CE8501 RCET Notes - by WWW - Easyengineering.net 2
CE8501 RCET Notes - by WWW - Easyengineering.net 2
net
ww
w.E
asy
E ngi
nee
rin
g.n
et
ww
w.E
UNIT 1a syE
ngi
nee
rin
g.n
et
ww
serviceability. It must also be economical and aesthetic.
w.E
The design of a structure must satisfy three basic requirements:
asy
1) Stability to prevent overturning, sliding or buckling of the structure, or parts of it, under the
action of loads,
En
2) Strength to resist safely the stresses induced by the loads in the various structural members;
and
gin
3) Serviceability to ensure satisfactory performance under service load conditions - which implies
eer
providing adequate stiffness and reinforcements to contain deflections, crack-widths and
ing
vibrations within acceptable limits, and also providing impermeability and durability (including
corrosion-resistance), etc.
.ne
There are two other considerations that a sensible designer ought to bear in mind, viz., economy
t
and aesthetics. One can always design a massive structure, which has more-than-adequate
stability, strength and serviceability, but the ensuing cost of the structure may be exorbitant, and
the end product, far from aesthetic. In the words of Felix Candela, the designer of a remarkably
wide range of reinforced concrete shell structures, It is indeed a challenge, and a responsibility, for
the structural designer to design a structure that is not only appropriate for the architecture, but
also strikes the right balance between safety and economy.
ww
done. This involves determination of the following.
Position and orientation of columns
w.E
Positioning of beams
Spanning of slabs
Layouts of stairs
asy
En
Selecting proper type of footing.
gin
1.1 Positioning and orientation of columns Following are some of the building principles, which
help in deciding the columns positions.
eer
1. Columns should preferably be located at (or) near the corners of a building, and at the
intersection of beams/walls.
ing
2. Select the position of columns to reduce bending moments in beams.
3. Avoid larger spans of beams. .ne
4. Avoid larger centre-to-centre distance between columns.
5. Columns on property line.
t
Orientation of columns
1. Avoid projection of columns: The projection of columns outside the wall in the room should
be avoided as they not only give bad appearance but also obstruct the use of floor space,
creating problems in placing furniture flush with the wall. The width of the column is required
to be kept not less than 200mm to prevent the column from being slender. The spacing of the
column should be considerably reduced so that the load on column on each floor is less and the
necessity of large sections for columns does not arise.
ww
1.3 Spanning of Slabs
w.E
This is decided by supporting arrangements. When the supports are only on opposite edges or
only in one direction, then the slab acts as a one way supported slab. When the rectangular slab is
asy
supported along its four edges it acts as a one-way slab when Ly/Lx < 2. The two-way action of slab
En
not only depends on the aspect ratio but also on the ratio of reinforcement on the directions. In one-
way slab, main steel is provided along with short span only and the load is transferred to two opposite
gin
supports. The steel along the long span just acts as the distribution steel and is not designed for
eer
transferring the load but to distribute the load and to resist shrinkage and temperature stresses. A slab
is made to act as a one-way slab spanning across the short span by providing main steel along the
short span and only distribution steel along the long span
ing
.ne
The provision of more steel in one direction increases the stiffness of the slab in that direction.
t
According to elastic theory, the distribution of load being proportional to stiffness in two orthogonal
directions, major load is transferred along the stiffer short span and the slab behaves as one way.
Since, the slab is also supported over the short edge there is a tendency of the load on the slab by the
side of support to get transferred to the nearer support causing tension at top across this short
supporting edge. Since, there does not exist any steel at top across this short edge in a one way slab
interconnecting the slab and the side beam, cracks develop at the top along that edge. The cracks may
run through the depth of the slab due to differential deflection between the slab and the supporting
short edge beam/wall. Therefore, care should be taken to provide minimum steel at top across the
short edge support to avoid this cracking.
A two-way slab is generally economical compare to one-way slab because steel along both
the spans acts as main steel and transfers the load to all its four supports. The two-way action is
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
advantageous essentially for large spans (>3m) and for live loads (>3kN/m2). For short spans and light
loads, steel required for two way slabs does not differ appreciably as compared to steel for two way
slab because of the requirements of minimum steel.
ww
isolated column footings are normally preferred except in case of exists for great depths, pile
foundations can be an appropriate choice. If columns are very closely spaced and bearing capacity of
w.E
the soil is low, raft foundation can be an alternative solution. For a column on the boundary line, a
combined footing or a raft footing may be provided
asy
The following are the assumptions made in the earthquake resistant design of structures:
En
Earthquake causes impulsive ground motions, which are complex and irregular in character,
changing in period and amplitude each lasting for small duration. Therefore resonance of the
gin
type as visualized under steady-state sinusoidal excitations, will not occur as it would need
time to build up such amplitudes.
eer
Earthquake is not likely to occur simultaneously with wind or max. Flood or max. sea waves.
ing
The value of elastic modulus of materials, wherever required, maybe taken as per static
analysis.
.ne
t
ww
complex.
w.E
Different types of loads
The loads in buildings and structures can be classified as vertical loads, horizontal
asy
loads and longitudinal loads. The vertical loads consist of dead load, live load and impact
En
load. The horizontal loads consist of wind load and earthquake load. The longitudinal
gin
loads i.e. tractive and braking forces are considered in special cases of design. The
estimation of various loads acting is to be calculated precisely. Indian standard code IS:
eer
875–1987 and American Standard Code ASCE 7: Minimum Design Loads for Buildings
ing
and Other Structures specifies various design loads for buildings and structures.
Live loads are added to the dead load to give the total loading exerted on the
structure. The calculation of dead loads of each structure is calculated by the volume of
each section and multiplied by the unit material weight.
2. Live load
Live load is a civil engineering term that refers to a load that can change over time.
The weight of the load is variable or shifts locations, such as when people are walking
around in a building. Anything in a building that is not fixed to the structure can result
in a live load since it can be moved around.
Live loads are factored into the calculation of the gravity load of a structure. They
are measured in pounds per square foot. The minimum live-load requirements are
based on the expected maximum load. A live load can be expressed either as a
uniformly distributed load (UDL) or as one acting on a concentrated area (point load).
w.E
The movement of air relative to a structure can apply wind loads, and analysis draws
upon an understanding of meteorology and aerodynamics as well as structures. Wind load
asy
may not be a significant concern for small, massive, low-level buildings, but it gains
En
importance with height, the use of lighter materials and the use of shapes that may affect
the flow of air, typically roof forms.
gin
eer
Where the dead weight of a structure is insufficient to resist wind loads, additional
ing
structure and fixings may be required. Wind load is required to be considered in structural
design especially when the heath of the building exceeds two times the dimensions
transverse to the exposed wind surface. .ne
t
The design wind loads for buildings and other structures shall be determined according to
one of the following procedures:
Method 1 – Simplified procedure for low-rise simple diaphragm buildings
Method 2 – Analytical procedure for regular shaped building and structures
Method 3 – Wind tunnel procedure for geometrically complex buildings and structures
4. Snow load
This load can be imposed by the accumulation of snow and is more of a concern in
geographic regions where snowfalls can be heavy and frequent. Significant quantities of
snow can accumulate, adding a sizable load to a structure. The shape of a roof is a
particularly important factor in the magnitude of the snow load. The code IS 875 (Part-
4):1987 deals with snow loads on roofs of the building. There are many variables involved
in determining snow’s weight:
5. Earthquake load
Earthquake load takes place due to the inertia force produced in the building because of
seismic excitations. Inertia force varies with the mass. The higher mass of the structure
will imply that the earthquake loading will also be high. When the earthquake load exceeds
the moment of resistance offered by the element, then the structure will break or damage.
The magnitude of earthquake loading depends upon the weight or mass of the building,
dynamic properties of the building and difference in stiffness of adjacent floors along with
ww
the intensity and duration of the earthquake. Earthquake load acts over the surface of a
structure placed on the ground or with an adjacent building. Buildings in areas of seismic
w.E
activity need to be carefully analysed and designed to ensure they do not fail if an
earthquake should occur.
asy
Earthquake load depends on the following factors;
Seismic hazard
En
Parameter of the structure
Gravity load. gin
6. Load combination eer
ing
A load combination results when more than one load type acts on the structure.
.ne
Building codes usually specify a variety of load combinations together with load factors
(weightings) for each load type to ensure the safety of the structure under different
maximum expected loading scenarios.
7. Special loads
t
Thermal load – The loads occur when the materials expand or contract with temperature
change and this can exert significant loads on a structure.
Settlement load – When one part of a building settles more than other parts this type of
load occurs.
Flood load – These are caused by flood and water ingress in the foundation which results
in corrosion.
Soil and fluid load – It is caused due to excessive flow of water in the soil which impacts
the soil density.
A code is a set of technical specifications intended to control the design and construction. The
code can be legally adopted to see that sound structure is designed and constructed code specifies
acceptable methods of design and construction to produce safe structures.
National building code have been formulated in different countries to lay down guidelines for
the design and construction of structures. International code council located in USA has published
international building code. National building code (NBC - 2005) published in India describes the
specification and design procedure for buildings.
