0% found this document useful (0 votes)
35 views88 pages

750com Um004 - en P

The User Manual for the PowerFlex® 20-750-PBUS Profibus DPV1 Option Module provides essential safety guidelines, installation instructions, and configuration details for users. It emphasizes the differences between solid-state and electromechanical equipment and includes warnings about potential hazards. This is the first release of the manual, which also contains troubleshooting information and specifications for the module.

Uploaded by

João
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
35 views88 pages

750com Um004 - en P

The User Manual for the PowerFlex® 20-750-PBUS Profibus DPV1 Option Module provides essential safety guidelines, installation instructions, and configuration details for users. It emphasizes the differences between solid-state and electromechanical equipment and includes warnings about potential hazards. This is the first release of the manual, which also contains troubleshooting information and specifications for the module.

Uploaded by

João
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 88

User Manual

PowerFlex® 20-750-PBUS
Profibus DPV1 Option Module
FRN 1.xxx
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your
local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes

This is the first release of the 20-750-PBUS Profibus DPV1 Option Module User
Manual.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 3


Summary of Changes

4 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Table of Contents

Preface Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7


Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Chapter 1
Getting Started Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Understanding Parameter Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Chapter 2
Installing the Option Module Preparing for an Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Setting the Endianness and Node Address Switches . . . . . . . . . . . . . . . . . 16
Connecting the Option Module to the Drive . . . . . . . . . . . . . . . . . . . . . . . 18
Connecting the Option Module to the Network . . . . . . . . . . . . . . . . . . . . 18
Network Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Chapter 3
Configuring the Option Module Configuration Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Using the PowerFlex 20-HIM-A6/-C6S HIM to Access Parameters . . 24
Setting the Node Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Setting a Master-Slave Hierarchy (Optional). . . . . . . . . . . . . . . . . . . . . . . . 24
Setting a Fault Action. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Resetting the Option Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Restoring Option Module Parameters to Factory Defaults . . . . . . . . . . . 29
Viewing the Option Module Status Using Parameters . . . . . . . . . . . . . . . 31
Flash Updating the Option Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Chapter 4
Configuring the Profibus Master Example Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Configure the MVI56-PDPMV1 Profibus DPV1 Master . . . . . . . . . . . . 34
GSD Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Slave Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 5


Table of Contents

Chapter 5
Using the I/O About I/O Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Understanding the I/O Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Using Logic Command/Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Using Reference/Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Using Datalinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
I/O Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Chapter 6
Acyclic Messaging About Acyclic Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Acyclic Messaging for DPV1 Class 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Example Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

Chapter 7
Troubleshooting Understanding the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
PORT Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
MOD Status Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
NET A Status Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Viewing Option Module Diagnostic Items . . . . . . . . . . . . . . . . . . . . . . . . . 64
Viewing and Clearing Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Appendix A
Specifications Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Appendix B
Option Module Parameters Parameter Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
About Parameter Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
How Parameters Are Organized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Device Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Host Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Appendix C
Logic Command/Status Words: Logic Command Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
PowerFlex 750-Series Drives Logic Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Glossary

Index

6 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Preface

About this Manual

Topic Page
Related Documentation 7
Rockwell Automation Support 8
Conventions Used in This Manual 8

Related Documentation
For: Refer to: Publication
Network Communication Option Module Network Communication Option Module Installation Instructions (for use 750COM-IN002
with PowerFlex 750-Series Drives)
Profibus Cable Profibus Installation Guideline http://www.profibus.com/
DriveExplorer™ http://www.ab.com/drives/driveexplorer, and DriveExplorer online help —
(installed with the software)
DriveTools™ SP (includes DriveExecutive™) http://www.ab.com/drives/drivetools, and DriveExecutive online help —
(installed with the software)
Enhanced Power-Flex 7-Class HIM Enhanced PowerFlex 7-Class HIM User Manual 20HIM-UM001
PowerFlex® 750-Series AC Drive PowerFlex 750-Series AC Drives User Manual 750-UM001
PowerFlex 750-Series Reference Manual 750-RM002
Prosoft Configuration Builder (Version http://www.prosoft-technology.com/prosoft/products/prosoft_software —
2.2.2.3) /pcb
Profibus Master (Prosoft MVI56-PDPMV1) http://www.prosoft-technology.com/content/view/full/8109 —
Profibus Standard http://www.profibus.com/ —

Documentation can be obtained online at


www.rockwellautomation.com/literature. To order paper copies of technical
documentation, contact your local Rockwell Automation distributor or sales
representative.

To find your local Rockwell Automation distributor or sales representative, visit


www.rockwellautomation.com/locations.

For information such as firmware updates or answers to drive-related questions,


go to the Drives Service & Support web site at www.ab.com/support/abdrives
and click on the “Downloads” or “Knowledgebase” link.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 7


Preface

Rockwell Automation Rockwell Automation, Inc. offers support services worldwide, with over 75
Support sales/support offices, over 500 authorized distributors, and over 250 authorized
systems integrators located through the United States alone. In addition,
Rockwell Automation, Inc. representatives are in every major country in the
world.

Local Product Support

Contact your local Rockwell Automation, Inc. representative for:


• Sales and order support
• Product technical training
• Warranty support
• Support service agreements

Technical Product Assistance


For technical assistance, please review the information in Chapter 7,
Troubleshooting, first. If you still have problems, then access the Allen-Bradley
Technical Support web site at www.ab.com/support/abdrives or contact
Rockwell Automation, Inc.

Conventions Used in This This manual provides information about the 20-750-PBUS Profibus DPV1
Manual network communications option for use with PowerFlex 750-Series drives. The
following conventions are used throughout this manual:

• Parameter names are shown in the format Device Parameter xx - [*] or


Host Parameter xx - [*]. The xx represents the parameter number. The *
represents the parameter name—for example Device Parameter 01 - [DPI
Port].

• Menu commands are shown in bold type face and follow the format Menu
> Command. For example, if you read “Select File > Open,” you should
click the File menu and then click the Open command.

• The firmware release is displayed as FRN X.xxx. The “FRN” signifies


Firmware Release Number. The “X” is the major release number. The
“xxx” is the minor update number.

• Prosoft Configuration Builder (Version 2.2.2.3) & Drive Explorer


(Version 6.02.99 - Full) is used for the screen displays in this manual.
Different versions of the software may differ in appearance and
procedures.

8 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Chapter 1

Getting Started

The 20-750-PBUS Option Module is intended for installation into a PowerFlex


750-Series drive and is used for network communication.

Topic Page
Components 9
Features 10
Understanding Parameter Types 10
Compatible Products 11
Required Equipment 11
Safety Precautions 12
Quick Start 13
Status Indicators 14

Components Figure 1 - Components of the Option Module


➋ 8
7
6
5
4
3
➌ 2
1

Item Part Description


➊ Status Indicators Three LEDs to indicate the status of the Option Module and
network communications. Refer to Chapter 7, Troubleshooting.
➋ Node Address Switches Set the node address of the Option Module. Refer to Setting
(Switches 1 - 7) the Endianness and Node Address Switches on page 16.
Endianness Selection Switch Set endianness of data transmitted over network.
(Switch 8)
➌ Selection Jumper Profibus or Profidrive selection switch (this feature is not
supported in this version so by changing the jumper position it
will not have any effect. Profibus is selected in both positions).
➍ Profibus DB9 Female Profibus connection to the network.
Connector

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 9


Chapter 1 Getting Started

Features The features of the Option Module include:

• Captive screws to secure and ground the Option Module to the drive.

• Switches to set a node address before applying power to the drive.


Alternately, you can disable the switches and use an Option Module
parameter to configure the node address.

• Compatibility with various configuration tools to configure the Option


Module and host drive. The tools include the enhanced PowerFlex 7-Class
HIM (Human Interface Module 20-HIM-A6 or 20-HIM-C6S) on the
drive, and drive-configuration software such as DriveExplorer (version
6.01 or later) or DriveExecutive (version 5.01or later), DriveObserver
(version 5.01 or later) or ControlFlash (version 7.00 or later) or third party
Profibus configuration software like Prosoft Configuration Builder etc.

• Status indicators that report the status of the Option Module and network
communications. Indicators are visible when the drive cover is removed.

• Parameter-configurable 32-bit Datalinks in the I/O to meet application


requirements (16 Datalinks to write data from the network to the drive,
and 16 Datalinks to read data from the drive to the network).

• Acyclic Messaging support.

• Master-Slave hierarchy that can be set up so that the Option Module and
PowerFlex 750-Series drive transmit data to and from a master on the
network.

• User-defined fault actions to determine how the Option Module and


connected drive respond to:

– I/O messaging communication disruptions (Comm Flt Action)


– Controllers in idle mode (Idle Flt Action)
– Acyclic Messaging

Understanding Parameter The Option Module has two types of parameters:


Types • Device parameters are used to configure the Option Module to operate on
the network. Device parameters, when viewed using DriveExplorer or
DriveExecutive, appear below the 20-750-PBUS listing in the “treeview”
in a separate Device Parameters folder. When viewed using the
20-HIM-A6 or 20-HIM-C6S HIM, these parameters appear in the DEV
PARAM folder.

10 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Getting Started Chapter 1

• Host parameters are used to configure the Option Module Datalink


transfer and various fault actions with the drive. Host parameters, when
viewed using DriveExplorer or DriveExecutive, appear below the
20-750-PBUS listing in the “treeview” in a separate Host Parameters
folder. When viewed using the 20-HIM-A6 or 20-HIM-C6S HIM, these
parameters appear in the HOST PARAM folder.

Compatible Products At the time of publication, the Option Module is compatible with Allen-Bradley
PowerFlex 750-Series drives.

Required Equipment Equipment Shipped with the Option Module

When you unpack the Option Module, verify that the package includes:
❑ One 20-750-PBUS Profibus Option Module
❑ One Network Communication Option Card Installation Instructions
(publication 750COM-IN002)

User-Supplied Equipment

To install and configure the Option Module, you must supply:


❑ A small flathead screwdriver
❑ Profibus cable
Note: Only use cable that conforms to Profibus cable standards. Belden
#3079A Profibus cable or equivalent is recommended.
❑ One 9-pin, male D-Sub Profibus connector
Note: Profibus connectors are available from a variety of sources and in
various sizes. As such, there may be mechanical limitations that prohibit the
use of some connectors. Phoenix SUBCON-PLUS-PROFIB/AX/SC (Part
# 2744380) or Siemens 6GK1500-0FC00 or Brad BM5G60PP4Mxxx are
recommended for use with PowerFlex 750 drives.
❑ Configuration tool, such as:
– PowerFlex 20-HIM-A6 or 20-HIM-C6S
– DriveExplorer (version 6.01 or later), DriveObserver (version 5.01 or
later), ControlFlash (version 7.00 or later) or third party profibus
configuration software
– DriveExecutive stand-alone software (version 5.01 or later) or bundled
with the DriveTools SP suite (version 5.01 or later)
❑ Controller configuration software RSLogix 5000
❑ A PC connection to the Profibus DPV1 network

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 11


Chapter 1 Getting Started

Safety Precautions Please read the following safety precautions carefully.

ATTENTION: Risk of injury or death exists. The PowerFlex drive may


contain high voltages that can cause injury or death. Remove all power
from the PowerFlex drive, and then verify power has been discharged
before installing or removing the Option Module.
ATTENTION: Risk of injury or equipment damage exists. Only personnel
familiar with drive and power products and the associated machinery
should plan or implement the installation, start up, configuration, and
subsequent maintenance of the drive using the Option Module. Failure to
comply may result in injury and/or equipment damage.
ATTENTION: Risk of equipment damage exists. The Option Module
contains ESD (Electrostatic Discharge) sensitive parts that can be damaged
if you do not follow ESD control procedures. Static control precautions are
required when handling the Option Module. If you are unfamiliar with
static control procedures, see Guarding Against Electrostatic Damage
(publication 8000-4.5.2).
ATTENTION: Risk of injury or equipment damage exists. If the Option
Module is transmitting control I/O to the drive, the drive may fault when
you reset the Option Module. Determine how your drive will respond
before resetting the module.
ATTENTION: Risk of injury or equipment damage exists. Host
Parameters 33 - [Comm Flt Action], and 34 - [Idle Flt Action] let you
determine the action of the Option Module and connected drive if I/O
communication is disrupted, the controller is idle, or Acyclic messaging for
drive control is disrupted. By default, these parameters fault the drive. You
can set these parameters so that the drive continues to run. Precautions
should be taken to ensure that the settings of these parameters do not
create a risk of injury or equipment damage. When commissioning the
drive, verify that your system responds correctly to various situations (for
example, a disconnected cable or a controller in idle state).
ATTENTION: Risk of injury or equipment damage exists. When a system is
configured for the first time, there may be unintended or incorrect machine
motion. Disconnect the motor from the machine or process during initial
system testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in
this publication are intended solely for purposes of example. There are
many variables and requirements with any application. Rockwell
Automation, Inc. does not assume responsibility or liability (to include
intellectual property liability) for actual use of the examples shown in this
publication.

12 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Getting Started Chapter 1

Quick Start This section is provided to help experienced users quickly start using the Option
Module. If you are unsure how to complete a step, refer to the referenced chapter.
Step Action Refer to…
1 Review the safety precautions for the Option Throughout This Manual
Module.
2 Verify that the PowerFlex drive is properly installed. PowerFlex 750-Series AC Drive
Installation Instructions
(publication 750-IN001)
3 Install the Option Module. Network Communication Option
Verify that the PowerFlex drive is not powered. Then, insert Card Installation Instructions
the Option Module in drive Port 4, 5 or 6. Use the captive (publication 750COM-IN002) and
screws to secure and ground the Option Module to the Chapter 2,
drive. Then connect the Option Module to the network Installing the Option Module
using a Profibus cable.
4 Apply power to the Option Module. Chapter 2,
a. The Option Module receives power from the drive. Installing the Option Module
Verify that the Option Module is installed correctly
and then apply power to the drive. The status
indicators should be green. If they flash red, there is a
problem. Refer to Chapter 7, Troubleshooting.
b. Configure/verify key drive parameters.
5 Configure the Option Module for your application. Chapter 3,
Set Option Module parameters for the following functions Configuring the Option Module
as required by your application:
• Node address
• I/O configuration
• Master-Slave hierarchy
• Fault actions
6 Configure the Profibus Master to communicate with Chapter 4,
the Option Module. Configuring the Profibus Master
Use controller configuration tools such as Prosoft
Configuration Builder for Profibus and RSLogix 5000 to
configure master on the Profibus network to recognize the
Option Module and drive.
7 Configure the I/O. Chapter 5,
Use a controller configuration tool such as RSLogix 5000 Using the I/O
that enables you to control the Option Module and
connected drive using I/O.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 13


Chapter 1 Getting Started

Status Indicators The Option Module uses three status indicators to report its operating status.
They can be viewed with the drive cover removed (Figure 2).

