the period of load change, the deviation from the
normal frequency, which may be called frequency error ( Δf ) ,is an index of mismatch
and can be used to send the appropriate command to change the generation by
adjusting the LFC system. It is basically controlling the opening of the inlet valve of
the prime movers according to the loading condition of the system. In the case of a
multi-area system, the LFC system also maintains the specified power interchanges
between the participating areas. In a smaller system, this control is done manually, but
in large systems automatic control devices are used in the loop of the LFC system.
6
The LFC system, however, does not consider the reactive power flow in the
system even through the reactive power flow is also affected to some extent during
the fluctuating load condition. But since there is no counterpart of the reactive power
in the mechanical side of the system, it does not come within the loop of the LFC
system.
areas are affected due to a small change in load in any of the areas so as the tie line
power flow are affected. So the transient situation information’s of all other areas are
needed by the control system of each area to restore the pre-defined values of tie line
powers and area frequency. Each output frequency finds the information about its
own area and the tie line power deviation finds the information about the other areas.
For example in a two area power system, the information can be written as
BiΔfi+ΔPtie. B = frequency bias, f = predefined frequency And P tie is the power in tie
line. This is the Area Control Error (ACE) which is the input to the controller.
Thus the load frequency control of a multi area power system generally
incorporates proper control system, by which the area frequencies could brought back
to its predefined value or very nearer to its predefined value so as the tie line power,
when the is sudden change in load occurs.
1. Effect of size: This is one of the major advantages for the total
interconnected system. As soon as a block of load is added, during the first
moments, the required energy is borrowed temporarily from the kinetic
energy of the system. Obviously, the larger the system is, the more is the
energy available. Hence the static frequency drop is comparatively less.
However, the same amount of change in load may cause a higher
frequency drop in an isolated or small power system, which may even
make the entire system unstable.
2. Reduced need of reserve capacity: Since the peak demands can occur at
various hours of the day in various areas, the ratio between peak and
average load for a large system is smaller than that of smaller systems. It is
therefore obvious that, all the interconnected areas can benefit from a
reduced need of reserve capacity by a scheduled arrangement of energy
interchange.
3. Linkage mechanism
4. Speed changer
With the help of linkage mechanism, the position of the pilot valve can be
changed in the following three different ways:
i. Directly by the speed changer: A small upward moment of linkage
point A corresponds to a decrease in the steady-state power output
or reference power ∆ Pref.
ii. Indirectly through the feedback due to the position changes in the
main system.
iii. Indirectly through feedback due to the position changes in linkage
point E resulting from a change in speed.
4. Speed changer. It provides a steady state power output setting for the
turbine. It downward movement opens the upper pilot valve so that more
steam is admitted to the turbine under steady condition (hence more steady
power output). The reverse happens for upward movement of speed
changer.
When two generators are running in parallel, the governor characteristic of the
first unit (Line 1) is shown towards the right, while that of the second unit (Line 2) is
shown towards the left of the frequency axis as shown in figure.
When the turbine load changes during generating operation, the servo
motor shall operates the guide vane smoothly coordinating with the speed
governor. The operation shall be performed by oil pressure from the pressure
oil supply system. The servo motor shall be capable to close the guide vane
from the fully opened position to the fully closed ones against maximum
hydraulic pressure of 600m in water column due to water hammer after load
rejection.
3. High speed: From 800″ and above height, specific speed (3-7rpm), speed
(120-720rpm). These are Impulse type of turbines (Peloton wheel).
The inlet is spiral shaped. Guide vanes direct the water tangentially to the
turbine wheel, known as a runner. This radial flow acts on the runner’s vanes, causing
the runner to spin. The guide vanes may be adjustable to allow efficient operation for
a range of water flow. As the water moves through the runner its spinning radius
decreases, further acting on the runner. This property, in addition to the water’s
pressure, helps Francis and other inward-flow turbines harness water energy
efficiently.
At the exit, water acts on cup shaped runner features, leaving with no swirl
and very little kinetic or potential energy. The turbine’s exit tube is shaped to help
decelerate the water flow and recover the pressure.
Δw
R= ΔP pu (2.2)
Where,
Δw = speed deviation
ΔP = output power
ACEi =
ΔP ij + B ¿ Δf (2.3)
i
Where,
i = control area for which ACE is being measured
Δ Pij = power interchange in areas i and j
1. The ACE signal should ideally be kept from becoming too large. Since
ACE is directly influence by random load variations, this creation can
treated statically by saying that the standard deviation of ACE should be
small.
2. ACE should not be allowed to ‘drift’. This means that the integral of ACE
over appropriate time should be small. A ‘drift’ in ACE has the cumulative
effect of creating system time errors or inadvertent interchange errors.
3. The amount of control action called for by the AGC should be kept to a
minimum.