For designing reinforced concrete following codes of different countries are available
India - IS456 - 2000 - Plain and reinforced concrete code practice.
ww USA - ACI 318-2011 - Building code requirements for Structural concrete (American concrete
institute)
w.E
UK - BS8110 -part1 - structural use of concrete -code of practice for design and construction.
(British standard Institute)
asy
Europe - EN 1992(Euro code 2) - Design of concrete structures
En
Canada - CAN/CSA - A23.3-04 - Design of concrete structures (Reaffirmed in 2010),
gin
Australia - As 3600 -2001 - concrete structures.
Germany - Din 1045 - Design of concrete structures
Russia - SNIP
eer
ing
China - GB 50010 -2002 code for design of concrete structures to help the designers, each
country has produced 'handbook'. In India following hand books called special publication are
available.
.ne
SP - 16-1980- Design Aid for Reinforced concrete to IS456-1978
SP - 23-1982- Hand book on concrete mixes
SP - 24 -1983 - Explanatory hand book on IS456 - 1978
t
SP - 34-1987 - Hand book on concrete reinforcement and detailing.
Various methods used for the design of R.C.C. structures are as follows:
This method of design was the oldest one. It is based on the elastic theory and assumes that
both steel and concrete and elastic and obey Hook’s law. It means that the stress is directly
proportional to strain up to the point of collapse. Based on the elastic theory, and assuming that the
ww
bond between steel and concrete is perfect, permissible stresses of the materials are obtained. The
basis of this method is that the permissible stresses are not exceeded anywhere in the structure when it
is subjected to worst combination of working loads.
w.E
In this method, the ultimate strength of concrete and yield strength or 0.2% proof stress of steel are
asy
divided by factors of safety to obtain permissible stresses. These factors of safety take into account the
uncertainties in manufacturing of these materials. As per IS456, a factor of safety of 3 is to be used for
En
bending compressive stresses in concrete and 1.78 for yield/proof strength of steel.
gin
The main drawbacks of the working stress method of design are as follows :
(i)
eer
It assumes that concrete is elastic which is not true as the concrete behaves in-elastically even
on low level of stresses.
(ii) ing
It uses factors of safety for stresses only and not for loads. Hence, this method does not give
.ne
true margin of safety with respect to loads because we do not know the failure load.
(iii)
t
It does not use any factor of safety with respect to loads. It means, there is no provision for the
uncertainties associated with the estimation of loads.
(iv) It does not account for shrinkage and creep, which are time dependent and plastic in nature.
(vi) It pays no attention to the conditions that arise at the time of collapse.
The working stress method is very simple and reliable but as per IS 456:2000 the working stress
method is to be used only if it is not possible to use limit state method of design. Working stress
method is the basic method and its knowledge is essential for understanding the concepts of design.
In this method, ultimate or collapse load is used as design load. The ultimate loads are obtained by
increasing the working/service loads suitably by some factors. These factors, which are multiplied by
the working loads to obtain ultimate loads, are called as load factors. These load factors give the exact
margins of safety in terms of load. This method used the real stress-strain curve of concrete and steel
and takes into account the plastic behavior of these materials.
Many designers feel that the load factor provides a clear margin of safety and one can easily tell the
load at which the structure fails, which is not clear from the working stress concept of permissible
stresses. This method was given in detail in IS 456-1964,
ww
(ii)
method taken into account the non-linear behavior of the concrete.
This method gives exact margin of safety in terms of load unlike working stress method
w.E which is based on the permissible stresses which do not give any idea about the
failure/collapse load.
(iii) asy
The sections designed by ultimate load method are thinner and require less reinforcement.
En
Hence the method is economical as compared to WSM.
gin
The main limitations of the ultimate load method are following:
(i)
eer
This method gives very thin sections which leads to excessive deformations and cracking,
thus making the structure unserviceable.
(ii) No factors of safety are used for material stresses.
ing
.ne
As the serviceability requirements are not satisfied at all in this method, the code replaced this method
by limit state method which takes into account the strength as well as serviceability requirements.
This limit state corresponds to the serviceability requirements i.e., deformation, cracking etc. It is
categorized into following types:
ww
This method is based upon the probabilities variation in the loads and material properties. Limit state
method takes into account the uncertainties associated with loads and material properties, thus uses
w.E
partial factors of safety to obtain design loads and design stresses.
asy
The limit state method is based on predictions unlike working stress method, which is deterministic in
nature, assumes that the loads, factors of safety and material stresses are known accurately. In the
En
limit state method, the partial safety factors are derived using probability and statistics and are
different for different load combinations, hence giving a more rational and scientific design procedure.
gin
eer
ing
.ne
t
w.E
husk ash, metakoline and ground granulated blast furnace slag may be used to reduce micro
cracks . The aggregate used is primarily for the purpose of providing bulk to the concrete and
asy
constitutes 60 to 80 percent of finished product.
En
Fine aggregates are used to increase the workability and uniformly of concrete mixture.
gin
Water used for mixing and curing shall be clean and free from oil, acids, alkalis, salts, sugar
eer
etc. The diverse requirements of mixability, stability, transportability place ability, mobility,
ing
compatibility of fresh concrete are collectively referred to as workability.
Compressive strength of concrete on 28th day after casting is considered as one of the measure
.ne
of quality. At least 4 specimens of cubes should be tested for acceptance criteria.
Grade of concrete
t
Based on the compressive strength of concrete, they are designated with letter H
followed by an integer number represented characteristic strength of concrete, measured using
150mm size cube. Characteristic strength is defined us the strength of material below which
not more than 5% of test results are expected to full. The concrete grade M10, M15 and M20
are termed as ordinary concrete and those of M25 to M55 are termed as standard concrete and
the concrete of grade 60 and above are termed as high strength concrete. The selection of
minimum grade of concrete is dictated by durability considerations which are based on kind of
environment to which the structure is exposed, though the minimum grade of concrete for
reinforced concrete is specified as M20 under mild exposure conditions, it is advisable to
adopt a higher grade. For moderate, severe, very severe and extreme exposure conditions,
ww
w.E
Reinforcing steel
asy
En
Steel bars are often used in concrete to take case of tensile stresses. Often they are
gin
called as rebars, steel bar induces ductility to composite material i.e. reinforced concrete steel
is stronger than concrete in compression also. Plain mild steel bars or deformed bars are
eer
generally used. Due to poor bond strength, plain bars are not used. High strength deformed
ing
bars generally cold twisted (CTD) are used in reinforced concrete. During beginning of 21st
century, Thermo-mechanical tream (TMT) bars which have ribs on surface are used in
.ne
reinforced concrete. Yield strength of steel bars are denoted as characteristic strength. Yield
t
strength of mild steel is 250MPa, yield strength of CTD &TMT bars available in market has
415 MPa or 500 MPa or 550MPa. TMT bars have better elongation than CTD bars. Stress-
strain curve of CTD bars or TMT bars do not have definite yield point, hence 0.2% proof
stress is used as yield strength. Fig 1.5 shows stress strain curve of different steel grades. Fe
followed by yield strength indicates steel grades. In the drawings of RCC, denotes MS bar and
# denotes CTD or TMT bars.
ww
w.E
asy
En
gin
eer
ing
.ne
t
1. Design a R.C beam to carry a load of 6 kN/m inclusive of its own weight on an effect span of
6m keep the breath to be 2/3 rd of the effective depth .the permissible stressed in the
concrete and steel are not to exceed 5N/mm2 and 140 N/mm2.take m=18
ww
Step 2: Moment on the beam.
2
w.E M = (w.l2)/8
asy
= (6x62)/8
= 27kNm
En
M = Qbd2
d2 = M/Qb
= (27x106)/ (0.84x2/3xd)gin
d = 245mm.
eer
Step 3: Balanced Moment. ing
Mbal = Qbd2
.ne
= 0.84x245x3652
= 27.41kNm. > M. t
It can be designed as singly reinforced section.
2. Design a beam subjected to a bending moment of 40kNm by working stress design. Adopt
width of beam equal to half the effective depth. Assume the permissible stressed in the concrete
and steel are not to exceed 5N/mm2 and 140 N/mm2.take m=18.
ww
Step 2: Moment on the beam.
w.E M = 40kNm
M = Qbd2
d2 = M/Qb asy
En
= (40x106)/ (0.84x1/2xd)
d = 456.2 say 460 mm.
b= 0.5 ,d = 0.5x460 gin
= 230mm
eer
Step 3: Balanced Moment.
Mba = Qbd2 ing
.ne
l
= 0.84x230x4602
= 40.88kNm. > M.
It can be designed as singly reinforced section. t
Step 4: Area of steel.
Xa = 159.42mm
W = (8 x 15.74)/52
t
= 5.03 kN/m
4. A reinforced concrete rectangular section 300 mm wide and 600 mm overall depth is
reinforced with 4 bars of 25 mm diameter at an effective cover of 50 mm on the tension side. The
beam is designed with M 20 grade concrete and Fe 415 grade steel. Determine the allowable
bending moment and the stresses developed in steel and concrete under this moment. Use
working stress method.