Figure 2 - Status Indicators


8
7
6


5
4
3
2
1

Item Name
➊ PORT
➋ MOD
➌ NET A

After installing the Option Module and applying power to the drive, see Start-Up
Status Indications on page 20 for possible start-up status indications and their
descriptions.

14 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Chapter 2

Installing the Option Module


This chapter provides instructions for installing the Option Module in a
PowerFlex 750-Series drive.
Topic Page
Preparing for an Installation 15
Setting the Endianness and Node Address Switches 16
Connecting the Option Module to the Drive 18
Connecting the Option Module to the Network 18
Network Termination 20
Applying Power 20

Preparing for an Before installing the Option Module:


Installation • Read the Profibus Installation Guideline.

• Verify that you have all required equipment. See Required Equipment on
page 11.

ATTENTION: Risk of equipment damage exists. The Option Module


contains ESD (Electrostatic Discharge) sensitive parts that can be damaged
if you do not follow ESD control procedures. Static control precautions are
required when handling the Option Module. If you are unfamiliar with
static control procedures, refer to Guarding Against Electrostatic Damage
(publication 8000-4.5.2).

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 15


Chapter 2 Installing the Option Module

Setting the Endianness and Set the Endianness of the Option Module by using the Byte Swap switch No. 8
Node Address Switches (see Figure 3). The Byte Swap switch can be set to either open "0” (Ltl Endian) or
closed "1” (Big Endian) data formats for the cyclic data exchanged on the
network. The cyclic data consists of:
• CTRL : Logic Command Word (4 bytes)
• REF : Speed Reference (4 bytes)
• STAT : Logic Status Word (4 bytes)
• FEEDBACK : Speed Feedback (4 bytes)
• 0 to 16 Datalinks (4 bytes each)

Depending on the setting of the switch, the 4 bytes for each of the above data
items are swapped.

Figure 3 - Setting Option Module Node Address Switches

Byte
8
Swap
7

5
8
7
Node 4
Add 1-7
6
5
4
3
2 3
1

IMPORTANT Each node on the Profibus network must have a unique address. Set the
node address before power is applied because the Option Module
detects the node address during initialization (Power On Reset). To
change a node address, you must set the new value and then remove
and reapply power to (or reset) the Option Module.

16 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Installing the Option Module Chapter 2

Set the Node Address by setting Node Address switches 1 through 7 to their
binary equivalent, where '0' and '1' indicate switch positions 'Open' and 'Closed'
respectively. See Table 1.

Table 1 - Node Address Switches settings


Node Node Address Switch Number
Address 7 6 5 4 3 2 1
Value
00 0 0 0 0 0 0 0
01 0 0 0 0 0 0 1
02 0 0 0 0 0 1 0
03 0 0 0 0 0 1 1
04 0 0 0 0 1 0 0
05 0 0 0 0 1 0 1
06 0 0 0 0 1 1 0
07 0 0 0 0 1 1 1
08 0 0 0 1 0 0 0
09 0 0 0 1 0 0 1
10 0 0 0 1 0 1 0
11 0 0 0 1 0 1 1
12 0 0 0 1 1 0 0
13 0 0 0 1 1 0 1
14 0 0 0 1 1 1 0
15 0 0 0 1 1 1 1
16 0 0 1 0 0 0 0
17 0 0 1 0 0 0 1
18 0 0 1 0 0 1 0
19 0 0 1 0 0 1 1
20 0 0 1 0 1 0 0
‫ڭ‬
120 1 1 1 1 0 0 0
121 1 1 1 1 0 0 1
122 1 1 1 1 0 1 0
123 1 1 1 1 0 1 1
124 1 1 1 1 1 0 0
125 1 1 1 1 1 0 1

Descriptions of node address values are as follows.

Node Address Value Description


00 If the Node Address value is set to “00”, the Option Module uses the
Device Parameter 05 - [Net Addr Cfg] to set the Node Address. See
Setting the Node Address on page 24.
01-125 Node address used by the Option Module.
126 The default address setting.

The switch settings can be verified by viewing Device Parameter 06 - [Net Addr
Act] using a PowerFlex 20-HIM-A6/-C6S HIM, DriveExplorer software, or
DriveExecutive software.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 17


Chapter 2 Installing the Option Module

Connecting the Option The Option Module can be installed in the PowerFlex 750-Series Drive control
Module to the Drive pod in Port 4, 5 or 6. For details, see the Network Communication Option Card
Installation Instructions (publication 750COM-IN002), provided with the
Option Module. See Figure 3 for an example of the Option Module installed in
the drive.

IMPORTANT Remove power from the drive before installing the Option Module in the
drive control pod.

IMPORTANT Insert Option module into port 4, 5 or 6 and make sure to tighten the
module screws to the drive control pod to properly ground the module to
the drive. Torque both screws to 0.45…0.67 N•m (4.0…6.0 lb•in). Also,
verify that the black insulator band is installed around the module screw
closest to the Profibus female connector. The insulator prevents
inadvertent electrical contact with the male end of the Profibus
connector when connected.

Connecting the Option ATTENTION: Risk of injury or death exists. The PowerFlex drive may
Module to the Network contain high voltages that can cause injury or death. Remove power from
the drive, and then verify power has been discharged before connecting the
Option Module to the network.

1. Remove power from the drive.


2. Remove the drive cover and lift up the drive HIM bezel to its open
position to access the drive control pod.
3. Use static control precautions.
4. Route the Profibus cable through the bottom of the PowerFlex drive.
5. Connect a Profibus connector to the cable.
Note: Profibus connectors are available from a variety of sources and in
various sizes. As such, there may be mechanical limitations that prohibit
the use of some connectors. Phoenix SUBCON-PLUS-PROFIB/AX/SC
(Part # 2744380) or Siemens 6GK1500-0FC00 or Brad
BM5G60PP4Mxxx are recommended for use with PowerFlex 750 drives.

Figure 4 - Profibus Connector

18 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Installing the Option Module Chapter 2

6. Connect the Profibus cable to the Option Module and secure it with the
two screws on the connector.

Note: Profibus communication may not operate correctly if the cable


shield does not make full contact with the connector housing.

Figure 5 - Network Wiring Diagram

B A B A B A B A B A B A

Terminal Signal Function


Housing Shield Bus cable shield (outer screen that surrounds A and B conductors)
1 Not connected
2 Not connected
3 B-LINE Positive RxD/TxD, according to RS485 specification
4 RTS Request to send
5 GND BUS Network Zero Volt Reference (isolated from drive side)
6 +5V BUS +5V output to network (isolated from drive side)
7 Not connected
8 A-LINE Negative RxD/TxD according to RS485 specification
9 Not connected

7. Ground the Shield to reduce electrostatic pickup. However, shielding is


only effective when the shield is properly connected to ground. Refer to
the "Profibus Installation Guideline " for instructions to correctly ground
the shield.

Figure 6 - Wiring Example


PowerFlex 750-Series Drives (with
20-750-PBUS Option Modules)

ControlLogix
Controller

Profibus
Network

8. Connect the other end of the Profibus cable routed through the bottom of
the drive to the Profibus network.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 19


Chapter 2 Installing the Option Module

Network Termination The first and last node on a Profibus DP Network segment should be terminated.

Rockwell Automation recommends that the user select one of the


aforementioned Profibus connectors with built-in termination.

Applying Power ATTENTION: Risk of equipment damage, injury, or death exists.


Unpredictable operation may occur if you fail to verify that parameter
settings are compatible with your application. Verify that settings are
compatible with your application before applying power to the drive.

Apply power to the drive. The Option Module receives its power from the drive.
When you apply power to the Option Module for the first time, its topmost
“PORT” status indicator should be steady green or flashing green after
initialization. If it is red, there is a problem. See Chapter 7, Troubleshooting.

Start-Up Status Indications

The drive STS (status) indicator can be viewed on front of the drive after power
has been applied. The Option Module status indicators can be viewed with the
drive cover open or removed (Figure 7).

Figure 7 - Drive and Option Module Status Indicators

See Table 2 for


possible start-up
status indications
Drive Control Pod

20 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Installing the Option Module Chapter 2

Table 2 - Drive and Option Module Start-Up Status Indications


Item Name Color State Description
Drive STS Indicator
➊ STS Green Flashing Drive ready but not running, and no faults are present.
(Status) Steady Drive running, no faults are present.
Yellow Flashing When running, a type 2 (non-configurable) alarm condition
exists – drive continues to run. When stopped, a start
inhibit condition exists and the drive cannot be started
(see drive parameter 933 - [Start Inhibits]).
Steady A type 1 (user configurable) alarm condition exists, but the
drive continues to run.
Red Flashing A major fault has occurred. Drive will stop. Drive cannot
be started until fault condition is cleared.
Steady A non-resettable fault has occurred.
Red/Yellow Flashing Alternately A minor fault has occurred. Use drive parameter 950 -
[Minor Flt Config] to enable. If not enabled, acts like a
major fault. When running, the drive continues to run.
System is brought to a stop under system control. The
fault must be cleared to continue.
Yellow/Green Flashing Alternately When running, a type 1 alarm exists.
Green/Red Flashing Alternately Drive is flash updating.
Option Module Status Indicators
➋ PORT Off The Option Module is not powered or connected properly
to the drive.
Red Flashing The Option Module is not receiving any communication
from drive.
Steady The Option Module detected a duplicate or invalid port ID.
Green Flashing The Option Module is establishing communication with
drive.
Steady The Option Module is properly connected and
communicating with drive.
Orange Steady The drive to which Option Module is connected is not an
Allen-Bradley brand.
➌ MOD Off The Option Module is not powered or connected properly
to the drive.
Red Flashing The Option Module has failed the firmware test or Flash
update is in progress.
Steady The Option Module has failed the hardware test.
Green Flashing The Option Module is operational but is not transferring
I/O data.
Steady The Option Module is operational and is transferring I/O
data.
➍ NET A Off The Option Module cannot establish network
communication or has experienced a Communication
Timeout.
Red Flashing The Option Module has detected a Network Configuration
Error.
Steady The Option Module has experienced an internal network
controller error (Profibus ASIC Self-Test failure).
Green Steady The Option Module is properly connected and
communicating over the Profibus network.

After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see page 62 and page 63.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 21


Chapter 2 Installing the Option Module

Configuring/Verifying Key Drive Parameters

The PowerFlex 750-Series drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to receive control commands from a peripheral or terminal block, with the
Reference coming from the network. You could also set the drive to receive its
control from the network with the Reference coming from another peripheral or
terminal block. Or you could set the drive to receive both its control and
Reference from the network.

The following steps in this section assume that the drive will receive the Logic
Command and Reference from the network.

1. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed
reference source:
A. Set the Port field to “0” as shown in Figure 8.

Figure 8 - Drive Parameter 545 - [Spd Ref A Sel] Setup Screen

B. Set the Parameter field to point to the port (slot) in which the Option
Module is installed (for example, Port 4 Reference). The number “874”
in the Parameter field of the example screen above is the parameter in
the drive that identifies the port.
2. Verify that drive Parameter 930 - [Speed Ref Source] is reporting that the
source of the Reference to the drive (Port 0) is the port in which the
Option Module is installed (for example, Port 4 Reference). This ensures
that any Reference commanded from the network can be monitored by
using drive Parameter 002 - [Commanded SpdRef ]. If a problem occurs,
this verification step provides the diagnostic capability to determine
whether the drive/Option Module or the network is the cause.
3. If hard-wired discrete digital inputs are not used to control the drive, verify
that all unused digital input drive parameters are set to "0" (Not Used).

22 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Chapter 3

Configuring the Option Module

This chapter provides instructions and information to set the parameters to


configure the Option Module.
Topic Page
Configuration Tools 23
Using the PowerFlex 20-HIM-A6/-C6S HIM to Access Parameters 24
Setting the Node Address 24
Setting a Master-Slave Hierarchy (Optional) 24
Setting a Fault Action 27
Resetting the Option Module 28
Restoring Option Module Parameters to Factory Defaults 29
Viewing the Option Module Status Using Parameters 31
Flash Updating the Option Module 31

For a list of parameters, see Appendix B, Option Module Parameters. For


definitions of terms in this chapter, see the Glossary.

Configuration Tools The Option Module stores parameters and other information in its own
non-volatile memory. You must, therefore, access the Option Module to view and
edit its parameters. The following tools can be used to access the Option Module
parameters:
Tool Refer to…
PowerFlex 20-HIM-A6/-C6S HIM PowerFlex 20-HIM-A6/-C6S HIM (Human Interface Module)
User Manual
DriveExplorer Software http://www.ab.com/drives/driveexplorer, or DriveExplorer
(version 6.01or higher) online help (installed with the software)
DriveExecutive Software http://www.ab.com/drives/drivetools, or DriveExecutive
(version 5.01 or higher) online help (installed with the software)

IMPORTANT For the HIM screens shown throughout this chapter, the Option Module is
assumed to be installed in drive Port 04. If your Option Module is
installed in a different drive port, that port would appear instead of Port
04.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 23


Chapter 3 Configuring the Option Module

Using the PowerFlex If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it
20-HIM-A6/-C6S HIM to can be used to access parameters in the Option Module.

Access Parameters 1. Display the Status screen, which is shown on HIM power up.

2. Use the or key to scroll to the Port in which the Option


Module is installed.
3. Press the PAR# soft key to display the Jump to Param # entry pop-up box.
4. Use the numeric keys to enter the desired parameter number, or use the ▲
or ▼ soft key to scroll to the desired parameter number.

For details on viewing and editing parameters, see the PowerFlex


20-HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication
20-HIM-UM001.

Setting the Node Address If the Option Module Node Address switches (Figure 3) are set to “00”
(Program) the value of Device Parameter 05 - [Net Addr Cfg] determines the
node address. When in any other combination of positions, the Node Address
switches determine the node address.

1. Set the value of Device Parameter 05 - [Net Addr Cfg] to a unique node
address.

Figure 9 - Profibus Node Address Screen on LCD HIM

Stopped AUTO
0.00 Hz F

Edit Net Addr Cfg


1

0 << 126

ESC  ENTER

2. Reset the Option Module; see Resetting the Option Module on page 28.

Setting a Master-Slave This procedure is only required if Datalinks are used to write or read data of the
Hierarchy (Optional) drive or its connected peripherals. A hierarchy determines the type of device with
which the Option Module exchanges data. In a master slave hierarchy, the Option
Module exchanges data with a Profibus master such as ProSoft's
MVI56-PDPMV1 Profibus DP scanner. This scanner integrates, as a third party
module, in a ControlLogix PLC backplane to allow Profibus DP
communications.

24 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Option Module Chapter 3

Enabling Datalinks To Write Data

The controller output image (controller outputs-to-drive) can have anywhere


from 0 to 16 additional 32-bit parameters (Datalinks). They are configured using
Host Parameters 01 - [DL From Net 01] through Parameter 16 - [DL From
Net 16]. The data type of a Datalink can be either real or a 32 bit integer. The
number of Datalinks actively used is controlled by the connection size configured
in the controller. See the controller example sections in Chapter 4 for more
information on setting the connection size.