= 194.66mm >Xa
= 117.81mm
ww
Step 3: Moment of Resistance For steel:
=
asy
(1963.5x230)(550-117.81/3)
=
En
230.64kNm
For concrete:
𝑥
(b. 2𝑎. 𝜎𝑐𝑏𝑐 )(d- 𝑥𝑎 /3)
gin
M =
eer
=
=
(300x117.81/2x7)(550-117.81/3)
63.17kNm ing
.ne
t
eer
1. Limit state of collapse:
ing
The limit state of collapse of the structure or part of the structure could be
assesses from rupture of one .ne
or more critical sections and from buckling due to
t
elastic or plastic instability or overturning. The resistance to bending, shear, torsion and
axial loads at every section shall not be less than the appropriate value at that section
produced by the probable most unfavorable combination of loads on the structure using
the appropriate partial safety factors.
2. Limit state of serviceability:
The limit state of serviceability relate to the performance or behavior of
structure at working loads. Normally, design is based on the considerations of limit
states of collapse on ultimate loads and on serviceability limit states of deflection and
cracking under service loads. Durability is taken care of by prescribing appropriate
grade of concrete, nominal cover for various exposure condition, cement content etc.
The advantages of limit state method over the other methods are the following
a) In the limit state method of analysis, the principles of both elastic as well as plastic
theories used and hence suitable for concrete structures
b) The structure designed by limit state method is safe and serviceable under design
loads and at the same time it is ensured that the structure does not collapse even
under the worst possible loading conditions
c) The process of stress redistribution, moment redistribution etc., are considered in
ww
the analysis and more realistic factor of safety values are used in the design
d) Hence the design by limit state method is found to be more economical.
w.E
e) The overall sizes of flexural members (depth requirements) arrived by limit state
method are less and hence they provide better appearance to the structures.
asy
Working Stress Method
En Limit State Method
gin
The stress in a component is derived from the The stresses are derived from the design load and
eer
working load and compared with the permissible are compared with the design strength.
stress.
ing
This method can also be referred to as the This method can also be referred to as non-
.ne
deterministic method as a result of the method deterministic because the method is based on a
t
assumes that the actual load, permissible stress probabilistic approach that relies on real data or
The work stress method is based on elastic theory The limit state method is based on the actual
which assumes that concrete and steel are elastic stress-strain curves of steel and concrete, The
and the stress-strain curve for both is linear. stress-strain curve for concrete is non-linear.
Physical capabilities are largely underestimated, The capabilities of the material are not
Safety factors are used in the work stress method. underestimated as much as they are in the
The ultimate load-carrying capacity cannot be Ultimate stresses of the material themselves are
Within the work stress method, the material In the limit state method, stress is allowed to
follows Hooke’s rule because the stress is not exceed the yield limit.
In working stress method, a section which is In LSM, a section normal to the axis of the
plane before bending remains plane after bending. structural element remains on the plane after
ww bending.
In the work stress method, no safety factor is used In the limit state method, the design load is
w.E
for the load. obtained by multiplying the load’s partial safety
En
The working stress method is less economical as The limit state method is more economical
eer
ing
.ne
t
1.9 Analysis and design of singly and doubly reinforced rectangular beams by
Limit state method
The Concrete beam whose only tension zone of cross-section area is covered with steel rod is known
as a singly reinforced beam.
TYPE 1 PROBLEM:
GIVEN DATA: Ast in mm2 or number of bars with diameter, size of beam (b, D), type of concrete
(fck), type of steel (fy), if load to be calculated then span is given. REQUIRED: Ultimate moment or
ww
factored moment or moment or resistance (Mu) or Mu & w.
Note:
w.E
1.
asy
Ultimate moment or factored moment (Mu) = 1.5 x working moment = 1.5 x M
2.
En
Ultimate load or factored load (wu) = 1.5 x working load = 1.5 x w
DESIGN STEPS:
gin
STEP 1: Note down the value for Xu,max/d by referring IS: 456-2000
eer
Fy in N/mm2 Xu,max/d
ing
250
415
0.53
0.48 .ne
500 0.46
t
STEP 2: Determine depth of neutral axis Xu/d Xu/d = (0.87.fy.Ast)/(0.36.fck.b.d)
Where,
Fy = characteristic tensile strength of steel in N/mm2 Ast = area of steel in tension in mm2
d = effective depth in mm
If Xu/d < Xu,max/d, then section is under reinforced. The moment of resistance is calculated by
If Xu/d > Xu,max/d, then section is over reinforced. The moment of resistance is calculated by
w.E
Mu,lim = 0.138.fck.b.d2 for Fe415 steel.
asy
Mu,lim = 0.133.fck.b.d2 for Fe500 steel.
En
If the section is balanced that is Xu/d = Xu,max/d then the limiting moment of resistance (Mu,lim) is
calculated.
gin
STEP 4: Working moment = M = Mu/1.5
eer
ing
The maximum bending moment for simply supported beam carrying UDL = wl2/8 Now equating
maximum bending moment and working moment
d=450mm,
Ast=4-#16,
fck=20 N/mm2,
fy=415 N/mm2
ww
Required: Xu
w.E
Solution:
asy
Step1: As per IS: 456-2000 Xu,max/d = 0.48 for Fe415
En
Step2: Xu/d = (0.87.fy.Ast)/(0.36.fck.b.d)
= 0.39
Section is under-reinforced.
PROBLEM 2.A singly reinforced concrete beam 250mm width is reinforced with 4 bars of 25mm
diameter at an effective depth 400mm. If M20 grade concrete and Fe415 bars are used. Compute
moment of resistance of the section.
Given data: b=250mm, d=400mm, Ast=4-#25, fck=20 N/mm2, fy=415 N/mm2 Required: Mu
Solution:
asy
Xu/d = (0.87x415x1963.75) / (0.36x20x250x400)
= 0.98 En
gin
Step3: By comparing Xu/d > Xu,max/d
eer
Section is Over-reinforced.
ing
Step4:
.ne
Mu,lim=0.138.fck.bd2
=0.138x20x250x400 2
t
= 110400000 N-mm = 110.4 kN-m
d=500mm,
fck=20 N/mm2,
fy=415 N/mm2
Required: Mu,lim
ww
Solution:
w.E
Mu,lim=0.138.fck.bd2
=0.138x20x250x5002 asy
= 172500000 N-mm En
gin
= 172.5 kN-m
eer
ing
PROBLEM 4.A rectangular section of 230x500mm is used as a simply supported beam for effective
span of 6m. The beam consists of tensile reinforcement of 4000 mm2 and center of reinforcement is
.ne
placed at 35mm from the bottom edge. What maximum total UDL can be allowed on the beam? Given
M20 concrete and Fe415 steel.
Given data:
t
b=230mm,
D=500mm,
Ast=4000mm2, d’=35mm,
fck=20 N/mm2,
Required: w
Solution:
Step2:
ww d=D-d’=500-35=465mm
w.E
Xu/d = (0.87x415x4000) / (0.36x20x230x465)
= 1.875
asy
Step3: by comparing Xu/d > Xu,max/d En
Section is Over-reinforced. gin
Step4: Mu,lim=0.138.fck.bd2 =0.138x20x230x4652 eer
ing
= 137259630 N-mm
.ne
Step5: M=Mu/1.5
= 137.26 kN-m
t
=137.26/1.5=91.506kN-m
M=wl2/8,
w=8M/l2
=8.91.506/62=20.33kN-m
Definition: the RCC beam section in which steel reinforcement is provided to resist both compression
and tension is called doubly reinforced beam.
1. When there are architectural restrictions on the depth of otherwise singly reinforced section.
2. Restriction in the depth at the location of beam at plinth level, along with the provision of
ventilator between the ground level and the bottom of plinth beam.
3. In a continuous beam floor system, where the beam acts as a T-beam in the midspan and acts
ww
as a rectangular beam at the supports where the B.M may be much greater than at the mid span.
4.
w.E
Where it is required to increase the stiffness of the beam.
5.
asy
It is found that the compression steel increases the rotation capacity and ductility
.ne
Solution:
t
Step1: calculate Asc= no of bars x π (ϕc)2/4 mm2, Ast= no of bars x π (ϕt)2/4 mm2 Where, ϕc=
diameter of compression steel, ϕt= diameter of tension steel
Step3: stress in compression (fsc): from the table F of SP16 by linear interpolation Calculate d’/d
ww
Mu= 0.36. fck.b.xu.( d-0.42.xu) + fsc.Asc(d-d’) If, Xu > Xu,max section is over reinforced.
w.E
Put Xu = Xu,max value and calculate moment of resistance by the following expression, Mu= 0.36.
asy
fck.b.xu,max.( d-0.42.xu,max) + fsc.Asc(d-d’)
En
To calculate safe udl of live load: follow same steps as in singly reinforced beams.
gin
Poblem 1 A doubly reinforced beam section is 250mm wide and 450mm deep to center of the
eer
tensile reinforcement. It is reinforced with 2 bars of 16mm diameter as compressive
reinforcement at an effective cover 50mm and 4 bars of 25mm diameter as tensile steel. Using
ing
M15 concrete and Fe250 steel. Calculate the ultimate moment of resistance of the beam.
Given data:
.ne
b=250mm, t
d=450mm,
fck=15 N/mm2,
fy=250 N/mm2,
d’=50mm,
Required: Mu Solution:
=2 πx(16)2/4=402.12mm2 Ast
=0.53x450=238.5mm
fsc=0.87.fy=0.87x250=217.5 N/mm2
ww
step4: Ast2=(Asc. fsc)/(0.87. fy)
w.E =(402.12x217.5)/(0.87x250)=402.12mm2
Mu=148.13 kN-m.
Problem 2 A doubly reinforced beam section is 250mm wide and 500mm deep to the
center of the tensile reinforcement. It is reinforced with 2 bars of 18mm diameter as
compression reinforcement at an effective cover of 40mm and 4 bars of 25mm diameter
as tensile reinforcement using M15 concrete and Fe415 steel. Calculate MR of the
section.
Given data:
b=250mm,
d=500mm,
fck=15 N/mm2,
fy=415 N/mm2,
ww
d’=40mm,
Asc= 2- #18,
w.E
Ast=4-#25
Required: Mu
Solution: asy
Step1: calculating,
En
Ast =no’s.xπ.(ϕt)2/4
= 4xπx(25)2/4= 1963.49mm2 Asc
gin
= no of bars x π (ϕc)2/4=2x πx(18)2/4=508.93mm2eer
Step2:
ing
Xu,max=0.48d for Fe415
.ne
=0.48x500
=240mm
Step3: stress in compression (fsc) d'/d
t
=40/500
=0.08
By referring table –F of sp16 d'/d fsc
0.05 355 Y1
0.08 ? Y
0.1 353 Y2
Y = Y1 + ((Y2-Y1)/(X2-X1))*(X-X1)
= 355+((353-355)/(0.1-0.05))*(0.08- 0.05)=353.8 N/mm2
ww = (0.87x415x1963.49-353.8x508.93)/ (0.36x15x250)
=391.74mm
w.EXu> Xu,max section is over reinforced.
Step7:
asy
Mu=0.138.fck.b.d2+fsc.Asc. (d-d’)
= 0.138x15x250x5002+353.8x508.93x (500- 40)
En
=212.2x106 N-mm
Mu=212.2 kN-m.
gin
eer
ing
.ne
t
ww
w.E
UNIT 2a syE
ngi
nee
rin
g.n
et
UNIT -II
DESIGN OF BEAMS
ww
w.E
asy
En
gin
When a concrete slab is cast monolithically with and, connected to rectangular beams, a
eer
portion of the slab above the beam behaves structurally as a part of the beam in compression.
ing
The slab portions are called the flange and beam the web. If the flange projections are on either
side of the rectangular web or rib, the resulting cross section resembles the T shape and hence is
.ne
called a T-beam section. On the other hand, if the flange projects on one side, the resulting
cross- section resembles an inverted L and hence is termed as L-beam.
Advantages of T-beam are t
1.Beam and slab are casted monolithically hence; casting can be done at a time.
2.Slab and beam combined together to carry more bending moment.
For same section, T-beams have more M.R (flexural strength) than that of rectangular beam.
It is that portion of slab which acts integrally with the beam and extends on either side of
the beam forming the compression zone. The effective width of flange depends upon the span of
the beam, thickness of slab and breadth of the web. It also depends upon the type of loads and
support conditions.
asy
First segment will be like a rectangular section and steel area Ast1.
En
Second segment will be like a beam section having concrete section of area [(bf-
bw)Df] and steel area of Ast2.
gin
eer
Our consideration in design and analysis for depth of neutral axis xu > Df will
be ascertain the compressive force taken up by concrete in second segment
and its line of action.
ing
.ne
If xu ≤ Df, the beam can be thought of as a rectangular section of width bf.
The stress distribution for various values of xu
Steps:1 Calculate depth of neutral axis assuming neutral axis lies within the flange
ww
Calculate neutral axis assuming neutral axis (NA) lies within flange. If xu>Df,assumption is
wrong. NA lies below the flange.
w.E
Recalculate the value of xu by using following relation C1+C2=TWhere, C1 =
asy
0.36.fck.xu.bw
C2 = 0.45.fck.(bf – bw).Df T = 0.87. fy. Ast
En
0.36.fck.xu.bw + 0.45.fck.(bf – bw).Df = 0.87. fy. Ast (assume (Df / xu) <0.43) and find xu
2.Df / xu > 0.43 use equation G.2.2.1 page No.97, IS:456-2000 for Mu calculation
ww
w.E
asy
En
gin
eer
ing
.ne
t
UNIT -II
DESIGN OF BEAMS
ww Since the beam is simply supported, the distance between the points of zero
moments l0 = l = 6m
w.E Clear span of the slab to the left or right of the beam
= C/C distance of adjacent panels — bw
=3000 — 350 = 2650mm
asy
i)
En
Effective width of the flange is the least of the following:
bf = l0 /6 + bw +6Df
gin
= 6000 + 350 + 6 x100= l950mm
ii)
t
120 mm. It is reinforced with 6- 20mmϕ bars on tension side with a cover of 30 mm. If M-
20 concrete and Fe415 steel are used. Calculate MR of beam. Take bw= 300mm.
Solution:
Given : bw = 300mm,
bf = l000mm,
Df = 120mm,
= 0.87x415x1885 / (0.36x1000x20)
ww xu< xu,max, section is under reinforced, calculate the moment of resistance by the
following expression
asy
= 0.87x415x1885x410x(1-((1885x415)/(1000x410x20)))
= 252.41x106 N-mm
eer
following section properties. Use M20 and Fe 415 HYSD bars. Width of flange =
ing
l300mm, Thickness of flange = l00mm, Width of rib = 325mm, Effective depth =
600mm, Area of steel = 4000mm2
Solution: .ne
Given: bw = 325mm,
bf = l300mm,
t
Df = l00mm,
d = 600mm,
fy =415N/mm2,
Ast = 4000mm2.
Assuming Actual Neutral Axis (xu) lies within the flange (i.e, xu ≤ Df )
Xu/d = (0.87.fy.Ast)/ (0.36.fck.b.d)
C2 = 0.45.fck.(bf – bw).Df
= 0.45x20x100x(1300-325)
ww = 0.87x415x4000 = 1444200 N
2340 xu + 877500 = 1444200
w.E xu = 242.18mm
asy
xu,max = 0.48d = 0.48x600 =
En
288mm xu< xu,max, section is under
reinforced. Df / xu = 100 / 242.18 = 0.413
< 0.43. gin
Hence use equation for Mu calculation
eer
ing
Mu= 0.36. fck.bw.d2.(xu/d).( 1-0.42.(xu/d)) + 0.45.fck.(bf – bw).Df.(d-(Df/2))
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
Solution:
Given: bf =1500 mm,
Df = 100 mm,
ww D = 600 mm,
asy
eff. cover = 40 mm,
fck = 15 N/mm2,
fy = 415 N/mm2. En
gin
Assuming Actual Neutral Axis (xu) lies within the flange (i.e, xu ≤ Df )
Xu/d = (0.87.fy.Ast)/ (0.36.fck.b.d)
eer
= 0.87x415x2455 / (0.36x1500x15)
= 109.42mm >Df (100mm) ing
Assumption is wrong, neutral axis lies below the flange and
.ne
Df / xu <0.43 Df / d
= 100 / 600 t
= 0.166 < 0.2
The value of xu by using relation
C1+C2=T
C1 = 0.36.fck.xu.bw = 0.36x15x300x xu
= 1620 xu
C2 = 0.45.fck.(bf – bw).Df
= 0.45x15x100x(1500-300) = 810000 N T
= 0.87. fy. Ast = 0.87x415x2455 = 886377.75 N
1620 xu+ 810000 = 886377.75
xu = 47.14mm xu < Df
Therefore assumption is that
Df / xu > 0.43,
C2 value changes, C2 = 0.45.fck.(bf – bw).yf
yf = (0.15 xu + 0.65Df)
= 0.15x xu+ 0.65x100 = 0.15x xu + 65
C2 = 0.45x15x (1500-300) x (0.15x xu + 65)
= 1215 x xu + 526500
Now using relation
C1+C2=T
gin
xu < xu,max, section is under reinforced.
Hence use equation for Mu calculation
Mu
eer
= 0.36. fck.bw.d2.(xu/d).( 1-0.42.(xu/d)) + 0.45.fck.(bf – bw).yf.(d-(yf/2)) yf
= 0.15x xu +65
= 0.15x 126.94 + 65 = 84.04mm
ing
Xu/d = 126.94 / 560 = 0.23 .ne
t
Mu= 0.36x 0.23 x (1-(0.42x0.23)) x300x5602x15 + 0.45x15x(1500-300)x84.04x(560-(84.04/2))
= 105559905+ 680724 (560 – 42.02)
= 458.16x106 N-mm
= 458.16 kN-m
An isolated T-beam has a flange of 1200x100mm, width of rib is 250mm and effective
depth is 600mm. Tension steel is 3500mm2. Grade of concrete is M20 and steel grade
is Fe415. Compute the ultimate moment of resistance. Span of SS beam = 8m. Also
calculate the safe superimposed load the T-beam can carry, if effective cover = 50mm.