IMPORTANT Always use the Datalink parameters in consecutive numerical order,


starting with the first parameter. For example, use Host Parameters 01,
02, and 03 to configure three Datalinks to write data. Otherwise, the
network I/O connection will be larger than necessary, which needlessly
increases controller response time and memory usage.

When using a ControlLogix controller and the Generic Profile, configure the
Datalink parameters now as described in this section.

Host Parameters 01 - [DL From Net 01] through 16 - [DL From Net 16]
configure which parameters in the drive, Option Module, or any other connected
peripheral receive the values from the network. The PowerFlex 20-HIM-A6 or
20-HIM-C6S HIM, DriveExplorer software, or DriveExecutive software can be
used to select the drive or peripheral by port number and the parameter by name.
As an alternate method, the parameter value can be set manually by number using
this formula:
From Net Parameter Value = (10000 * port number) + (Destination Parameter Number)

For example, suppose you want to use Host Parameter 01 - [DL From Net 01] to
write to Parameter 03 of an optional encoder module plugged into drive Port 5.
Using the formula, the value for Host Parameter 01 - [DL From Net 01] would
be (10000 * 5) + (3) = 50003.

The following steps are required to enable Datalinks to write data:

1. Set the values of only the required number of contiguous


controller-to-drive Datalinks needed to write data to the drive and that are
to be included in the network I/O connection.
2. Reset the Option Module; see Resetting the Option Module on page 28.
3. Since the Logic Command and Reference is always used in the Option
Module, configure the parameters in the drive to accept the Logic
Command and Reference from the Option Module. When using the
controller for speed reference via the Option Module, set two fields in
drive Parameter 545 - [Speed Ref A Sel]:
a. Set the Port field for the drive (for example, 0 - PowerFlex 755).

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 25


Chapter 3 Configuring the Option Module

b. Set the Parameter field to identify the port in which the Option
Module is installed (for this example, Port 4 Reference). Also, verify
that the mask parameters in the drive (for example, Parameter 324 -
[Logic Mask]) are configured to receive the desired logic from the
Option Module. See the drive documentation for details.

After the above steps are complete, the Option Module is ready to receive
input data and transfer status data to the Profibus master (controller).
Next, configure the controller to recognize and transmit I/O to the
Option Module. Refer to Chapter 4, Configuring the Profibus Master.

Enabling Datalinks To Read Data

The controller input image (drive-to-controller inputs) can have 0 to 16


additional 32-bit parameters (Datalinks). They are configured using Host
Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16]. The number of
Datalinks actively used is controlled by the connection size in the controller. See
the controller example sections in Chapter 4 for more information on setting the
connection size.

IMPORTANT Always use the Datalink parameters in consecutive numerical order,


starting with the first parameter. For example, use Host Parameters 17,
18, 19, 20, and 21 to configure five Datalinks to read data. Otherwise, the
network I/O connection will be larger than necessary, which needlessly
increases controller response time and memory usage.

When using a ControlLogix controller and the Generic Profile, configure the
Datalink parameters now as described in this section.

Host Parameters 17 - [DL To Net 01] through 32 - [DL To Net 16] configure
which parameters in the drive, Option Module, or any other connected
peripheral send the values to the network. The PowerFlex 20-HIM-A6 or
20-HIM-C6S HIM, DriveExplorer software, or DriveExecutive software can be
used to select the drive or peripheral by port number and the parameter by name.
As an alternate method, the parameter value can be set manually by number using
this formula:
To Net Parameter Value = (10000 * Port Number) + (Origination Parameter Number)

For example, suppose you want to use Host Parameter 17 - [DL To Net 01] to
read Parameter 2 of an optional I/O module plugged into drive Port 6. Using the
formula, the value for Host Parameter 17 - [DL To Net 01] would be (10000 *
6)+ (2) = 60002.

The following steps are required to enable Datalinks to read data:

1. Set the values of only the required number of contiguous


drive-to-controller Datalinks needed to read data from the drive and that
are to be included in the network I/O connection.

26 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Option Module Chapter 3

2. Reset the Option Module; see Resetting the Option Module on page 28.

The Option Module is configured to send output data to the master (controller).
You must now configure the controller to recognize and transmit I/O to the
Option Module. Refer to Chapter 4, Configuring the Profibus Master.

Setting a Fault Action By default, when communications are disrupted (for example, a cable is
disconnected) or the master is idle, the drive responds by faulting if it is using I/O
from the network. You can configure a different response to:
• Disrupted I/O communication by using Host Parameter 33 - [Comm Flt
Action].
• An idle controller by using Host Parameter 34 - [Idle Flt Action].

ATTENTION: Risk of injury or equipment damage exists. Host


Parameters 33 - [Comm Flt Action], and 34 - [Idle Flt Action] let you
determine the action of the Option Module and connected drive if
communications are disrupted or the master is idle. By default, these
parameters fault the drive. You may configure these parameters so that the
drive continues to run, however, precautions should be taken to ensure that
the settings of these parameters do not create a risk of injury or equipment
damage. When commissioning the drive, verify that your system responds
correctly to various situations (for example, a disconnected network cable
or controller in idle state).

Changing the Fault Action

Set the values of Host Parameters 33 - [Comm Flt Action] and 34 - [Idle Flt
Action] to the desired responses:
Value Action Description
0 Fault The drive is faulted and stopped (default).
1 Stop The drive is stopped, but not faulted.
2 Zero Data The drive is sent 0 for output data after a communications disruption. This
does not command a stop.
3 Hold Last The drive continues in its present state after a communications disruption.
4 Send Flt Cfg The drive is sent the data that you set in the fault configuration parameters
(Host Parameter 37- [Flt Cfg Logic] through 54 - [Flt Cfg DL16]).

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 27


Chapter 3 Configuring the Option Module

Figure 10 - Edit Fault Action HIM Screens

Stopped AUTO Stopped AUTO


0.00 Hz F 0.00 Hz F

Edit Comm Flt Action Edit Idle Flt Action


Fault 0 Fault 0

0 << 4 0 << 4

ESC ▲ ▼  ENTER ESC ▲ ▼  ENTER

Changes to these parameters take effect immediately. A reset is not required.

If communication is disrupted and then is re-established, the drive will


automatically receive commands over the network again.

Setting the Fault Configuration Parameters


When setting Host Parameters 33 - [Comm Flt Action] and 34 - [Idle Flt
Action] to the “Send Flt Cfg,” the values in the following parameters are sent to
the drive after a communications fault and/or idle fault occurs. You must set
these parameters to values required by your application.
Option Module Host Parameter Description
Parameter 37 - [Flt Cfg Logic] A 32-bit value sent to the drive for Logic Command.
Parameter 38 - [Flt Cfg Ref] A 32-bit REAL (floating point) value sent to the drive for
Reference.
Parameter 39 - [Flt Cfg DL 01] A 32-bit integer value sent to the drive for a Datalink. If the
through destination of the Datalink is a REAL (floating point)
Parameter 54 - [Flt Cfg DL 16] parameter, you must convert the desired value to the
binary representation of the REAL value. (An internet
search of “hex to float” provides a link to a tool to do this
conversion.)

Changes to these parameters take effect immediately. A reset is not required.

Resetting the Option Changes to switch settings and some Option Module parameters require you to
Module reset the Option Module before the new settings take effect. You can reset the
Option Module by power cycling the drive or by using Device Parameter 07 -
[Reset Module].

ATTENTION: Risk of injury or equipment damage exists. If the Option


Module is transmitting control I/O to the drive, the drive may fault when
you reset the Option Module. Determine how your drive will respond
before resetting the Option Module.

Set Device Parameter 07 - [Reset Module] to “1” (Reset Module).

28 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Option Module Chapter 3

Figure 11 - Edit Reset Module HIM Screen

Stopped AUTO
0.00 Hz F Value Description
Edit Reset Module 0 Ready (Default)
Ready 0
1 Reset Module
0 << 2
2 Set Defaults
ESC ▲ ▼  ENTER

When you enter “1” (Reset Module), the Option Module will be immediately
reset. An alternate method to reset the module is by power cycling the drive.
When you enter “2” (Set Defaults), the Option Module will set ALL of its Device
and Host parameters to their factory default values. (This is the same as pressing
the ALL soft key when using the MEMORY folder method described in
Restoring Option Module Parameters to Factory Defaults on page 29). After
performing a Set Defaults, you must enter “1” (Reset Module) or power cycle the
drive so that the new values take effect. Thereafter, this parameter will be restored
to a value of “0” (Ready).

IMPORTANT When performing a Set Defaults, the drive may detect a conflict and then
not allow this function to occur. If this happens, first resolve the conflict
and then repeat Set Defaults action.

TIP If your application allows, you can also reset the Option Module by
cycling power to the drive (resetting the drive) or by using the HIM’s
Reset Device function located in the drive’s DIAGNOSTIC folder.

Restoring Option Module As an alternate method, you can restore the Option Module parameters using a
Parameters to Factory MEMORY folder menu item instead of using Device Parameter 07 - [Reset
Module] described in Resetting the Option Module on page 28. The MEMORY
Defaults folder method provides two ways to restore the Option Module Device and Host
parameters:
• ALL—Restores ALL Option Module Device and Host parameters to their
factory default values.
• MOST—Restores MOST Option Module Device and Host parameters—
except Device Parameter 05 - [Net Addr Cfg] which is used for network
setup.

To restore Option Module Device and Host parameters to their factory default
values:

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 29


Chapter 3 Configuring the Option Module

1. Access the Status screen, which is displayed on HIM power up.

Figure 12 - Status Screen

Stopped AUTO
0.00 Hz F

Host Drive
240V 4.2A
Rev 3.002 Ser. A
00
ESC REF PAR# TEXT

2. Use the or key to scroll to the Port in which the Option


Module is installed.

3. Press the key to display its last-viewed folder.

4. Use the or key to scroll to the MEMORY folder.

5. Use the or key to select Set Defaults.

6. Press the (Enter) key to display the Set Defaults pop-up box.

7. Press the (Enter) key again to display the warning pop-up box to
reset Device and Host parameters to their factory default values.
8. Press the MOST soft key to restore MOST Device and Host parameters to
factory defaults or press the ALL soft key to restore ALL parameters. Or
press the ESC soft key to cancel.

IMPORTANT When performing a Set Defaults, the drive may detect a conflict
and then not allow this function to occur. If this happens, first
resolve the conflict and then repeat this Set Defaults procedure.

9. Reset the Option Module using Device Parameter 07 - [Reset Module] or


by cycling power to the drive so that the restored parameters take effect.

30 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Option Module Chapter 3

Viewing the Option Module The following parameters provide information about the status of the Option
Status Using Parameters Module. You can view these parameters at any time.
Module Device Parameter Description
02 - [DLs From Net Act] The number of controller-to-drive Datalinks that are included in the
network I/O connection (controller outputs).
03 - [DLs To Net Act] The number of drive-to-controller Datalinks that are included in the
network I/O connection (controller inputs).
04 - [Net Addr Src] Displays the source from which the Option Module node address is
taken. This will be either “0” (Switches) set with the Node Address
switches shown in Figure 3, or “1” (Parameters) which uses the
address from Device Parameter 05 - [Net Addr Cfg].
06 - [Net Addr Act] The node address used by the Option Module. This will be one of the
following values:
• The address set by the node address switches Figure 3.
• The value of Device Parameter 05 - [Net Addr Cfg].
• An old address of the switches or parameter if they have been
changed and the Option Module has not been reset.

Flash Updating the Option The Option Module can be flash updated over the network or serially through a
Module direct connection from a computer to the drive using a 1203-USB or 1203-SSS
serial converter.

When flashing over the network, you can use the Allen-Bradley software tool
ControlFLASH, the built-in flash capability of DriveExplorer Lite or Full, or the
built-in flash capability of DriveExecutive.

When flashing through a direct serial connection from a computer to a drive, you
can use the same Allen-Bradley software tools described above, or you can use
HyperTerminal set to the X-modem protocol.

To obtain a flash update for this Option Module, go to


http://www.ab.com/support/abdrives/webupdate. This site contains all
firmware update files and associated Release Notes that describe firmware update
enhancements/anomalies, how to determine the existing firmware version, and
how to flash update using DriveExplorer, DriveExecutive, ControlFLASH or
HyperTerminal.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 31


Chapter 3 Configuring the Option Module

Notes:

32 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Chapter 4

Configuring the Profibus Master

Profibus Masters are available from several manufacturers, including Prosoft


Technology. This chapter provides instructions on how to use the
MVI56-PDPMV1 Profibus DPV1 Master to:
• Configure the MVI56-PDPMV1 Profibus DPV1 Master.
• Install the 20-750-PBUS GSD file in the software tool library.
• Configure the 20-750-PBUS as a PowerFlex 750 Profibus slave.
Topic Page
Example Network 33
Configure the MVI56-PDPMV1 Profibus DPV1 Master 34
GSD Installation 38
Slave Configuration 40

Example Network In this example, we will be configuring one PowerFlex 750-Series drive with a
20-750-PBUS Option Module, to be assigned as Station1 on a Profibus network.
This configuration shall be used as an example system throughout the rest of this
manual. Apart from the node address and Option Module mapping, most drives
will have identical configurations. This chapter describes the steps to configure a
simple network as shown in Figure 13.

Figure 13 - Example Profibus Network

Station 0

PowerFlex 750-Series
Drive Station 1

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 33


Chapter 4 Configuring the Profibus Master

Configure the To begin, start ProSoft Configuration Builder (PCB). ProSoft Configuration
MVI56-PDPMV1 Profibus Builder's window consists of a treeview on the left, an information pane and a
configuration pane on the right side of the window. When you first start PCB,
DPV1 Master the treeview consists of folders for DEFAULT PROJECT and DEFAULT
LOCATION, with a DEFAULT MODULE in the DEFAULT LOCATION
folder. Figure 14 shows the PCB window with a new project.

Figure 14 - Prosoft Configuration Builder Screen

Start configuring the module by adding the MVI56-PDPMV1 module to the


project.

1. Use the mouse to select Default Module in the treeview, and then click the
right mouse button to open a shortcut menu.

34 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Profibus Master Chapter 4

2. On the shortcut menu, choose CHOOSE MODULE TYPE. This action


opens the Choose Module Type dialog box. In the Select Module Type
dropdown list, select MVI56-PDPMV1(Figure 15).

Figure 15 - Module Type Selection Screen

3. For selected module MVI56-PDPMV1, there is a default list of ports as


shown in Figure 16.

Figure 16 - Default Ports for MVI56-PDPMV1 Module

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 35


Chapter 4 Configuring the Profibus Master

4. In the PCB treeview, click [+] to expand the MVI56-PDPMV1 tree,


right-click the PROFIBUS DP icon, and then select Configure
(Figure 17). This action opens the PROFIBUS Master Setup dialog box
(Figure 18).