Solution:
Given: bw = 250mm,
bf = l200mm,
ww Df = l00mm,
d = 600mm,
asy
fy = 415N/mm2,
Ast = 3500mm2,
l = 8m,
En
D = 600 + 50 = 650mm.
gin
eer
For Isolated T-beam Effective flange width is the least of the following:
1. bf = I /[( I/b)+4] + bw
= 8000/((8000/1200)+4)+250 = 1000mm
ing
2. bf = actual width of the flange = 1200 mm
Therefore, bf = 1000 mm. .ne
t
Assuming Actual Neutral Axis (xu) lies within the flange (i.e, xu ≤ Df )
Xu/d = (0.87.fy.Ast)/ (0.36.fck.b.d) = 0.87x415x3500 / (0.36x1000x20) =
175.51mm > Df (100mm)
Assumption is wrong, neutral axis lies below the flange.
Df / d = 100 / 600 = 0.166 < 0.2
The value of xu by using relation C1+C2=T
C1 = 0.36.fck.xu.bw = 0.36x20x250x xu = 1800 xu
C2 = 0.45.fck.(bf – bw).Df = 0.45x20x100x(1000-250) = 675000 N T = 0.87. fy.
Ast = 0.87x415x3500 = 1263675 N
1800 xu+ 675000 = 1263675
xu = 327.04mm
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
ww
w.E
asy
En
gin
eer
ing
.ne
t
Problem: Design a reinforced concrete beam of rectangular cross-section for the following data
b = 300mm d = 800mm
D = 850mm fck= 15 N/mm2
fy= 250N/mm2 Mu= 200 kNm
V = 100 kN Tu=50kN.m
ww
w.E
Since tensile reinforcement is not known at the outset, therefore the minimum % of tension steel is
asy
En
gin
eer
Hence both the longitudinal and transverse reinforcement shall be provided
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
UNIT 3a syE
ngi
nee
rin
g.n
et
DESIGN OF SLABS
The one way slab is supported by a beam The two way slab is supported by the beam
1
on two opposite side only. on all four sides.
ww beam.
directions.
3 w.E One way slab two opposite side support Two Way Slab four side mins all side
asy
beam /wall supported beam /wall
One way slab is bend only in one spanning Two way slab is bend both spanning side
4
En
side direction while load transfer direction while load transfer
One way slab is bend only in one spanning ginIn two-way slab, the crank is provided in
5
side direction while load transfer
eer
four directions.
6
If L/b the ratio is greater than or equal 2 or
ing
If L/b the ratio is less than 2 then it is
7
In one-way slab, the load is carried in one
directions.
beam.
The deflected shape of the one-way slab is Whereas the deflected shape of the two-way
8
cylindrical. slab is a dish or saucer-like shape.
10 In one-way slab quantity of steel is less. In two-way slab quantity of steel is more as
12 Ly/Lx ≥ 2 one way slab spanning. Ly/Lx < 2 two way slab spanning
One way slab near about 100mm to two way slabs is in the range of 100mm to
13
150mm based on the deflection. 200mm depending upon
ww
w.E
asy
En
gin
eer
ing
.ne
t
INTRODUCTION
A slab is like a flat plate loaded transversely and supported on its edges. Under
the loads, it bends and the directions of its bending depend on its shape and support
conditions. A beam bends only in one direction, i.e. in its own plane; where as a slab
may have multidirectional bending. Therefore, slabs may have different names
depending upon its bending, support conditions and shapes. For example, a slab may be
called
ww
(a) One-way simply supported rectangular slab,
(b) Two-way simply supported or restrained rectangular slab,
w.E
(c) Cantilever rectangular slab,
asy
(d) Fixed or simply supported circular slab, etc
En
One-way slab means it bends only in one direction and, therefore, reinforcement
for bending (i.e. main reinforcement) is provided only in that direction. A slab
gin
supported on all sides bends in all the directions so the main reinforcements provided
eer
shall be such that they may be effective in all directions. For ease of analysis and
ing
convenience of reinforcement detailing, the bending moments in a slab are calculated in
.ne
two principal directions only and, therefore, such a slab is called a two-way slab.
A slab is designed as a beam of unit width in the direction of bending. In this
t
unit, only the most commonly used rectangular slabs, with uniformly distributed load
is described.
Objectives
After studying this unit, you should be able to
• describe the design and detailing of cantilever slabs,
• design and explain detailing of one-way and two-way simply supported slabs, and
• explain the design and detailing of two-way restrained slabs
types of slabs
(a) The maximum diameter of reinforcing bars shall not exceed1/8 th of total
thickness (D) of the slab.
(b) Normally, shear reinforcement is not provided in slabs. The shear resistance
requirements may, then, be complied either by increasing the percentage of
tensile reinforcement or by increasing the depth of slab, but the latter is preferred
as it is economical. For solid slabs, the design shear strength for concrete slab
shall be τ ,c, K, , where K has the values given IS 800.
(c) To take care of temperature and shrinkage stresses, minimum reinforcement in
either direction shall not be less than 0.15 percent and 0.12 percent of total cross
ww section area of concrete section for mild steel and high strength deformed bars,
w.E
respectively.
(d) To meet the requirement for limit state of cracking the following two rules are
observed: asy
(i)
En
The horizontal distance between parallel main reinforcement shall not
gin
be more than 3 times the effective depth of slab or 300 mm whichever
(ii)
is smaller.
eer
The horizontal distance between parallel bars provided against
ing
temperature and shrinkage shall not be more than 5 d or 450 mm,
whichever is smaller
.ne
DESIGN OF SLAB
Definition :
t
Slab is a thin flexural member used as a floor of structure to support the imposed load
Loads on slab :
Generally in design of horizontal slab two types of loads are considered.
Dead load
Imposed load
Dead load :
The dead load in slab comprises of the immovable partitions. Floor finishes
weathering courses and primarily its weight .The dead loads are to be determined
ww When the ratio of the longer span to shorter span is greater than 2, it is called one
way slab and bending takes place along one direction. The loads on the slab is
w.E
transferred to the supports only on the main reinforcement. Hence main reinforcement
is provided in the shorter span.
Minimum requirement in slab : asy
En
As per clause 26.5.2.1 of IS 456:2000, the reinforcement in either direction ,in
gin
slabs shall not be less than 0.12% of the total cross sectional area , when HYSD bars
Fe415 are used.
Maximum size of bars in slabs eer
ing
As per clause 26.5.2.2 of IS 456 :2000 , the reinforcing bars shall not exceed 1/8 of the
total thickness of the slab.
.ne
DESIGN OF CANTILEVER SLAB
t
Design a cantilever chajja slab projecting 1m from the support using M20 grade
concrete and Fe415 HYSD bars. Adopt a live load of 3kN/m2.
i. Given
L = 1m
q = 3 kN/m2
fck = 20 N/mm2
fy = 415 N/mm2
𝜏bd = 1.2N/mm2 for plain bars for
M20grade concrete
Live load
asy= 3.000
Finishes
Total working load = En
= 0.875 kN/m
7.000 kN/m
Design ultimate load wu = gin
(1.5 x 7.00)
= 10.5 kN/m
eer
ing
iv. Ultimate design moments and shear forces
Mu = 0.5 wu L2 .ne
=
=
0.5 x 10.5 x 12
5.25 kNm
t
Vu = wu l
= 10.5 x 1
= 10.50 kN
= 62.10 kNm
Since Mu < Mu lim ,
Section is under – reinforced.
vi. Reinforcements
fy Ast
Mu = 0.87 fy Ast d (1 - )
fck bd
140 Ast
5.25 x 106 = 0.87 x 415x Ast x 150 (1 – )
20 × 1000 ×150
Solving Ast = 105 mm2 < Ast min
ww Hence provide 10 mm diameter bars at 300 mm centres (Ast = 262 mm2) in the
span direction and the same as distribution reinforcement.
w.E
vii. Anchorage length
asy 𝟎.𝟖𝟕𝐟𝐲 𝛟
Ld
En
=
𝟒𝛕𝐛𝐝
=
gin
𝟎.𝟖𝟕 𝐱 𝟒𝟏𝟓 𝐱 𝟏𝟎
𝟒 𝐱 𝟏.𝟐 𝐱 𝟏.𝟔
= 470 mm
eer
viii. Check for deflection control ing
(𝒅𝐋)max (𝒅𝐋)Basic x kt .ne
And kc
=
= kf = 1.00 t
𝟏𝟎𝟎 𝐀𝐬𝐭
𝐩𝐭 =
𝐛𝐝
𝟏𝟎𝟎 𝐱 𝟐𝟔𝟐
=
𝟏𝟎𝟑 𝐱 𝟏𝟓𝟎
= 0.174 mm
kt = 1.8
(𝒅𝐋)Actual =
𝟏𝟎𝟎𝟎
𝟏𝟓𝟎
= 6.66 < 12.6
ww
w.E
asy
En
gin
eer
ing
.ne
t
Design a simply supported one–way slab over a clear span of 3.5 m. It carries a live load
of 4kN/m2 and floor finish of 1.5kN/m2. The width of supporting wall is 230 mm. Adopt
M-20 concrete & Fe-415 steel.
ww
& clear cover 15mm for mild exposure d =
Effective span is lesser of the two
160 – 25 = 140mm
w.E
i. l = 3.5 + 0.23 (width of support) = 3.73 m
ii. l =
asy
3.5 + 0.14 (effective depth)
Effective span = 3.64 m
= 3.64 m
23.60 x 106
= √
0.138 x 20 x 1000
w.E Ast =
0.5fck
fy
[ 1 – √1 − 4.6 𝑀𝑢
𝑓𝑐𝑘 𝑏𝑑 2
] bd
asy [ 4.6 ×23.60 × 106
Ast
En
=
0.5 x 20
415
1– √1 −
20 ×1000×1402
]1000x140
= 505 mm2 gin
Spacing of 10mm Sv =
ast
Ast
x 1000 eer
Sv =
78
x 1000 =ing 154mm
505
Provide 10mm @ 150C/C. .ne
Distribution steel@ 0.12% of the Gross area
0.12
x 1000 x 160 = 192 mm2
t
100
50
Spacing of 10mm Sv = x 1000 = 260 mm
192
Provide 8mm @ 260mm
Step: 5 Check for shear
Wu l
Design shear Vu =
2
14.25 x 3.64
=
2
= 25.93 kN
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
25.93 × 103
τv =
1000 × 140
= 0.18 N/mm2 (<τc max = 28 N/mm2)
w.E k2
k3
-
-
Modification factor for compression steel
Modification factor for T-sections
asy
if span exceeds 10 m (10/span)
En
𝐤 𝟏 = 1.38 for 𝐩𝐭 = 0.37 (Fig. 4, cl.32.2.1)
ww
w.E
asy
E ngi
nee
rin
g.n
et
ww The dead load in slab comprises of the immovable partitions. Floor finishes
weathering courses and primarily its weight .The dead loads are to be determined
w.E
based on the weight of the materials .
Imposed loads:
asy
Imposed load is the load induced by the intent use or occupancy of the building
En
including the weight of movable partitions load due to impact vibrations.
Basic rules for the design of the slab :
gin
eer
The two main factors to be considered while designing the slab are:
Strength of the slab against flexure, shear, twisted.
Stiffness against deflection ing
One way slab – codal requirements : .ne
t
When the ratio of the longer span to shorter span is greater than 2, it is called one
way slab and bending takes place along one direction. The loads on the slab is
transferred to the supports only on the main reinforcement. Hence main reinforcement
is provided in the shorter span.
Minimum requirement in slab :
As per clause 26.5.2.1 of IS 456:2000, the reinforcement in either direction ,in
slabs shall not be less than 0.12% of the total cross sectional area , when HYSD bars
Fe415 are used.
Maximum size of bars in slabs
As per clause 26.5.2.2 of IS 456 :2000 , the reinforcing bars shall not exceed 1/8 of the
Design a R.C Slab for a room measuring 6.5mx5m. The slab is cast monolithically over
the beams with corners held down. The width of the supporting beam is 230
mm.The slab carries superimposed load of 4.5kN/m2. Use M-20 concrete and Fe-500
Steel.
Since, the ratio of length to width of slab is less than 2 and slab is resting on
beam, the slab is designed as two way restrained slab.
Step: 1 Depth of slab and effective span
ww
Assume approximate depth d = l/30
w.E Assume D
=
=
5000/30
180 mm
= 166mm
asy
& clear cover 15 mm for mild exposure d
Mx = ∝x Wu 𝑙𝑥 2
My = ∝y Wu 𝑙𝑥 2
ly
For = 1.3,
lx
∝x = 0.079
∝y = 0.056
w.E
Positive moment at mid span of longer span Mx
= 28.40 kNm
= 0.056 x 13.5 x 5.162
En
Minimum depth required from maximum BM consideration
d =
gin
M
√ 0.138uf
ck b
√
28.40 x 106 eer
=
0.138 x 20 x 1000
ing
However, provide d
d =
=
103 mm
160 mm .ne
Step: 4 Area of Reinforcement
t
Area of steel is obtained using the following equation.
fy Ast
Mu = 0.87 fy Ast d (1 - )
fck bd
500 Ast
20.13 x 106 = 0.87 x 500x Ast x 150 (1 – )
20 × 1000 ×150
20.13 x 106 = 65250 Ast – 10.875 Ast2
Solving, Ast = 327 mm2
Spacing at 10 mm;
79
x 100 = 241
327
w.E
Step: 5 Check for shear
Wu l
Design shear Vu
asy =
2
13.5 x 5.16
En =
2
= 34.83 kN
gin
34.83 × 103
τv =
1000 × 160 eer
= 0.217 N/mm 2
ing
(<τc max = 28 N/mm2)
.ne
Shear resisted by concrete 𝛕𝐜 = 0.42 for 𝐩𝐭 = 0.37 (Table 19, IS 456-2000)
𝛕𝐜 > 𝛕𝐯 t
Step: 6 Check for Deflection
ww
w.E
asy
En
gin
eer
ing
.ne
t
DESIGN EXAMPLES
1.A slab has clear dimensions 4 m x 6 m with wall thickness 230 mm the live load
on the slab is 5 kN/m2 and a finishing load of 1kN/m2 may be assumed. Using M20
concrete and Fe415 steel, design the slab
Given data
Dimension = 4 x 6
ww Shorter span 1x = 4m
asy 𝑙𝑥 4
En = 1.5 < 2
It is a two way slab.
Width of support gin
= 230 mm
Live load = 5 kN/m2
eer
Materials ,fck = 20 N/mm2
Fy = 415 N/mm2
ing
Depth of slab: .ne
Effective depth d =
𝑠𝑝𝑎𝑛
25
4000
t
=
25
= 160 mm
Assume cover 20mm, 10mm diameter rod
10
Overall depth D = 160 + 20 +
2
=185mm
D = 200 mm
Effective span:
𝑤𝑎𝑙𝑙 𝑡ℎ𝑖𝑐𝑘𝑛𝑒𝑠𝑠 𝑤𝑎𝑙𝑙 𝑡ℎ𝑖𝑐𝑘𝑛𝑒𝑠𝑠
1. c/c of supports le = + 𝑠ℎ𝑜𝑟𝑡𝑒𝑟 𝑠𝑝𝑎𝑛 +
2 2
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
0.23 0.23
= +4+
2 2
= 4.23 m
2. clear span + effective depth = 4 + 0.24
= 4.24m
Take least value, 1e = 4.23 m
Load calculation:
Self weight= B X D X γ
= 1 X 0.2 X 25
ww = 5 kN/ m
Live load = 5 kN/m
gin
= 16.5 kN/ m
Bending moment & shear force:
MX = αX WUle2
eer
My = αy WUle2 ing
From table 26 of IS 456: 2000 .ne
𝑙y
lx
= 1.5 t
Four edges are discontinuous,
αX = 0.089
αy =0.056
Bending moment:
MX = 15.59x4.22x0.089
= 25.01 kNm
MY = 0.056 x 15.93 x 4.22
= 15.73 kNm
Shear force :
𝑊𝑢𝑙𝑒
SF =
2
15.93×4.2
=
2
= 33.45 KN
Check for Depth :
MU = 0.138 fckbd2
25×106
d=√
0.138×20×1000
ww = 95.17 mm
dprov>dreq
w.E Hence the design is safe.
Area of reinforcement:
For shorter span: asy
En
MU = 0.87 fy × Ast × d [1 –
Ast ×fy
]
gin
25 ×106 = 0.87 × 415 × Ast × 160 [1-
b×d×fck
Ast ×415
]
= 240 mm2
× 1000× 200
t
Provide 10mm dia bar.
Spacing :
ast π⁄ ×102
𝑖. × 1000 = 4 × 1000
Ast 459.85
= 170.79 mm ≈ 170mm
ii. 3d = 3 x 160 = 480 mm
take the least value = 170 mm
provide 10 mm dia bar 170 mm c/c.
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
ii) 3d = 3×160
ww = 480mm
Take the least value for spacing = 300mm,
w.E
provide 10mm diameter bar, 300m
gin
=
33.45 ×103
= 0.2N⁄mm2
eer
To find 𝜏c ,
ing
Percentage of steel, pt = 100 ×
Ast
b×d .ne
= 100 ×
= 0.28%
459.85
1000×160 t
The value lies between 0.25 and 0.50, use interpolation
X1 0.25 Y1 0.36 X 0.28
X2 0.5 Y2 0.48 Y ?
(y2 − y1 )
Y = 𝜏c = y1 + (x – x1)
(x2 − x1 )
0.48−0.36
= 0.36 + (0.28 – 0.25)
0.50−0.25
= 0.37N⁄mm2
To find K ,
Overall depth, D = 185mm
Refer pg no:73 of IS 456-2000
This value lies between 150 to 175, use interpolation
X1 150 Y1 1.3 X 185
X2 175 Y2 1.25 Y ?
(y2 − y1 )
Y = K= y1 + (x – x1)
(x2 − x1 )
1.25−1.3
= 1.3 + (185 - 150)
175−150
ww = 1.27
w.E
𝜏c× K = 0.38× 1.27
= 0.48N⁄mm2
asy
𝜏v <𝜏c× K,
En
Hence the design is safe.