Figure 17 - Configuring the Profibus Master Properties

5. In the PROFIBUS Master Setup dialog box in the Select Port dropdown
list, select Com1(Figure 18) if connected serially to the
MVI56-PDPMV1.

Figure 18 - Port Selection Screen

36 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Profibus Master Chapter 4

6. After selecting Com1, click Configure PROFIBUS (Figure 19).

Figure 19 - Opening the Profibus Configuration Screen

This action opens the ProSoft Configuration Builder for Profibus


MVI56-PDPMV1 configuration tool (Figure 20).

Figure 20 - Profibus Configuration Screen

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 37


Chapter 4 Configuring the Profibus Master

GSD Installation ProSoft Configuration Builder (PCB) uses Profibus slave definition files (GSD
files) to obtain basic configuration information about the Profibus slaves you add
to the network. The GSD configuration files identify the slave's capabilities so
that the MVI56-PDPMV1 module can communicate with it correctly.

For example: The 20-750-PBUS GSD file is named "20750D3B.gsd". It is the


GSD file for the drive’s 20-750-PBUS Option Module and can be downloaded
from http://www.ab.com/support/abdrives/webupdate. The configuration tool
only requires the 20-750-PBUS GSD file for the 20-750-PBUS Option Module
to be registered one time in this tool for configuring networks with this Option
Module.

Follow these steps to install the GSD file or files for your slave module or
modules.

1. Open the Tools menu, and choose Install new GS*-file... (Figure 21).

Figure 21 - Installing the GSD File

2. This action opens a dialog box that allows you to browse for the location of
the GSD (Figure 22).

Figure 22 - Selecting the GSD File

38 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Profibus Master Chapter 4

3. Choose the file to install, and then click Open. If the file already exists in
the configuration file path, you will be prompted to overwrite the file.
4. You will be prompted to associate the GSD configuration file with a
bitmap image of the slave (Figure 23).

Figure 23 - Bitmap Image Prompt

5. Use the File/Open dialog box to browse for the location of the image file to
use. If you have no specific bitmap file, you may Cancel the bitmap upload,
and a generic slave icon will be used in the Bus Configuration window for
this slave (Figure 24). Select the image files provided with GSD file for the
20-750-PBUS Option Module.

Figure 24 - GSD Image Selection

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 39


Chapter 4 Configuring the Profibus Master

6. This will prompt a screen showing the newly added slave in the treeview
(Figure 25).

Figure 25 - Selected Slave in Device List Treeview

Slave Configuration The following steps describe how to add and configure a 20-750-PBUS Option
Module as a Slave.

1. In ProSoft Configuration Builder tool, click the plus sign [+] to expand
the PROFIBUS DP treeview (Figure 26).

Figure 26 - Device Configuration - Available Options

40 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Profibus Master Chapter 4

2. Navigate to the Drives/Allen-Bradley folder containing the 20-750-PBUS


Slave to add, and then click the plus sign [+] to expand the folder.
3. Drag the Slave icon into the Bus Configuration window. This action adds
the slave to the Profibus network and configures it to the Master in a
networked relationship (Figure 27).

Figure 27 - Adding 20-750-PBUS Slave Module

4. In the treeview, click the plus sign [+] to expand the slave you added. This
action opens a list of device configuration values. Figure 27 shows the
possible input/output configuration values for a 20-750-PBUS Slave. The
Datalinks (1-16) allow the assignment of configured drive parameters to
be included in the Profibus DP I/O data frames that are transferred
between the ControlLogix PLC and the PowerFlex 750-Series drive.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 41


Chapter 4 Configuring the Profibus Master

5. Drag the input and output parameters to the Slot Location Grid
(Subscriber List) below the Bus Configuration window. This view displays
the slot number, configuration data, and starting input and output
addresses that will be assigned in the PLC memory for the
MVI56-PDPMV1 module. The MVI56-PDPMV1 Master uses this
information to identify and communicate with individual slaves on the
network (Figure 28).

Figure 28 - Inserting Ctrl/Stat & Ref/Fdbk (Device Configuration) into Slot 1

For this example, we will configure words of Ctrl/Stat & Ref/Fdbk. These
input and output 32-bit values are assigned to addresses within the
MVI56-PDPMV1 module's internal database. For each new slave added to
the Profibus network, PCB automatically converts the input/output byte
addresses to input and output image addresses for the tag database in the
ControlLogix processor.
6. Likewise add as many modules as required. All the modules from Ctrl/Stat
& Ref/Fdbk to Datalink16 can be added (Figure 29).

Figure 29 - Inserting Configuration Options into all Slots

42 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Profibus Master Chapter 4

7. Double-click the Slave icon to view the Slave Properties or right-click on


the slave icon and select Object Properties as shown in Figure 30.

Figure 30 - Choosing Slave Properties

8. PCB automatically assigns a Profibus address to each new slave. The


address assignment begins at address 3, and is incremented by 1 for each
new slave added to the network. You can change the address in the
Common tab of the Slave properties dialog box. The address should match
the PowerFlex 750-Series drive’s Profibus address assigned for the specific
drive you are configuring. PCB will not allow you to assign a Profibus
address that is already in use by another module on this network
(Figure 31).

Figure 31 - Profibus Address Selection

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 43


Chapter 4 Configuring the Profibus Master

9. Click on the value selection of the DP Mode parameter and, from the drop
down list, select DPV1 (Figure 32).

Figure 32 - DP Mode Selection

10. Click on the value selection of the Diagnostic Alarm parameter and, from
the drop down list, select Enabled (Figure 33).

Figure 33 - Enabling Diagnostic Alarm

44 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Configuring the Profibus Master Chapter 4

Downloading the Project to the Module

The following steps describe how to download the project to the


MVI56-PDPMV1 module. You need to connect to the module with the serial
cable, since it was described earlier that you would be using the Com1 port as the
interface.

1. Right-click the MVI56-PDPMV1 module and choose Download From


PC To Device.
2. In the "Select Connection Type" dropdown list, choose Com1. The default
path appears in the text box (Figure 34).

Figure 34 - Communication Port Selection

3. Click DOWNLOAD to start downloading the project to the


MVI56-PDPMV1 module (Figure 35).

Figure 35 - Download Project to MVI56-PDPMV1 Module

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 45


Chapter 4 Configuring the Profibus Master

4. After the configuration is transferred, it will automatically start rebooting


of the MVI56-PDPMV1 module (Figure 36).

Figure 36 - MVI56-PDPMV1 Module Rebooting

5. After rebooting the MVI56-PDPMV1 module, you can view the status of
download (Figure 37).

Figure 37 - Download Completed

46 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Chapter 5

Using the I/O

This chapter provides information and examples that explain how to control,
configure, and monitor a PowerFlex 750-Series drive using Profibus DPV0
messaging.
Topic Page
About I/O Messaging 47
Understanding the I/O Image 48
Using Logic Command/Status 48
Using Reference/Feedback 49
Using Datalinks 49
I/O Communication 51

ATTENTION: Risk of injury or equipment damage exists. The examples in


this publication are intended solely for purposes of example. There are
many variables and requirements with any application. Rockwell
Automation, Inc. does not assume responsibility or liability (to include
intellectual property liability) for actual use of the examples shown in this
publication.

About I/O Messaging Profibus DPV0 or I/O messaging is used to transfer the data which controls the
PowerFlex drive and its Reference. I/O messaging can also be used to transfer data
to and from Datalinks which are mapped to parameters in the PowerFlex
750-Series drives.

The Option Module includes the Logic Command, Logic Status, Reference, and
Feedback (32-bit words) in the controller’s I/O image. This basic I/O must
always be configured by the Profibus configuration tool to the 20-750-PBUS
Option Module, enabling the ability to control and monitor the PowerFlex
750-Series drive.

Additional I/O if needed, can be configured using up to 16 Datalinks to write


data and/or up to 16 Datalinks to read data. When using any combination of
these Datalinks, one 32-bit word for each Datalink will be added to the basic I/O
Input Size and/or Output Size.

Chapter 3, Configuring the Option Module, and Chapter 4, Configuring the


Profibus Master discuss how to configure the Option Module and controller on
the network for the required I/O.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 47


Chapter 5 Using the I/O

Understanding the I/O The terms input and output are defined from the controller’s point of view.
Image Therefore, output I/O is data that is produced by the controller and consumed by
the Option Module. Input I/O is status data that is produced by the Option
Module and consumed as input by the controller. The I/O image will vary based
on how many of the drive’s 32-bit Datalinks (Host DL From Net 01-16 and Host
DL To Net 01-16) are used.

Profibus Master Image

The I/O image can be configured based upon the number of Datalinks required
by the user. Table 3 shows the I/O image when using all of the 32-Bit Datalinks.

Table 3 - Profibus Master I/O Image for PowerFlex 750-Series Drives (32-bit Logic
Command/Status, Reference/Feedback, and Datalinks)
DINT Output I/O DINT Input I/O
0 Logic Command 0 Logic Status
1 Reference 1 Feedback
2 DL From Net 01 2 DL To Net 01
3 DL From Net 02 3 DL To Net 02
4 DL From Net 03 4 DL To Net 03
5 DL From Net 04 5 DL To Net 04
6 DL From Net 05 6 DL To Net 05
7 DL From Net 06 7 DL To Net 06
8 DL From Net 07 8 DL To Net 07
9 DL From Net 08 9 DL To Net 08
10 DL From Net 09 10 DL To Net 09
11 DL From Net 10 11 DL To Net 10
12 DL From Net 11 12 DL To Net 11
13 DL From Net 12 13 DL To Net 12
14 DL From Net 13 14 DL To Net 13
15 DL From Net 14 15 DL To Net 14
16 DL From Net 15 16 DL To Net 15
17 DL From Net 16 17 DL To Net 16

Using Logic The Logic Command is a 32-bit word of control data produced by the controller
Command/Status and consumed by the Option Module. The Logic Status is a 32-bit word of status
data produced by the Option Module and consumed by the controller.
• Logic Command word is always the first 32-bit word in the output image.
• Logic Status word is always the first 32-bit word in the input image.

This manual contains the bit definitions for compatible products available at the
time of publication in Appendix C, Logic Command/Status Words: PowerFlex
750-Series Drives.

48 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Using the I/O Chapter 5

Using Reference/Feedback The Reference is a 32-bit REAL (floating point) piece of control data produced by
the controller and consumed by the Option Module. The Feedback is a 32-bit
REAL (floating point) piece of status data produced by the Option Module and
consumed by the controller.
• Reference word is always the second 32-bit word in the output image.
• Feedback word is always the second 32-bit word in the input image.

The Reference and Feedback 32-bit REAL value represents drive speed. The
scaling for the speed Reference and Feedback are dependent on drive Parameter
300 - [Speed Units]. For example, if Parameter 300 is set to Hz, a 32- bit REAL
Reference value of "30.0" would equal a Reference of 30.0 Hz. If Parameter 300 is
set to RPM, a 32- bit REAL Reference value of "1020.5" would equal a Reference
of 1020.5 RPM. Note that the commanded maximum speed can never exceed the
value of drive Parameter 520 - [Max Fwd Speed]. Table 4 shows example
References and their results for a PowerFlex 750-Series drive that has its:
• Parameter 300 - [Speed Units] set to Hz.
• Parameter 37 - [Maximum Freq] set to130 Hz.
• Parameter 520 - [Max Fwd Speed] set to 60 Hz.

When Parameter 300 - [Speed Units] is set to RPM, the other parameters are also
in RPM.

Table 4 - PowerFlex 750-Series Drive Example Speed Reference/Feedback Scaling


Network Reference Value Speed Command Output Speed Network Feedback
Value (2) Value
130.0 130 Hz 60 Hz (3) 60.0
65.0 65 Hz 60 Hz (3) 60.0
32.5 32.5 Hz 32.5 Hz 32.5
0.0 0 Hz 0 Hz 0.0
-32.5 (1) 32.5 Hz 32.5 Hz 32.5
(1) The effects of values less than 0.0 depend on whether the PowerFlex 750 - Series drive uses a bipolar or
unipolar direction mode. See the drive documentation for details.
(2) For this example, drive parameter 300 - [Speed Units] is set to Hz.
(3) The drive runs at 60 Hz instead of 130 Hz or 65 Hz because drive Parameter 520 - [Max Fwd Speed] sets 60 Hz
as the maximum speed.

Using Datalinks A Datalink is a mechanism used by PowerFlex drives to transfer data to and from
the controller. Datalinks allow a drive parameter value to be read or written to
without using a Profibus DPV1 Service. When enabled, each Datalink occupies
one 32-bit word in a ControlLogix controller, providing a mirror of the
PowerFlex 750-Series drive data value that the Datalinked parameter represents.

The following rules apply when using PowerFlex 750-Series drive Datalinks:

• The target of a Datalink can be any Host parameter, including those of a


peripheral. For example, drive parameter 535 - [Accel Time 1] can be the
target of any or all Option Modules installed in the drive.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 49


Chapter 5 Using the I/O

• The data passed through the Datalink mechanism is determined by the


settings of Host Parameters 01...16 - [DL From Net 01-16] and Host
Parameters 17...32 - [DL To Net 01-16].

IMPORTANT A reset is always required after configuring Datalinks so that the


changes take effect.

• When an I/O connection that includes Datalinks is active, those Datalinks


being used are locked and cannot be changed until that I/O connection
becomes idle or inactive.

• When you use a Datalink to change a value, the value is NOT written to
the Non-Volatile Storage (NVS). The value is stored in volatile memory
and lost when the drive loses power. Thus, use Datalinks when you need to
change a value of a parameter frequently.

Datalinks for PowerFlex 750-Series peripherals (embedded EtherNet/IP adapter


and Option Modules such as an encoder or a communication module) are locked
when the peripheral has an I/O communication with a controller. When a
controller has an I/O communication to the drive, the drive does not allow a reset
to defaults, configuration download or anything else that could change the
makeup of the I/O communication in a running system. The I/O
communication with the controller must first be disabled to allow changes to the
respective Datalinks.

Depending on the controller being used, the I/O connection can be disabled by:
• Putting the controller in Program mode
• Disconnecting the drive from the network
• Placing the master in idle mode

DeviceLogix Datalinks are also locked while the DeviceLogix program is


running. The DeviceLogix program must first be disabled to allow changes to the
Datalinks. Set DeviceLogix parameter 53 - [DLX Operation] to “DisableLogic”
to disable the logic (the parameter value will then change to “LogicDisabld”).

TIP A COP (Copy) instruction or a UDDT is needed—for REAL parameters,


speed Reference, and speed Feedback only—to copy the DINT data into
a REAL word for input data conversion. For output data conversion, a COP
(Copy) instruction or UDDT is needed—for REAL parameters, speed
Reference, and speed Feedback only—to copy the REAL data into a DINT
word. To determine whether a parameter is a 32-bit integer (DINT) or a
REAL data type, see the Data Type column in the chapter containing
parameters in the PowerFlex 750-Series AC Drives Programming Manual
(publication 750-PM001).