Check for deflection:
𝑙 𝑙 gin
𝑑
max =
𝑑
basic
= 20 × 1.4 ×1 = 30
× Kb × Kc
eer
𝑙
=
Effective span ing
.ne
pro
𝑑 Effective depth
4000
=
𝑙
160
( )max> ( )pro
𝑑
= 26.25mm
𝑙
𝑑
t
Hence the design is safe for deflection.
Check for crack control:
1. Reinforcement provided must be greater than minimum percentage of
reinforcement provided as per IS 456-2000.
Astmin = 0.12% of cross section area
= 0.12/100 × 1000× 185
= 222 mm2
Ast pro >Astmin,
Hence it is safe.
2. Spacing is not greater than 3d.
3d = 3 ×160
= 480mm
Spacing < 3d,
Hence it is safe.
𝐷
3. Diameter of reinforcement should be less than
8
𝐷
d<
8
𝐷 185
=
ww = 28.12mm
8 8
w.E d<
𝐷
8
En
gin
eer
ing
.ne
t
2.A slab has clear dimensions 3.5 m x 6 m with wall thickness 230 mm the live
load on the slab is 5 kN/m2 and a finishing load of 1kN/m2 may be assumed. Using
M20 concrete and Fe415 steel, design the slab
Given data
Dimension = 3.5 x 6
Shorter span 1x = 3.5
Longer span 1y =6
𝑙𝑦 6
=
𝑙𝑥 3.5
= 1.7 < 2
It is a two way slab
Width of support = 230 mm
Live load = 5 kN/m2
Materials ,fck = 20 N/mm2
Fy
ww = 415 N/mm2
w.E
Depth of slab,
Effective depth, d
asy =
𝑠𝑝𝑎𝑛
25
En =
3500
25
i. c/c of supports le =
𝑤𝑎𝑙𝑙 𝑡ℎ𝑖𝑐𝑘𝑛𝑒𝑠𝑠
2
+ 𝑠ℎ𝑜𝑟𝑡𝑒𝑟 𝑠𝑝𝑎𝑛 +
2
t
𝑤𝑎𝑙𝑙 𝑡ℎ𝑖𝑐𝑘𝑛𝑒𝑠𝑠
0.23 0.23
= + 3.5 +
2 2
= 3.73 m
ii. clear span + effective depth = 3.5 + 0.14
= 3.64
Take least value, 1e = 2.6 m
Load calculation:
Self weight =BXDX γ
= 1 X 0.165 X 25
= 4. 13 KN/ m
Live load = 5 KN/m
Floor finish = 1 KN/m
Total load = 4.13 + 5 + 1
= 10.13 KN/ m
Factor load = 1.5 x 10.13
= 15.2 KN/ m
ww
w.E
Bending moment & shear force:
MX = αX WUle2
asy My = αy WUle2
From table 26 of IS 456: 2000
En 𝑙y
lx gin
= 1.7
MU = 0.138 fckbd2
19.74×106
d = √0.138×20×1000
= 84.57 mm
dprov>dreq
Hence the design is safe
Area of reinforcement:
For shorter span:
ww MU = 0.87 fy × Ast × d [1 –
Ast ×fy
b×d×fck
]
En
Ast min = 0.12% × bd
=
0.12
100 gin
× 1000× 165
= 198 mm2
eer
Provide 10mm dia bar
Spacing : ing
𝑖
ast
× 1000 =
π⁄ ×102
4
× 1000 .ne
Ast 416.9
= 188.7 mm t
≈ 180mm
ii. 3d = 3 x 140
= 420 mm
Take the least value for spacing
provide 10 mm dia bar 180 mm c/c
For longer span:
Ast ×fy
MU = 0.87 fy × Ast × d [1 – ]
b×d×fck
Ast ×415
11.24 ×106 = 0.87 × 415 × Ast × 140 [1- ]
1000×100×20
Ast= 230.2mm2
Spacing :
ast π⁄ ×102
4
i. × 1000 = × 1000
Ast 230.2
= 323.72mm
≈ 300mm
ii. 3d = 5 ×140
= 800mm
iii. 300 mm
Take the least value for spacing
ww
provide 10mm diameter bar, 300mm c/c
w.E
Check for shear:
vu
asy
Permissible shear stress, 𝜏v = ⁄b × d
En
=
27.66 ×103
1000×140
= 0.19N⁄mm2
gin
Nominal shear stress
To find 𝜏c ,
= 𝜏c × K
eer
Percentage of steel, pt = 100 ×
Ast
ing
= 100 ×
b×d
416.69
.ne
= 0.29%
1000×140
t
The value lies between 0.25 and 0.50, use interpolation
X1 0.25 Y1 0.36 X 0.29
X2 0.5 Y2 0.48 Y ?
(y2 − y1 )
Y = 𝜏c = y1 + (x – x1)
(x2 − x1 )
0.48−0.36
= 0.36 + (0.29 – 0.25)
0.50−0.25
= 0.38N⁄mm2
To find K ,
Overall depth, D = 165mm
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
(y2 − y1 )
Y = K= y1 + (x – x1)
(x2 − x1 )
1.25−1.3
= 1.3 + (165 - 150)
175−150
= 1.27
𝜏c× K = 0.38× 1.27
= 0.48N⁄mm2
ww 𝜏v <𝜏c× K,
w.E
Hence the design is safe.
asy
Check for deflection:
En
(l⁄d)max = (l⁄d)basic × Kb × Kc
gin
= 20 × 1.5 ×1
= 30 eer
(l⁄d)pro =
Effective span
ing
=
Effective depth
3.64 .ne
0.14
= 26mm t
(l⁄d)max> (l⁄d)pro
Hence the design is safe for deflection.
= 198 mm2
Ast pro >Astmin,
Hence it is safe.
5. Spacing is not greater than 3d.
3d = 3 ×140
= 420mm
Spacing < 3d
Hence it is safe.
6. Diameter of reinforcement should be less than D⁄8
ww d < D/8
D⁄ = 165⁄
8 8
w.E = 20.62mm
= 700 mm
Provide 8 mm ∅ bar 160mm c/c , for the length of 700 mm at the corners
Reinforcement details
ww
w.E
asy
En
gin
eer
ing
.ne
t
Design a one-way slab for an office floor which is continuous over T beams at 3.5m
intervals. Assume a live load 4kN/m2 adopt M20 grade concrete and Fe415 steel
HYSD bars.
Given:
L = 3.5 m
q = 4 kN/m2
fck = 20 N/mm2
fy = 415 N/mm2
ww
Step: 1 Depth of slab
w.E
Assuming a span/depth ratio of 26 (Clause 23.2.1 of IS 456)
Effective depth d
asy=
= (span/26)
3500/26 = 135 mm
Adopt d En
= 140 mm
D = 160 mm gin
Step: 2 Load calculation
eer
Self-weight of slab = 0.165 x 25 =
ing
4.125 kN/m2
5 x 3.52 4 x 3.52
= 1.5 [ + ]
10 9
= 17.35 kNm
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
5 x 3.52 4 x 3.52
= 1.5 [ + ]
12 10
= 15 kNm
Step: 4 Shear force calculation
Maximum shear force at the support
Vu = 1.5 x 0.6 (g + q) L
= (1.5 x 0.6) (5 + 4) 3.5
ww = 28.35 kN
w.E
Step: 5 Check for Depth of the slab
Mu lim = 0.138 fck bd2
Since Mu En =
<
54.1 kNm
Mu lim ,
Section is under – reinforced. gin
Step: 6 Reinforcement details
eer
Mu = 0.87 fy Ast d (1 -
ing
fy Ast
fck bd
)
28.35 x 103
=
103 x 140
= 0.20 N/mm2
100 x Ast
pt =
bd
100 x 262
=
103 x 140
= 0.187
Refer to Table 19, IS 456 and readout:
kτc = 1.27 x 0.30 = 0.38 N/mm2
Since 𝛕𝐜 > 𝛕𝐯 , the sab is safe against shear stresses.
ww
Step: 8 Check for Deflection
w(.)E
Considering the end and inferior spans
𝐋
(𝒅𝐋)Basic x kt x kc x kf
𝒅
max
Also kc
asy=
= kf = 1.00
𝐩𝐭 En 𝟏𝟎𝟎 𝐱 𝟑𝟗𝟑
=
𝟏𝟎𝟑 𝐱 𝟏𝟒𝟎
gin
=
From Fig.8.1, read out
0.28
kt = eer
1.5
(𝒅𝐋)max = (𝟐𝟎+𝟐𝟔
𝟐
)1.5 = 34.5ing
(𝒅𝐋)Actual 𝟑𝟓𝟎𝟎 .ne
=
𝟏𝟒𝟎
General
Staircases are generally provided connecting successive floors of a building and in small
buildings. They are only means of access between the floors. The staircase comprises of flight
of step generally with one or more intermediate landings provides between the floors level.
Dog-legged staircase is the most common type used in all types of buildings . it
comprises of two adjacent flights running parallel with a landing slab at mid height.