50 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Using the I/O Chapter 5

I/O Communication The following example describes how to use Profibus DPV0 I/O communication
for the ControlLogix for Profibus master - MVI56-PDPMV1.

I/O data transferred to and from the 20-750-PBUS Option Module nodes can be
viewed in the MVI56-PDPMV1 ControlLogix controller tags for the DPV0
cyclic communication connections. See Figure 38 and Figure 39 for input and
output mapping in the MVI56-PDPMV1.

Figure 38 - Input Mapping in the MVI56-PDPMV1

Figure 39 - Output Mapping in the MVI56-PDPMV1

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 51


Chapter 5 Using the I/O

The input and output data can also be viewed through the ProSoft Configuration
Builder tool, while in the Monitor/Modify mode of operation. The PowerFlex
750-Series drive data is displayed under the value column for each of the
configured Profibus modules by selecting the "Online slave properties" tab as
shown in Figure 40.

Figure 40 - Online Slave Properties

52 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Chapter 6

Acyclic Messaging

This chapter provides information and examples that explain how to use Profibus
Class 1 DPV1 Acyclic Messaging to configure and monitor the PowerFlex
750-Series drive through the 20-750-PBUS Option Module.
Topic Page
About Acyclic Messaging 53
Acyclic Messaging for DPV1 Class 1 56
Example Messaging 56

ATTENTION: Risk of injury or equipment damage exists. The examples in


this publication are intended solely for purposes of example. There are
many variables and requirements with any application. Rockwell
Automation, Inc. does not assume responsibility or liability (to include
intellectual property liability) for actual use of the examples shown in this
publication.
ATTENTION: Risk of equipment damage exists. If Acyclic Messages are
programmed to write parameter data to Non-Volatile Storage (NVS)
frequently, the NVS will quickly exceed its life cycle and cause the drive to
malfunction. Do not create a program that frequently uses Acyclic
Messages to write parameter data to NVS. Datalinks do not write to NVS
and should be used for frequently changed parameters.

About Acyclic Messaging Acyclic Messaging is used to transfer data to the PowerFlex 750-Series drive
through the 20-750-PBUS Option Module and other connected peripherals that
do not require continuous updates. Acyclic messaging, or DPV1 messaging in the
case of the 20-750-PBUS Option Module is also used to configure and monitor a
drive's parameters on a Profibus network. Drive parameters as well as peripheral
Host and Device parameters can be accessed via acyclic messaging for a PowerFlex
750-Series drive. For a full list of drive parameters, refer to the Powerflex
750-Series AC Drives Programming Manual (publication 750-PM001) and for a
list of 20-750-PBUS Option Module Host and Device Parameters, see Appendix
B. To use acyclic messaging's read and write services, you need the values of the
slot and index to which a parameter is associated. Value ranges for slot & index
are shown in Table 5.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 53


Chapter 6 Acyclic Messaging

Table 5 - Profibus Slot and Index for Drive and Option Module Parameters

Profibus Slot Profibus Index Device Range (Dec)


0x00 0x00 - 0xFF Profibus Parameters(1) 0-255
0x01 - 0x3F 0x00 - 0xFF Host Drive (Port 0) 0-16383
0x40 - 0x43 0x00 - 0xFF Option Module 16384 - 17407
0x44 - 0x47 0x00 - 0xFF Port 1 Parameters 17408 - 18431
0x48 - 0x4B 0x00 - 0xFF Port 2 Parameters 18432 - 19455
0x4C - 0x4F 0x00 - 0xFF Port 3 Parameters 19456 - 20479
0x50 - 0x53 0x00 - 0xFF Port 4 Parameters 20480 - 21503
0x54 - 0x57 0x00 - 0xFF Port 5 Parameters 21504 - 22527
0x58 - 0x5B 0x00 - 0xFF Port 6 Parameters 22528 - 23551
0x5C - 0x5F 0x00 - 0xFF Port 7 Parameters 23552 - 24575
0x60 - 0x63 0x00 - 0xFF Port 8 Parameters 24576 - 25599
0x64 - 0x67 0x00 - 0xFF Port 9 Parameters 25600 - 26623
0x68 - 0x6B 0x00 - 0xFF Port 10 Parameters 26624 - 27647
0x6C - 0x6F 0x00 - 0xFF Port 11 Parameters 27648 - 28671
0x70 - 0x73 0x00 - 0xFF Port 12 Parameters 28672 - 29695
0x74 - 0x77 0x00 - 0xFF Port 13 Parameters 29696 - 30719
0x78 - 0x7B 0x00 - 0xFF Port 14 Parameters 30720 - 31743
0x7C - 0x7F 0x00 - 0xFF Reserved 31744 - 32767
0x80 - 0xBF 0x00 - 0xFF Reserved 32768 - 49151
0xC0 - 0xC3 0x00 - 0xFF Option Host Parameters 49152 - 50175
0xC4 - 0xC7 0x00 - 0xFF Port 1 Host Parameters 50176 - 51199
0xC8 - 0xCB 0x00 - 0xFF Port 2 Host Parameters 51200 - 52223
0xCC - 0xCF 0x00 - 0xFF Port 3 Host Parameters 52224 - 53247
0xD0 - 0xD3 0x00 - 0xFF Port 4 Host Parameters 53248 - 54271
0xD4 - 0xD7 0x00 - 0xFF Port 5 Host Parameters 54272 - 55295
0xD8 - 0xDB 0x00 - 0xFF Port 6 Host Parameters 55296 - 56319
0xDC - 0xDF 0x00 - 0xFF Port 7 Host Parameters 56320 - 57343
0xE0 - 0xE3 0x00 - 0xFF Port 8 Host Parameters 57344 - 58367
0xE4 - 0xE7 0x00 - 0xFF Port 9 Host Parameters 58368 - 59391
0xE8 - 0xEB 0x00 - 0xFF Port 10 Host Parameters 59392 - 60415
0xEC - 0xEF 0x00 - 0xFF Port 11 Host Parameters 60416 - 61439
0xF0 - 0xF3 0x00 - 0xFF Port 12 Host Parameters 61440 - 62463
0xF4 - 0xF7 0x00 - 0xFF Port 13 Host Parameters 62464 - 63487
0xF8 - 0xFB 0x00 - 0xFF Port 14 Host Parameters 63488 - 64511
0xFC - 0xFF 0x00 - 0xFF Reserved 64512 - 65535
(1) Parameters for Profibus identification and maintenance records.

For accessing any parameter within a drive, a general mechanism is used to map
the parameter with a Profibus slot and index number.

Every drive device port has a base slot number which supports 256 indices in a
slot. These slot and index combinations are mapped to various drive and Option
Module parameters through the 20-750-PBUS Option Module. The general
formula to arrive at slot and index numbers for a specific parameter is:

Slot Number = Base Slot Number + Quotient of (parameter number / 256)

Index Number = Remainder of (parameter number / 256)

54 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Acyclic Messaging Chapter 6

Due to Profibus standard requirements of various identification and maintenance


functions, there is an exception to the rule for assigning Host drive parameters.
When accessing drive parameters, the slot number will start at 0x01. The formula
for Host drive parameter is:

Slot Number = Base Slot Number + Quotient of (parameter number / 256) + 1

This is illustrated in the following examples:

Example 1: To access drive parameter 25 [Motor NP Volts], refer to Table 5 to


find the slot number associated with Port 0, which can be used to access the first
256 parameters. To access parameters 257 - 512, the slot number will increment
by 1, and so on.

For the Drive (Port 0), the base slot number is 0x00 + 1 (per the exception).
Therefore, the slot number can be calculated from the general formula as:

Slot Number = 0x00 + Quotient of (25 / 256) + 1 (for Drive Host


Parameters) = 0x01

The index number will be the remainder of the Drive Parameter number divided
by 256, as shown in this formula:

Index Number = Remainder of (25 / 256) = 25

Example 2: To access Device Parameter 5 - [Net Addr Cfg] in the Option


Module, when the Option Module is installed in Port 4 of the drive, refer to
Table 5 to find the Slot Number associated with Port 4.

For Port 4 Device parameters, the base slot number is 0x50. Therefore, the slot
number can be calculated from the general formula as:

Slot Number = 0x50 + Quotient of (5 / 256) = 0x50

The index number will be the remainder of the Port 4 Device Parameter number
divided by 256, as shown in this formula:

Index Number = Remainder of (5 / 256) = 5

Example 3: To access Host Parameter 37 - [Flt Cfg Logic] in the Option


Module, when the Option Module is installed in Port 4 of the drive, refer to
Table 5 to find the Slot Number associated with Port 4 Host Parameters.

For Port 4 Host parameters, the base slot number is 0xD0. Therefore, the slot
number can be calculated from the general formula as:

Slot Number = 0xD0 + Quotient of (37 / 256) = 0xD0

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 55


Chapter 6 Acyclic Messaging

The index number will be the remainder of the Port 4 Host Parameter number
divided by 256, as shown in this formula:

Index Number = Remainder of (37 / 256) = 37

Acyclic Messaging for The 20-750-PBUS PowerFlex 750-Series drives Option Module provides the
DPV1 Class 1 following Profibus DPV1 Class 1 Acyclic Services:

READ: This service is used to read a PowerFlex 750-Series drive or Option


Module’s parameter.

WRITE: This service is used to modify a PowerFlex 750-Series drive or Option


Module’s parameter.

Example Messaging Examples of using Profibus DPV1 Class 1, Acyclic Messaging to read and write a
drive parameter is described in this section.

Read Example for Drive Parameter 1 - [Output Frequency]

To read the drive Parameter 1 - [Output Frequency] from the PowerFlex


750-Series drive using a Class 1 Acyclic Read Service, setup a ControlLogix
controller (with a MVI56-PDPMV1 Profibus Master). After the master is setup,
the ControlLogix tags must be populated with the values to read the parameter as
shown in Figure 41.

Drive Parameter 1 - [Output Frequency]:


• Slot Number = 0x00 + Quotient of (1 / 256) + 1= 1
• Index Number = Remainder of (1 / 256) = 1
• Length in bytes of the value of the parameter (32 bit floating point value) /
8=4

To test the Read service, you may manually enter the values as shown below into
the MVI56-PDPMV1 controller scoped tags where a ProSoft MVI56-PDPMV1
Profibus master module is installed in the backplane of the ControlLogix rack.
• MVI56PDPMV1.Mailbox.AcyclicRead.Out.SlotNumber = 1
• MVI56PDPMV1.Mailbox.AcyclicRead.Out.SlaveAddress = 3
• MVI56PDPMV1.Mailbox.AcyclicRead.Out.Length = 4
• MVI56PDPMV1.Mailbox.AcyclicRead.Out.Index = 1

Next, manually enter a value of '1' into the


MVI56PDPMV1.MailboxCommand.AcyclicRead tag, to send the message.

56 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Acyclic Messaging Chapter 6

Figure 41 - Acyclic Class 1 Read for Parameter 1 - [Output Frequency]

When the message response returns successfully, the data for the Output
Frequency parameter will be placed in the tags
MVI56PDPMV1.Mailbox.AcyclicRead.In.Data[] byte array. In the PLC
program, the return message data may be copied to a locally configured program
tag, and converted by correctly assigning the data type for the Local tag to which
the data returned from the read request matches. In the case of drive Parameter 1
- [Output Frequency] as in this example, the local tag's data type should be a
floating point or a "REAL" data type.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 57


Chapter 6 Acyclic Messaging

Acyclic Class 1 Read response data can be viewed as shown in Figure 42.

Figure 42 - Acyclic Class 1 Read Response Data for Parameter 1 - [Output


Frequency]

Figure 43 shows the RSLogix ladder logic example, that may be used to interface
the MVI56-PDPMV1 module’s functional block and perform continuous DPV1
Acyclic Read operations.

Figure 43 - Acyclic Class 1 Read Response Data on RSLogix

Write Example for Drive Parameter 520 - [Max Fwd Speed]

To write the Parameter 520 - [Max Fwd Speed] to the PowerFlex 750-Series drive
using a Class 1 Acyclic Write Service, setup a ControlLogix controller (with a
MVI56-PDPMV1 Profibus Master). After the master is setup, the ControlLogix
tags must be populated with the correct slot and index addressing values to write
the parameter as shown in Figure 44.

Drive Parameter 520 - [Max Fwd Speed]:


• Slot No. = 0x00 + Quotient of (520 / 256) + 1 = 3
• Index No. = Remainder of (520 / 256) = 8
• Length in bytes of the value of the Parameter (32 bit floating point value) /
8=4

58 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Acyclic Messaging Chapter 6

To test the Write Service, you may manually enter the values as shown below into
the MVI56-PDPMV1 controller scoped tags where a ProSoft MVI56-PDPMV1
Profibus master module has been installed in the backplane of the ControlLogix
rack.
• MVI56PDPMV1.Mailbox.AcyclicWrite.Out.SlotNumber = 3
• MVI56PDPMV1.Mailbox.AcyclicWrite.Out.SlaveAddress = 3
• MVI56PDPMV1.Mailbox.AcyclicWrite.Out.Length = 4
• MVI56PDPMV1.Mailbox.AcyclicWrite.Out.Index = 8

The data bytes to be written can be entered in the


MVI56PDPMV1.Mailbox.AcyclicWrite.Out.Data[] array, or the data may be
copied via ladder logic and a locally configured program tag which represents the
correct data type, for the data value, to be written to drive Parameter 520. In this
case the value would be a floating point or "REAL" data type. The value shown in
Figure 44, indicates a value of 60.00 Hz.

Figure 44 - Acyclic Class 1 Write for Parameter 520 - [Max Fwd Speed]

To manually trigger the message to be sent, enter a value of '1' into the
MVI56PDPMV1.MailboxCommand.AcyclicWrite tag.

The message response status indicates success, when the data in the
"MVI56PDPMV1.Mailbox.AcyclicWrite.In.ErrorDecode" tag is a value of 0x00.
Note that any non-zero value indicates an error has occurred.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 59


Chapter 6 Acyclic Messaging

Acyclic Class 1 Write response data can be viewed as shown in Figure 45.

Figure 45 - Acyclic Class 1 Write Response Data for Parameter 520 - [Max Fwd
Speed]

60 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Chapter 7

Troubleshooting

This chapter provides information for diagnosing and troubleshooting potential


problems with the Option Module and network.
Topic Page
Understanding the Status Indicators 61
PORT Status Indicator 62
MOD Status Indicator 63
NET A Status Indicator 63
Viewing Option Module Diagnostic Items 64
Viewing and Clearing Events 65

Understanding the Status The Option Module has three status indicators. They can be viewed with the
Indicators drive cover removed (Figure 46).

Figure 46 - Status Indicators

Item Status Indicator Description Page


➊ PORT DPI Connection Status 62
➋ MOD Option Module Status 63
➌ NET A Profibus Status 63

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 61


Chapter 7 Troubleshooting

PORT Status Indicator This red/green bicolor LED indicates the status of the Option Module’s
connection to the drive as shown in the table below.
Status Cause Corrective Action
Off The Option Module is not powered or connected • Securely connect and ground the Option Module to the
properly to the drive. drive by fully inserting it into the drive port and tightening
its two captive screws to the recommended torque.
• Apply power to the drive.
Flashing Red The Option Module is not receiving any • Verify that cables are securely connected.
communication from drive. • Cycle power to the drive.
Steady Red The Option Module detected a duplicate or invalid Important: Cycle power to the drive after making any of the
port ID. following corrections:
• Securely connect and ground the Option Module to the
drive by fully inserting it into the drive port and tightening
its two captive screws to the recommended torque.
• Configure the Option Module and PowerFlex drive to use a
Datalink that is not already being used by another
peripheral.
Flashing The Option Module is establishing communication No action required. This status indicator will turn steady
Green with drive. green or red.
Steady The Option Module is properly connected and No action required.
Green communicating with drive.
Steady The brand of the Option Module and drive do not Connect the Option Module to a compatible product of the
Orange match. same brand (an Allen-Bradley PowerFlex 750-Series drive).

62 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Troubleshooting Chapter 7

MOD Status Indicator This red/green bicolor LED indicates the status of the Option Module as shown
in the table below.
Status Cause Corrective Action
Off The Option Module is not powered or connected • Securely connect and ground the Option Module to the
properly to the drive. drive by fully inserting it into the drive port and tightening
its two captive screws to the recommended torque.
• Apply power to the drive and network.
Flashing The Option Module has failed the firmware test. • Cycle power to the drive. Parameter settings may have
Red been changed.
• Clear faults in the Option Module.
• If cycling power does not correct the problem, the Option
Module parameter settings may have been corrupted.
Reset defaults and reconfigure the Option Module.
• If resetting defaults does not correct the problem, flash
the Option Module with the latest firmware release.
Steady The Option Module has failed the hardware test. • Cycle power to the drive.
Red • Replace the Option Module.
Flashing Green The Option Module is operational but is not • Place the master in RUN mode.
transferring I/O data. • Configure the Option Module for the program in the
controller.
• Program the controller to recognize and transmit I/O to the
Option Module.
• Normal behavior if no I/O is being transferred.
Steady Green The Option Module is operational and is No action required.
transferring I/O data.

NET A Status Indicator This red/green bicolor LED indicates the status of the Profibus connection to the
drive 20-750-PBUS Option Module as shown in the table below.
Status Cause Corrective Actions
Off The Option Module cannot establish network • Securely connect the Option Module to the drive and
communication or has experienced a connect it to the network using a Profibus cable.
Communication Timeout. • Correctly connect the Profibus cable to the Profibus
connector.
• Apply power to the drive.
Flashing Red The Option Module has detected a Network Re-configure the Profibus module.
Configuration Error.
Steady Red Thje Option Module has experienced an internal • Cycle power to the drive.
network controller error (Profibus ASIC Self-Test • Re-configure the Profibus master.
failure).
Steady Green The Option Module is properly connected and No action required.
communicating over the Profibus network.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 63


Chapter 7 Troubleshooting

Viewing Option Module If you encounter unexpected communications problems, the Option Module’s
Diagnostic Items diagnostic items may help you or Rockwell Automation personnel troubleshoot
the problem. Option Module diagnostic items can be viewed using the PowerFlex
20-HIM-A6/-C6S HIM, DriveExplorer software (version 6.01 or later), or
DriveExecutive software (version 5.01 or later). For details on viewing diagnostic
items using the HIM, refer to the PowerFlex 20-HIM-A6/-C6S HIM (Human
Interface Module) User Manual, publication 20HIM-UM001.
Table 6 - Option Module Diagnostic Items
No. Name Description
1 Common Logic Cmd The present value of the Common Logic Command being transmitted to the drive by this Option Module.
2 Prod Logic Cmd The present value of the Product Logic Command being transmitted to the drive by this Option Module from the controller.
3 Reference The present value of the Reference being transmitted to the drive by this Option Module.
4 Common Logic Sts The present value of the Common Logic Status being received from the drive by this Option Module.
5 Prod Logic Sts The present value of the Product Logic Status being received from the drive by this Option Module from the controller.
6 Feedback The present value of the Feedback being received from the drive by this Option Module.
7 Input Size The size of the input image in bytes transferred from the network to the drive.
8 Output Size The size of the output image in bytes transferred from the drive to the network.
9 DL Fr Net Avail The number of Host DL From Net xx Datalinks currently available to the Option Module.
10 DL To Net Avail The number of Host DL To Net xx Datalinks currently available to the Option Module
11 DL Fr Net 01 Val The present value of respective Host DL From Net xx parameter being transmitted to the drive by this Option Module. (If not
12 DL Fr Net 02 Val using a Datalink, its respective value should be zero.)
13 DL Fr Net 03 Val
14 DL Fr Net 04 Val
15 DL Fr Net 05 Val
16 DL Fr Net 06 Val
17 DL Fr Net 07 Val
18 DL Fr Net 08 Val
19 DL Fr Net 09 Val
20 DL Fr Net 10 Val
21 DL Fr Net 11 Val
22 DL Fr Net 12 Val
23 DL Fr Net 13 Val
24 DL Fr Net 14 Val
25 DL Fr Net 15 Val
26 DL Fr Net 16 Val
27 DL To Net 01 Val The present value of respective Host DL To Net xx parameter being received from the drive by this Option Module. (If not
28 DL To Net 02 Val using a Datalink, its respective value should be zero.)
29 DL To Net 03 Val
30 DL To Net 04 Val
31 DL To Net 05 Val
32 DL To Net 06 Val
33 DL To Net 07 Val
34 DL To Net 08 Val
35 DL To Net 09 Val
36 DL To Net 10 Val
37 DL To Net 11 Val
38 DL To Net 12 Val
39 DL To Net 13 Val
40 DL To Net 14 Val
41 DL To Net 15 Val
42 DL To Net 16 Val
43 DPI Rx Errs The present value of the DPI Receive error counter.

64 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Troubleshooting Chapter 7

Table 6 - Option Module Diagnostic Items (Continued)


No. Name Description
44 DPI Rx Errs Max The maximum value (since reset) of the DPI Receive Error counter.
45 DPI Tx Errs The present value of the DPI Transmit error counter.
46 DPI Tx Errs Max The maximum value (since reset) of the DPI Transmit Error counter.
47 Net RX Cnt Number of Profibus telegrams received by Profibus ASIC.
48 Net RX Err Cnt Number of erroneous Profibus telegrams received by the Profibus ASIC since the last time it went into Data Exchange mode.
49 Net RX Terr Cnt Total number of erroneous Profibus telegrams received by the Profibus ASIC since the last power cycle.
50 Boot Flash Count Number of times the boot firmware in the Option Module has been flash updated.
51 App Flash Count Number of times the application firmware in the Option Module has been flash updated.

Viewing and Clearing The Option Module has an event queue to record significant events that occur in
Events the operation of the module. When such an event occurs, an entry consisting of
the event’s numeric code and a timestamp is put into the event queue. You can
view the event queue using the PowerFlex 20-HIM-A6/-C6S HIM,
DriveExplorer (6.01 or later) software, or DriveExecutive (5.01 or later) software.
For details on viewing and clearing events using the HIM, refer to the PowerFlex
20-HIM-A6/-C6S HIM (Human Interface Module) User Manual (publication
20HIM-UM001).

The event queue can contain up to 32 entries, which are stored in EEPROM
Memory on the Option Module — making the event queue non-volatile.
Eventually the event queue will become full, since its contents are retained
through Option Module power cycles and resets. At that point, a new entry
replaces the oldest entry. Only an event queue clear operation or the corruption
of the EEPROM group containing the event queue will clear the event queue
contents. In the latter case, the Option Module will not generate a fault to
indicate that the event queue was corrupted.

Resetting the Option Module to defaults has no effect on the event queue, other
than to log a Code 58 “Module Defaulted” event.

Many events in the event queue occur under normal operation. If you encounter
unexpected communications problems, the events may help you or Allen-Bradley
personnel troubleshoot the problem. The following events may appear in the
event queue.
Table 7 - Option Module Events
Code Event Text Description
Option Module Events
1 No Event Text displayed in an empty event queue entry.
2 Device Power Up Power was applied to the Option Module.
3 Device Reset The Option Module was reset.
4 EEPROM CRC Error The EEPROM checksum/CRC is incorrect, which limits Option Module functionality. Default parameter values must be
loaded to clear this condition.
5 App Updated The application firmware has been flash updated.
6 Boot Updated The boot firmware has been flash updated.
7 Watchdog Timeout The software watchdog detected a failure and reset the module.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 65


Chapter 7 Troubleshooting

Table 7 - Option Module Events (Continued)


Code Event Text Description
DPI Events
8 DPI Bus Off A bus-off condition was detected on DPI.
9 DPI Ping Timeout A ping message was not received on DPI within the specified time.
10 DPI Port Invalid The Option Module was not connected to a valid port on a DPI product.
11 DPI Port Changed The DPI port changed after start up.
12 DPI Host Reset The drive sent a reset event message.
13 DPI Baud 125kbps The Option Module detected that the drive was communicating at 125 kbps.
14 DPI Baud 500kbps The Option Module detected that the drive was communicating at 500 kbps.
15 DPI Host Invalid The Option Module was connected to an incompatible product.
16 DPI Dup Port Another peripheral with the same port number is already in use.
17 DPI Type 0 Logon The Option Module has logged in for Type 0 control.
18 DPI Type 0 Time The Option Module has not received a Type 0 status message within the specified time.
19 DPI DL Logon The Option Module has logged into a Datalink.
20 DPI DL Error The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another
peripheral.
21 DPI DL Time The Option Module has not received a Datalink message within the specified time.
22 DPI Ctrl Disable The Option Module has sent a “Soft Control Disable” command to the drive.
23 DPI Ctrl Enable The Option Module has sent a “Soft Control Enable” command to the drive.
24 DPI Msg Timeout A Client-Server message sent by the Option Module was not completed within 1 second.
25 DPI Manual Reset The Option Module was reset by changing its Reset Module parameter.
SI Events
26 SI Online The Option Module has logged into the Serial Interface Communications.
27 SI Logon Error The Option Module failed to log into the Serial Interface.
28 SI Comm Fault The Serial Interface Communications has faulted.
Network Events
29 Net Link Up A network link was available for the Option Module.
30 Net Link Down The network link was removed from the Option Module.
31 Net Dup Address The Option Module uses the same address as another device on the network.
32 Net Comm Fault The Option Module detected a communications fault on the network.
33 Net Sent Reset The Option Module received a reset from the network.
34 Net IO Close An I/O connection from the network to the Option Module was closed.
35 Net Idle Fault The Option Module detected an idle fault condition on the network (Master in programming mode or slave
parameterization in progress).
36 Net IO Open An I/O connection from the network to the Option Module has been opened.
37 Net IO Timeout An I/O connection from the network to the Option Module has timed out.
38 Net IO Size Err The Option Module received an incorrectly sized I/O packet.
39-56 Reserved —
57 Option Card Flt Internal Option Module faults.
58 Module Defaulted The Option Module has been set to defaults.
59 Net Freeze Freeze command has been issued by the PROFIBUS master for this Option Module.
60 Net Unfreeze Unfreeze command has been issued by the PROFIBUS master for this Option Module.
61 Net Sync Sync command has been issued by the PROFIBUS master for this Option Module.
62 Net Unsync Unsync command has been issued by the PROFIBUS master for this Option Module.
63 Net Clear Cmd The Option Module received a PROFIBUS "Clear Command" from the network master.
64 Net Set Prm The Option Module received a PROFIBUS "Set Parameters" command from the network master.
65 Net WD Timeout The PROFIBUS ASIC has declared a network timeout.

66 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Appendix A

Specifications

Appendix A presents the specifications for the Option Module.


Topic Page
Communications 67
Electrical 67
Mechanical 67
Environmental 68
Regulatory Compliance 68

Communications Network
Protocol Profibus
Data Rates 9.6K, 19.2K, 45.45K, 93.75K, 187.5K, 500K, 1.5M, 3M, 6M, and
12M. The Option Module has auto baud rate detection.
Media Profibus Cable with DB9 connector
Drive
Protocol DPI
Data Rates 500k

Electrical Consumption
Drive 250 mA at 14 VDC supplied by the host drive
Network None

Mechanical Dimensions
Height 15.76mm (0.62 inches)
Length 130 mm (5.12 inches)
Width 83 mm (3.27 inches)
Weight 57 g (2 oz.)

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 67


Appendix A Specifications

Environmental Temperature
Operating -5...65 °C (30...149 °F)
Storage -40...85 °C (-40...185 °F)
Humidity
Operating 5...80% non condensing
Non-Operating 5...95% non condensing
Shock (Operating) 15 g peak acceleration
Vibration
Operating 2.0 g at 55...512 Hz
Non-Operating 5 g at 5 Hz...2 kHz
Atmosphere Important: The Option Module must not be installed in an area
where the ambient atmosphere contains volatile or corrosive gas,
vapors or dust. If the Option Module is not going to be installed
for a period of time, it must be stored in an area where it will not
be exposed to a corrosive atmosphere.

Regulatory Compliance Certification Specification


UL UL508C
CE IEC50178 and IEC61800-3
cUL CAN/ CSA C22.2 No.14-M91
CTick EN61800-3

NOTE: This is a product of category C2 according to IEC 61800-3. In a


domestic environment this product may cause radio interference in which case
supplementary mitigation measures may be required.

68 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Appendix B

Option Module Parameters

Appendix B provides information about the Option Module parameters.


Topic Page
Parameter Types 69
About Parameter Numbers 69
How Parameters Are Organized 69
Device Parameters 70
Host Parameters 72

Parameter Types The Option Module has two types of parameters:

• Device parameters are used to configure the Option Module to operate on


the network. Device parameters, when viewed using DriveExplorer or
DriveExecutive, appear below the 20-750-PBUS listing in the treeview in a
separate Device Parameters folder. When viewed using the HIM, these
parameters appear in the DEV PARAM folder.

• Host parameters are used to configure the Option Module Datalink


transfer and various fault actions with the drive. Host parameters, when
viewed using DriveExplorer or DriveExecutive, appear below the
20-750-PBUS listing in the treeview in a separate Host Parameters folder.
When viewed using the HIM, these parameters appear in the HOST
PARAM folder.

About Parameter Numbers Each parameter set is numbered consecutively.


Configuration Tool Numbering Scheme
• DriveExplorer The Device parameters and Host parameters begin with parameter 01.
• DriveExecutive For example, Device Parameter 01 - [DPI Port] and Host Parameter 01
• HIM - [Net to Drv DL 01] are Parameter 1 as indicated by this manual.
• Acyclic Messaging See Chapter 6, Acyclic Messaging.

How Parameters Are The Device Parameters and Host Parameters are separately displayed in a
Organized Numbered List view order.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 69


Appendix B Option Module Parameters

Device Parameters Parameter


No Name & Description Details
01 [Port Number] Default: 5
Displays the drive port into which the Option Minimum: 0
Module is installed. Typically, this will be Port 4, 5 or Maximum: 7
6. Type: Read Only
02 [DLs From Net Act] Default: 0
Displays the number of actual controller-to-drive Minimum: 0
Datalinks that the drive is using based on the I/O Maximum: 16
connection opened by the controller. Type: Read Only
03 [DLs To Net Act] Default: 0
Displays the number of actual drive-to-controller Minimum: 0
Datalinks that the controller is using based on the Maximum: 16
I/O connection opened by the controller. Type: Read Only
04 [Net Addr Src] Default: 0 = Switches
Displays the source from which the Option Module Values: 0 = Switches
node address is taken. This will be either the Node 1 = Parameters
Address switches (see Figure 3 and Table 1) or the Type: Read Only
value of Device Parameter 05 - [Net Addr Cfg].
05 [Net Addr Cfg] Default: 126
Sets the network node address for the Option Minimum: 0
Module if Device Parameter 04 - [Net Addr Src] is Maximum: 126
set to “1” (Parameters). Type: Read/Write
06 [Net Addr Act] Default: 126
Displays the actual network node address used by Minimum: 0
the Option Module. Maximum: 126
Type: Read Only
07 [Reset Module] Default: 0 = Ready
No action if set to “0” (Ready). Resets the Option Values: 0 = Ready
Module if set to “1” (Reset Module). Restores the 1 = Reset Module
Option Module to its factory default settings if set to 2 = Set Defaults
“2” (Set Defaults). This parameter is a command. It Type: Read/Write
will be reset to “0” (Ready) after the command has Reset Required: No
been performed.
When performing a Set Defaults, the drive may
detect a conflict. If this occurs, the drive will not
allow a Set Defaults action. You must resolve the
conflict before attempting a Set Defaults action for
the Option Module.

ATTENTION: Risk of injury or equipment damage exists. If the Option


Module is transmitting I/O that controls the drive, the drive may fault when
you reset the Option Module. Determine how your drive will respond
before resetting the Option Module.

70 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Option Module Parameters Appendix B

Parameter
No Name & Description Details
08 [Net Data Format] Default: 0 = Ltl Endian
Displays the byte alignment for the network data as Values: 0 = Ltl Endian
selected using the data-swap switch. 1 = Big Endian
Type: Read Only
09 [PROFIBUS Mode] Default: 0 = Normal
Displays the Profibus operation mode selected by Values: 0 = Normal
the user using the mode selection jumper. This will 1 = PROFIdrive
be either Normal or PROFIdrive (PROFIdrive is not Type: Read Only
supported in this version. It is reserved for future
Firmware update).
10 [PROFIBUS Alarms] Default: 0 = Enable
Enables or disables generation of alarms on Values: 0 = Enable
Profibus. 1 = Disable
Type: Read/Write
11 [DPV1 Map Mode] Default: 0 = Standard
Enables S7 Controller compatibility. Values: 0 = Standard
1 = S7 Comp
Type: Read/Write

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 71


Appendix B Option Module Parameters

Host Parameters Parameter


No Name & Description Details
01 [DL From Net 01] Default: 0
02 [DL From Net 02] Default: 0
03 [DL From Net 03] Default: 0
04 [DL From Net 04] Default: 0
05 [DL From Net 05] Default: 0
06 [DL From Net 06] Default: 0
07 [DL From Net 07] Default: 0
08 [DL From Net 08] Default: 0
09 [DL From Net 09] Default: 0
10 [DL From Net 10] Default: 0
11 [DL From Net 11] Default: 0
12 [DL From Net 12] Default: 0
13 [DL From Net 13] Default: 0
14 [DL From Net 14] Default: 0
15 [DL From Net 15] Default: 0
16 [DL From Net 16] Default: 0
Sets the port number and parameter number to Minimum: 0
which the selected Datalinks should connect. Each Maximum: 159999
selected port/parameter will be written with data Type: Read/Write
received from the network. These are parameters Reset Required: No
written by the controller (outputs from the
controller).
If setting the value manually, the parameter value =
(10000 * port number ) + (destination parameter
number). For example, suppose you want to use
Host Parameter 01 - [DL From Net 01] to write to
Parameter 01 of an optional encoder module
plugged into drive Port 5. The value for Host
Parameter 01 - [DL From Net 01] would be 50001
[(10000 * 5) +1].

72 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Option Module Parameters Appendix B

Parameter
No Name & Description Details
17 [DL To Net 01] Default: 0
18 [DL To Net 02] Default: 0
19 [DL To Net 03] Default: 0
20 [DL To Net 04] Default: 0
21 [DL To Net 05] Default: 0
22 [DL To Net 06] Default: 0
23 [DL To Net 07] Default: 0
24 [DL To Net 08] Default: 0
25 [DL To Net 09] Default: 0
26 [DL To Net 10] Default: 0
27 [DL To Net 11] Default: 0
28 [DL To Net 12] Default: 0
29 [DL To Net 13] Default: 0
30 [DL To Net 14] Default: 0
31 [DL To Net 15] Default: 0
32 [DL To Net 16] Default: 0
Sets the port number and parameter number to Minimum: 0
which the selected Datalinks should connect. Each Maximum: 159999
selected port/parameter will be read and their Type: Read/Write
values transmitted over the network to the Reset Required: No
controller. These are parameters read by the
controller (inputs to the controller).
If setting the value manually, the parameter value =
(10000 * port number ) + (origination parameter
number). For example, suppose you want to use
Host Parameter 17 - [DL To Net 01] to read
Parameter 01 of an optional I/O module plugged
into drive Port 4. The value for Host Parameter 17
- [DL To Net 01] would be 40001 [(10000 * 4) + 1].
33 [Comm Flt Action] Default: 0 = Fault
Sets the action that the Option Module and drive Values: 0 = Fault
will take if the Option Module detects that I/O 1 = Stop
communications have been disrupted. This setting 2 = Zero Data
is effective only if I/O that controls the drive is 3 = Hold Last
transmitted through the Option Module. When 4 = Send Flt Cfg
communication is re-established, the drive will Type: Read/Write
automatically receive commands over the network Reset Required: No
again.

ATTENTION: Risk of injury or equipment damage exists. Host Parameter


33 - [Comm Flt Action] lets you determine the action of the Option
Module and connected drive if I/O communications are disrupted. By
default, this parameter faults the drive. You may configure this parameter
so that the drive continues to run, however, precautions should be taken to
ensure that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a disconnected
cable).

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 73


Appendix B Option Module Parameters

Parameter
No Name & Description Details
34 [Idle Flt Action] Default: 0 = Fault
Sets the action that the Option Module and drive Values: 0 = Fault
will take if the Option Module detects that the 1 = Stop
controller is in program mode or faulted. This 2 = Zero Data
setting is effective only if I/O that controls the drive 3 = Hold Last
is transmitted through the Option Module. When 4 = Send Flt Cfg
the controller is put back in Run mode, the drive Type: Read/Write
will automatically receive commands over the Reset Required: No
network again.

ATTENTION: Risk of injury or equipment damage exists. Host Parameter


34 - [Idle Flt Action] lets you determine the action of the Option Module
and connected drive when the controller is idle. By default, this parameter
faults the drive. You may configure this parameter so that the drive
continues to run, however, precautions should be taken to ensure that the
setting of this parameter does not create a risk of injury or equipment
damage. When commissioning the drive, verify that your system responds
correctly to various situations (for example, a controller in idle state).

35 [Peer Flt Action] Reserved


This parameter is functional. However, since the
Option Module does not support Peer I/O, any
entered value is not used.
36 [Msg Flt Action] Reserved
The Option Module does not support this
functionality. Any entered value is not used.
37 [Flt Cfg Logic] Default: 0000 0000 0000 0000
Sets the Logic Command data that is sent to the 0000 0000 0000 0000
drive if any of the following is true:
Minimum: 0000 0000 0000 0000
• Host Parameter 33 - [Comm Flt Action] is set 0000 0000 0000 0000
to “4” (Send Flt Cfg) and I/O communications are Maximum: 1111 1111 1111 1111
disrupted.
1111 1111 1111 1111
• Host Parameter 34 - [Idle Flt Action] is set to Type: Read/Write
“4” (Send Flt Cfg) and the controller is idle. Reset Required: No
Important: The bit definitions in the Logic
Command word for PowerFlex 750-Series drives
are shown in Appendix C.
38 [Flt Cfg Ref] Default: 0
Sets the Reference data that is sent to the drive if Minimum: -3.40282 x 1038
any of the following is true: Maximum: 3.40282 x 1038
Type: Read/Write
• Host Parameter 33 - [Comm Flt Action] is set Reset Required: No
to “4” (Send Flt Cfg) and I/O communications are
disrupted.
• Host Parameter 34 - [Idle Flt Action] is set to
“4” (Send Flt Cfg) and the controller is idle.

74 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Option Module Parameters Appendix B

Parameter
No Name & Description Details
39 [Flt Cfg DL 01] Default: 0
40 [Flt Cfg DL 02] Default: 0
41 [Flt Cfg DL 03] Default: 0
42 [Flt Cfg DL 04] Default: 0
43 [Flt Cfg DL 05] Default: 0
44 [Flt Cfg DL 06] Default: 0
45 [Flt Cfg DL 07] Default: 0
46 [Flt Cfg DL 08] Default: 0
47 [Flt Cfg DL 09] Default: 0
48 [Flt Cfg DL 10] Default: 0
49 [Flt Cfg DL 11] Default: 0
50 [Flt Cfg DL 12] Default: 0
51 [Flt Cfg DL 13] Default: 0
52 [Flt Cfg DL 14] Default: 0
53 [Flt Cfg DL 15] Default: 0
54 [Flt Cfg DL 16] Default: 0
Sets the data that is sent to the Datalink in the Minimum: 0
drive if any of the following is true: Maximum: 4294967295
Type: Read/Write
• Host Parameter 33 - [Comm Flt Action] is set Reset Required: No
to “4” (Send Flt Cfg) and I/O communications are
disrupted.
• Host Parameter 34 - [Idle Flt Action] is set to
“4” (Send Flt Cfg) and the controller is idle.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 75


Appendix B Option Module Parameters

Notes:

76 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Appendix C

Logic Command/Status Words: PowerFlex


750-Series Drives

Appendix C presents the definitions of the Logic Command and Logic Status
words that are used for PowerFlex 750-Series drives.

Logic Command Word


Logic Bits
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description
x Normal Stop 0 = Not Normal Stop
1 = Normal Stop
x Start (1) 0 = Not Start
1 = Start
x Jog 1 (2) 0 = Not Jog 1 (Par. 556)
1 = Jog 1
x Clear Fault (3) 0 = Not Clear Fault
1 = Clear Fault
x x Unipolar Direction 00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Direction Control
x Manual 0 = Not Manual
1 = Manual
x Reserved
x x Accel Time 00 = No Command
01 = Use Accel Time 1 (Par. 535)
10 = Use Accel Time 2 (Par. 536)
11 = Use Present Time
x x Decel Time 00 = No Command
01 = Use Decel Time 1 (Par. 537)
10 = Use Decel Time 2 (Par. 538)
11 = Use Present Time
x Ref Select 1 000 = No Command
x Ref Select 2 001 = Ref A Select (Par. 545)
x Ref Select 3 010 = Ref B Select (Par. 550)
011 = Preset 3 (Par. 573)
100 = Preset 4 (Par. 574)
101 = Preset 5 (Par. 575)
110 = Preset 6 (Par. 576)
111 = Preset 7 (Par. 577)
x Reserved
x Coast Stop 0 = Not Coast to Stop
1 = Coast to Stop
x Current Limit Stop 0 = Not Current Limit Stop
1 = Current Limit Stop
x Run (4) 0 = Not Run
1 = Run
x Jog 2 (2) 0 = Not Jog 2 (Par. 557)
1 = Jog 2
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
x Reserved
(1) A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Start condition will start the drive.
(2) A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Jog 1/Jog 2 condition will jog the drive. A transition to a “0” will stop the drive.
(3) To perform this command, the value must switch from “0” to “1.”
(4) A Not Stop condition (logic bit 0 = 0) must first be present before a 1 = Run condition will run the drive. A transition to a “0” will stop the drive.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 77


Appendix C Logic Command/Status Words: PowerFlex 750-Series Drives

Logic Status Word


Logic Bits
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Command Description
x Run Ready 0 = Not Ready to Run
1 = Ready to Run
x Active 0 = Not Active
1 = Active
x Command Direction 0 = Reverse
1 = Forward
x Actual Direction 0 = Reverse
1 = Forward
x Accelerating 0 = Not Accelerating
1 = Accelerating
x Decelerating 0 = Not Decelerating
1 = Decelerating
x Alarm 0 = No Alarm (Par. 959 & 960)
1 = Alarm
x Fault 0 = No Fault (Par. 952 & 953)
1 = Fault
x At Setpt Spd 0 = Not at Setpoint Speed
1 = At Setpoint Speed
x Manual 0 = Manual Mode Not Active
1 = Manual Mode Active
x Spd Ref ID 0 00000 = Reserved
x Spd Ref ID 1 00001 = Auto Ref A (Par. 545)
x Spd Ref ID 2 00010 = Auto Ref B (Par. 550)
00011 = Auto Preset Speed 3 (Par. 573)
x Spd Ref ID 3 00100 = Auto Preset Speed 4 (Par. 574)
x Spd Ref ID 4 00101 = Auto Preset Speed 5 (Par. 575)
00110 = Auto Preset Speed 6 (Par. 576)
00111 = Auto Preset Speed 7 (Par. 577)
01000 = Reserved
01001 = Reserved
01010 = Reserved
01011 = Reserved
01100 = Reserved
01101 = Reserved
01110 = Reserved
01111 = Reserved
10000 = Man Port 0
10001 = Man Port 1
10010 = Man Port 2
10011 = Man Port 3
10100 = Man Port 4
10101 = Man Port 5
10110 = Man Port 6
10111 = Reserved
11000 = Reserved
11001 = Reserved
11010 = Reserved
11011 = Reserved
11100 = Reserved
11101 = Man Port 13 (Emb. ENET)
11110 = Man Port 14 (Drive Logix)
11111 = Alternate Man Ref Sel
x Reserved
x Running 0 = Not Running
1 = Running
x Jogging 0 = Not Jogging (Par. 556 & 557)
1 = Jogging
x Stopping 0 = Not Stopping
1 = Stopping
x DC Brake 0 = Not DC Brake
1 = DC Brake
x DB Active 0 = Not Dynamic Brake Active
1 = Dynamic Brake Active
x Speed Mode 0 = Not Speed Mode (Par. 309)
1 = Speed Mode
x Position Mode 0 = Not Position Mode (Par. 309)
1 = Position Mode
x Torque Mode 0 = Not Torque Mode (Par. 309)
1 = Torque Mode
x At Zero Speed 0 = Not at Zero Speed
1 =At Zero Speed
x At Home 0 = Not at Home
1 = At Home
x At Limit 0 = Not at Limit
1 = At Limit
x Current Limit 0 = Not at Current Limit
1 = At Current Limit
x Bus Freq Reg 0 = Not Bus Freq Reg
1 = Bus Freq Reg
x Enable On 0 = Not Enable On
1 = Enable On
x Motor Overload 0 = Not Motor Overload
1 = Motor Overload
x Regen 0 = Not Regen
1= Regen

78 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Glossary

Acyclic Messaging Profibus DPV1 acyclic messages are used to transfer data that does not require
continuous updates. Typically the read and write services used for acyclic
messaging are used to configure, monitor, and diagnose devices over the Profibus
network.

ControlFLASH An Allen-Bradley software tool that lets users electronically update firmware on
printed circuit boards.

Controller A controller, also called programmable logic controller, is a solid-state control


system that has a user-programmable memory for storage of instructions to
implement specific functions such as I/O control, logic, timing, counting, report
generation, communication, arithmetic, and data file manipulation. A controller
consists of a central processor, input/output interface, and memory. See also
Master.

Data Rate The data rate is the speed at which data is transferred on the Profibus network.
The available data rates depend on the type of cable and total cable length used
on the network:

Data Rate Maximum Cable Length


9.6 K 1000m
19.2 K 1000m
45.45 K 1000m
93.75 K 1000m
187.5 K 1000m
500 K 400m
1.5 M 200m
3M 100m
6M 100m
12 M 100m

Datalinks A Datalink is a type of pointer used by PowerFlex 750-Series drives to transfer


data to and from the controller. Datalinks allow specified parameter value(s) to
be accessed or changed. When active, each 32-bit Datalink in a PowerFlex
750-Series drive consumes 4 bytes in the input image table and/or 4 bytes in the
output image table of the controller.

DriveExplorer Software A tool for monitoring and configuring Allen-Bradley products and network
communication Option Modules. It can be run on computers running various
Microsoft Windows operating systems. DriveExplorer (version 6.xx or later) can
be used to configure this Option Module and PowerFlex drive. Information
about DriveExplorer software and a free lite version can be accessed at
http://www.ab.com/drives/driveexplorer.

DriveTools SP Software A software suite designed for running on various Microsoft Windows operating
systems. This software suite provides a family of tools, including DriveExecutive,
that you can use to program, monitor, control, troubleshoot, and maintain
Allen-Bradley products. DriveTools SP can be used with PowerFlex drives.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 79


Glossary

Information about DriveTools SP can be accessed at


http://www.ab.com/drives/drivetools.

Fault Action A fault action determines how the Option Module and connected drive act when
a communications fault (for example, a cable is disconnected) occurs or when the
controller is switched out of run mode. The former uses a communications fault
action, and the latter uses an idle fault action.

Fault Configuration When communications are disrupted (for example, a cable is disconnected), the
Option Module and PowerFlex drive can respond with a user-defined fault
configuration. The user sets the data that is sent to the drive using specific fault
configuration parameters in the Option Module. When a fault action parameter
is set to use the fault configuration data and a fault occurs, the data from these
parameters is sent as the Logic Command, Reference, and/or Datalink(s).

Flash Update The process of updating firmware in a device. The Option Module can be flash
updated using various Allen-Bradley software tools. See Flash Updating the
Option Module on page 31.

GSD File A GSD (Generic Station Description) File is a device database text file used by
the network configuration tool to identify a Profibus module and its capabilities.
The file is normally registered in the Profibus configuration tool for a device, and
is supplied with the device via removable media or on the internet as a download.

HIM (Human Interface Module) A device that can be used to configure and control a drive. The PowerFlex
20-HIM-A6 or 20-HIM-C6S HIM can be used to configure PowerFlex
750-Series drives and their connected peripherals.

Hold Last When communication is disrupted (for example, a cable is disconnected), the
Option Module and PowerFlex drive can respond by holding last. Hold last
results in the drive receiving the last data received via the network connection
before the disruption. If the drive was running and using the Reference from the
Option Module, it will continue to run at the same Reference.

Idle Action An idle action determines how the Option Module and connected drive act
when the controller is switched out of run mode.

I/O Data I/O data, sometimes called "implicit messages" or "input/output," is time-critical
data such as a Logic Command and Reference. The terms "Input" (To Net) and
"Output" (From Net) are defined from the controller's point of view. Output is
produced by the controller and consumed by the Option Module. Input is
produced by the Option Module and consumed by the controller.

Logic Command/Logic Status The Logic Command is used to control the PowerFlex 750-Series drive (for
example, start, stop, direction). It consists of one 32-bit word of output to the
Option Module from the network. The definitions of the bits in this word are
shown in Appendix C.

The Logic Status is used to monitor the PowerFlex 750-Series drive (for example,
operating state, motor direction). It consists of one 32-bit word of input from the

80 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Glossary

Option Module to the network. The definitions of the bits in this word are
shown in Appendix C.

Master-Slave Hierarchy An Option Module configured for a master-slave hierarchy exchanges data with
the master device. Usually, a network has one master which is the master device,
and all other devices (for example, drives with installed Profibus DPV1 Option
Modules) are slave devices.

On a network with multiple masters (called a multimaster hierarchy), each slave


device must have one specified master.

Master A master is a separate module (of a multi-module controller) or a built-in


component (of a single-module controller) that provides communication with
option modules connected to a network. See also Controller.

MVI56-PDPMV1 The MVI56-PDPMV1, Profibus DP-V1 Master Communication Module is a


Profibus communication interface for ControlLogix platform PLC’s. It is
developed under license from Rockwell Automation, and incorporates
proprietary backplane technology that enables data exchange with ControlLogix
processors. More information for the MVI56-PDPMV1ControlLogix module
can be found at http://www.prosoft-technology.com/content/view/full/8109.

Node Address A node address is a unique address identifier for a device assigned to a Profibus
network. A PROFIBUS network can have as many as 126 devices connected on
it , where each device on the network must have a unique node address between 0
and 126.

NVS (Non-Volatile Storage) NVS is the permanent memory of a device. Devices such as the Option Module
and drive store parameters and other information in NVS so that they are not lost
when the device loses power. NVS is sometimes called "EEPROM."

Option Module Devices such as drives, controllers, and computers usually require a network
communication Option Module to provide a communication interface between
them and a network such as Profibus. An Option Module reads data on the
network and transmits it to the connected device. It also reads data in the device
and transmits it to the network.

The 20-750-PBUS Profibus DPV1 Option Module connects PowerFlex


750-Series drives to a Profibus DPV0/DPV1 network. Option Modules are
sometimes also called "adapters," "cards," "embedded communication options," and
"peripherals." On PowerFlex 750-Series drives, Option Modules can also be I/O,
encoders, safety, etc.

Ping A message that is sent by a DPI product to its peripheral devices. Pings are used to
gather data about the product, including whether it can receive messages and if
they can log in for control.

PowerFlex 750-Series (Architecture Allen-Bradley PowerFlex 750-Series drives are part of the PowerFlex 7-Class
Class) Drives family of drives.

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 81


Glossary

Profibus Network A Profibus network uses RS485 to connect devices (for example, controllers,
drives, motor starters and other equipment in automation systems). A Profibus
network can support a maximum of 126 devices. Each device is assigned a unique
node address and transmits data on the network at the same data rate. A cable is
used to connect devices on the network. It contains the bus signal. Devices can be
connected to the network in a daisy chain connection.

ProSoft Configuration Builder ProSoft Configuration Builder (PCB) is used to configure MVI56-PDPMV1
(PCB) (Profibus DP-V1 Master Communication Module). The newest version of
ProSoft Configuration Builder is available from
http://www.prosoft-technology.com/content/view/full/10018.

Reference/Feedback The Reference is used to send a setpoint (for example, speed, frequency, torque)
to the drive. It consists of one 32-bit word of output to the Option Module from
the network.

Feedback is used to monitor the speed of the drive. It consists of one 32-bit word
of input from the Option Module to the network.

RSLogix 5000 RSLogix software is a tool for configuring and monitoring controllers to
communicate with connected devices. It is a 32-bit application that runs on
various Windows operating systems. Information about RSLogix software can be
found at http://www.software.rockwell.com/rslogix.

SI (Serial Interface) A next generation communication interface used by various Allen-Bradley drives,
such as PowerFlex 750-Series drives.

Status Indicators Status indicators are LEDs that are used to report the status of the Option
Module, network, and drive. The indicators are on the Option Module and can
be viewed when the drive is powered and its cover is removed.

Stop Action When communications are disrupted (for example, a cable is disconnected), the
Option Module and drive can respond with a stop action. A stop action results in
the drive receiving zero as values for Logic Command, Reference, and Datalink
data. If the drive was running and using the Reference from the Option Module,
it will stay running but at zero Reference.

UDDT (User-Defined Data Type) A structure data type that you define during the development of an application
(for example, to convert 32-bit REAL parameter data for written and read values
to correctly display them in human readable format).

Zero Data When communications are disrupted (for example, a cable is disconnected), the
Option Module and drive can respond with zero data. Zero data results in the
drive receiving zero as values for Logic Command, Reference, and Datalink data.
If the drive was running and using the Reference from the Option Module, it will
stay running but at zero Reference.

82 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Index

A DriveExecutive software
definition/web site 79
acyclic messaging
Option Module configuration tool 23
about 53
DriveExplorer software
definition 79
definition/web site 79
applying power to the Option Module 20
free lite version 79
attentions 12
Option Module configuration tool 23
drives, see PowerFlex 750-Series
B (Architecture Class) drives
baud rate, see data rate DriveTools SP software 79
bit definitions of Logic Command/Status
word for PowerFlex 750-Series E
drives 78
EEPROM, see Non-Volatile Storage (NVS)
equipment required 11
C events
cable, Profibus 19 clearing/viewing 65
Comm Flt Action Host parameter 73 list of 65
communications card, see Option Module
compatible products
F
description 11
documentation for 7 fault action
components of the Option Module 9 configuring the Option Module for 27
configuration tools 23 definition 80
connecting Option Module fault configuration
to the drive 18 configuring the Option Module for 28
to the network 18 definition 80
ControlFLASH 79 faults, see events
controller 79 features 10
flash update
definition 80
D guidelines 31
data rate 79 Flt Cfg DL 01-16 Host parameters 75
Datalinks (Host parameters DL From Net Flt Cfg Logic Host parameter 74
01-16 and DL To Net 01-16) Flt Cfg Ref Host parameter 74
definition 79
in I/O image 48
using 49
G
Device parameters list 70 GSD (Generic Station Description) files -
diagnostic items 64 definition/web site 80
DL From Net 01-16 Host parameters 72
DL To Net 01-16 Host parameters] 73 H
DLs From Net Act Device parameter 70 HIM (Human Interface Module)
DLs To Net Act Device parameter 70 accessing parameters with 24
documentation for compatible products 7 definition 80
DPV1 Map Mode Device parameter 71

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 83


Index

hold last Net Addr Cfg Device parameter 70


configuring the Option Module for 27 Net Addr Src Device parameter 70
definition 80 Net Data Format Device parameter 71
Host parameters list 72-75 network cable 19
network termination 20
I network wiring diagram 19
node address
I/O definition 81
about 47
setting with parameter 24
communication 51
setting with switches 16
definition 80
Non-Volatile Storage (NVS)
understanding the I/O image 48
definition 81
idle action 80
in drive 49
Idle Flt Action Host parameter 74
in Option Module 23
installation
applying power to the Option Module 20
connecting to the network 18 O
preparing for 15 Option Module
applying power 20
L compatible products 11
components 9
LEDs, see status indicators configuration tools 23
Logic Command/Status
connecting
bit definitions for PowerFlex 750-Series
to the drive 18
drives 78
to the network 18
definition 80
definition 81
in I/O image 48
Device parameters list 70-71
using 48
features 10
flash updating 31
M Host parameters list 72-75
manual installation 15-??
conventions 8 node address
related documentation 7 setting with parameter 24
web site 7 setting with switches 16
Master-Slave hierarchy resetting 28
configuring Option Module for 24 restoring parameters to factory default
definition 81 values 29
messages, see acyclic messaging or I/O specifications 67
MOD status indicator viewing its status using parameters 31
locating 14
troubleshooting with 63 P
Msg Flt Action Host parameter 74
parameters
MVI56-PDPMV1 81
accessing 23
Device parameters list 70-71
N Host parameters list 72-75
NET A status indicator numbering scheme 69
locating 14 restoring to factory default values 29
troubleshooting with 63 Peer Flt Action Host parameter 74
Net Addr Act Device parameter 70 ping 81

84 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Index

Port Number Device parameter 70 specifications


PORT status indicator Option Module 67
locating 14 Profibus 82
troubleshooting with 62 status indicators
PowerFlex 20-HIM-A6/-C6S HIM 24 definition 82
PowerFlex 750-Series (Architecture Class) locating 14
drives MOD 14, 63
compatible with Option Module 11 NET A 14, 63
definition 81 normal operation 20
HIM 24 PORT 14, 62
preparing for an installation 15 troubleshooting with 62-63
processor, see controller understanding 61
Profibus stop action 82
cable 19
connector for Option Module 9
data rate 67
T
network definition 82 technical support 8
specification 82 tools required 11
PROFIBUS Alarms Device parameter 71 troubleshooting 61-66
PROFIBUS Mode Device parameter 71
programmable logic controller, see U
controller
UDDT (User-Defined Data Type) 82
ProSoft Configuration Builder 82
update, see flash update

Q
W
quick start 13
web site for
DriveExecutive software 79
R DriveExplorer software 79
Reference/Feedback DriveTools SP software 79
definition 82 GSD files 80
in I/O image 48 MVI56-PDPMV1 81
using 49 ProSoft Configuration Builder 82
regulatory compliance 68 related documentation 7
related documentation 7 RSLogix 5000 82
Reset Module Device parameter 70 wiring, see cable, Profibus
resetting the Option Module 28
RSLogix 5000 82 Z
zero data
S configuring the Option Module for 27
safety precautions 12 definition 82
Serial Interface (SI) 82

Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011 85


Index

Notes:

86 Rockwell Automation Publication 750COM-UM004A-EN-P - August 2011


Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use
of these tools.

For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/.

For U.S. Allen-Bradley Drives Technical Support — Tel: (1) 262.512.8176, Fax: (1) 262.512.2222,
Email: [email protected], Online: www.ab.com/support/abdrives

Installation Assistance

If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.

United States or Canada 1.440.646.3434


Outside United States or Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
Canada your local Rockwell Automation representative.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback

Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

www.rockwellautomation.com

Power, Control and Information Solutions Headquarters


Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

Publication 750COM-UM004A-EN-P - August, 2011


Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like