Loads on staircases
The various types of loads to be resisted by the staircases are grouped under dead and
ww
live load
1. Dead load which includes the self-weight of the stair , tread and risers and self
asy
uniformly distributed live load of 2 to 3 KN/m2 depending upon the users and for
public buildings, a uniformly distributed load of 5KN/m2 is specifies in the code
TYPES OF STAIRCASE En
Straight stairs
Quarter turn stairs
gin
Half turn stairs eer
Spiral stairs
Curved stairs ing
Dog legged stair
.ne
t
STRAIGHT STAIRS
These are the stairs along which there is no change in direction on any flight between two
successive floors. The straight stairs can be of following types.
Scissors stairs
Straight stairs can have a change in direction at an intermediate landing. In case of angle
stairs, the successive flights are at an angle to each other. Scissor stairs are comprised of a pair
of straight runs in opposite directions and are placed on opposite sides of a fire resistive wall.
ww
w.E Straight Stair with Single Flight
asy
QUARTER TURN STAIRS En
gin
They are provided when the direction of flight is to be changed by 90 0. The change in
eer
direction can be effected by either introducing a quarter space landing or by providing winders
at the junctions.
ing
.ne
t
SPIRAL STAIRS
These stairs are similar to circular stairs except that the radius of curvature is small and the
stairs may be supported by a center post. Overall diameter of such stairs may range from 1 to
2.5 m.
ww
CURVED STAIRS
w.E
These stairs, when viewed from above, appear to follow a curve with two or more centre of
curvature, such as ellipse.
gin
step before 180 degrees and persevering upwards. Due to its appearance in sectional elevation,
it is a very common and popular stair consisting of two flights that run in opposite directions
eer
separated by a landing in the middle space. These staircases are used when the available space
ing
is equal to twice the width of the stairs and stairs lie in their compact layout that has better
circulation from a design point of view.
.ne
t
ww
w.E
UNIT 4a syE
ngi
nee
rin
g.n
et
Compression members are structural elements primarily subjected to axial compressive forces
and hence, their design is guided by considerations of strength and buckling. Examples of compression
member pedestal, column, wall and strut.
ww Effective length: The vertical distance between the points of inflection of the compression
w.E
member in the buckled configuration in a plane is termed as effective length le of that compression
member in that plane. The effective length is different from the unsupported length l of the member,
asy
though it depends on the unsupported length and the type of end restraints. The relation between the
effective and unsupported lengths of any compression member is
En le = k l
gin
Where k is the ratio of effective to the unsupported lengths.
eer
Pedestal: Pedestal is a vertical compression member whose effective length le does not exceed three
ing
times of its least horizontal dimension b. The other horizontal dimension D shall not exceed four times
of b.
.ne
t
Column: Column is a vertical compression member whose unsupported length l shall not exceed sixty
times of b (least lateral dimension), if restrained at the two ends. Further, its unsupported length of a
cantilever column shall not exceed 100b2/D, where D is the larger lateral dimension which is also
restricted up to four times of b
Wall: Wall is a vertical compression member whose effective height Hwe to thickness t (least lateral
dimension) shall not exceed 30. The larger horizontal dimension i.e., the length of the wall L is more
than 4t.
Types of columns
1. Based on shape
Rectangle
Square
Circular
Short column and Long column or Short and Slender Compression Members
ww A compression member may be considered as short when both the slenderness ratios namely
lex/D and ley/b are less than 12:
w.E
Where
lex= effective length in respect of the major axis, D= depth in respect of the major axis, l ey=
effective length in respect of the minor axis, and b = width of the member.
asy
It shall otherwise be considered as a slender or long compression member.
En
The great majority of concrete columns are sufficiently stocky (short) that slenderness
gin
can be ignored. Such columns are referred to as short columns. Short column generally fails by
crushing of concrete due to axial force. If the moments induced by slenderness effects weaken
eer
a column appreciably, it is referred to as a slender column or a long column. Long columns
generally fail by bending effect than due to axial effect. Long column carry less load compared
to long column.
ing
3. Based on pattern of lateral reinforcement
.ne
Tied columns with ties as laterals
Columns with Spiral steel as laterals or spiral columns t
Majority of columns in any buildings are tied columns. In a tied column the longitudinal
bars are tied together with smaller bars at intervals up the column. Tied columns may be square,
rectangular, L-shaped, circular, or any other required shape. Occasionally, when high strength
and/or high ductility are required, the bars are placed in a circle, and the ties are replaced by a
bar bent into a helix or spiral. Such a column, called a spiral column. Spiral columns are
generally circular, although square or polygonal shapes are sometimes used. The spiral acts to
restrain the lateral expansion of the column core under high axial loads and, in doing so, delays
the failure of the core, making the column more ductile. Spiral columns are used more
extensively in seismic regions. If properly designed, spiral column carries 5% extra load at
failure compared to similar tied column.
ww
w.E
asy
5. Based on materials
En
Timber
gin
eer
Stone
Masonry
RCC
ing
PSC
Steel .ne
Aluminium ,
Composite column
t
In practical construction, columns are rarely truly concentric. Even a theoretical column loaded
axially will have accidental eccentricity due to inaccuracy in construction or variation of materials etc.
Accordingly, all axially loaded columns should be designed considering the minimum eccentricity
ww The longitudinal reinforcing bars carry the compressive loads along with the concrete. stipulates
the guidelines regarding the minimum and maximum amount, number of bars, minimum diameter of
w.E
bars, spacing of bars etc. The following are the salient points:
The minimum amount of steel should be at least 0.8 per cent of the gross cross-sectional area
asy
of the column required if for any reason the provided area is more than the required area.
En
The maximum amount of steel should be 4 per cent of the gross cross-sectional area of the
column so that it does not exceed 6 per cent when bars from column below have to be lapped
with those in the column under consideration.
gin
eer
Four and six are the minimum number of longitudinal bars in rectangular and circular
columns, respectively.
The diameter of the longitudinal bars should be at least 12 mm. ing
.ne
Columns having helical reinforcement shall have at least six longitudinal bars within and in
t
contact with the helical reinforcement. The bars shall be placed equidistant around its inner
circumference.
The bars shall be spaced not exceeding 300 mm along the periphery of the column.
The amount of reinforcement for pedestal shall be at least 0.15 per cent of the cross-sectional
area provided.
Pitch and Diameter of Lateral Ties
Pitch: The maximum pitch of transverse reinforcement shall be the least of the following:
(i) the least lateral dimension of the compression members;
(ii) sixteen times the smallest diameter of the longitudinal reinforcement bar to be tied; and
(iii) 300 mm.
(b) Diameter: The diameter of the polygonal links or lateral ties shall be not less than one-fourth of the
diameter of the largest longitudinal bar, and in no case less than 6 mm.
Assumptions
The maximum compressive strain in concrete in axial compression is taken as 0.002.
The maximum compressive strain at the highly compressed extreme fibre in concrete subjected
ww to axial compression and bending and when there is no tension on the section shall be 0.0035
minus 0.75 times the strain at the least compressed extreme fibre.
w.E
Plane sections normal to the axis remain plane after bending.
The maximum strain in concrete at the outermost compression fibre is taken as 0.0035 in
bending.
asy
The relationship between the compressive stress distribution in concrete and the strain in
En
concrete may be assumed to be rectangle, trapezoid, parabola or any other shape which results
in prediction of strength in substantial agreement with the results of test.
gin
An acceptable stress strain curve is given in IS:456-200. For design purposes, the compressive
strength of concrete in the structure shall be assumed to be 0.67 times the characteristic strength.
eer
The partial safety factor y of 1.5 shall be applied in addition to this.
The tensile strength of the concrete is ignored.
P.1.Design the reinforcement in a column of size 400 mm x 600 mm subjected to an axial load of
2000 kN under service dead load and live load. The column has an unsupported length of 4.0 m
and effectively held in position and restrained against rotation in both ends. Use M 25 concrete
and Fe 415 steel.
w.E
Step 3: Area of steel
asy
Pu = 0.4 fck Ac + 0.67 fy Asc
En
3000(103) = 0.4(25){(400)(600) – Asc} + 0.67(415) Asc which gives,
Asc = 2238.39 mm2
gin
Provide 6-20 mm diameter and 2-16 mm diameter rods giving 2287 mm2 (> 2238.39 mm2)
eer
and p = 0.953 per cent, which is more than minimum percentage of 0.8 and less than maximum
percentage of 4.0. Hence, o.k.
Step 4: Lateral ties
ing
.ne
The diameter of transverse reinforcement (lateral ties) is determined from cl.26.5.3.2 C-2 of IS
t
456 as not less than (i) θ/4 and (ii) 6 mm. Here, θ = largest bar diameter used as longitudinal
reinforcement = 20 mm. So, the diameter of bars used as lateral ties = 6 mm.
The pitch of lateral ties should be not more than the least of
(ii) sixteen times the smallest diameter of longitudinal reinforcement bar to be tied = 16(16) = 256 mm
(iii) 300 mm
Design the reinforcement in a column of size 450 mm × 600 mm, subject to an axial load
of 2000 kN under service dead and live loads. The column has an unsupported length of 3.0m
ww
and its ends are held in position but not in direction. Use M20 concrete and Fe 415 steel.
w.EGiven:
leff= 3000 mm
b = 450 mm
asy
D = 600 mm
P =2000kN En
M20, Fe415 gin
eer
Ends are fixed. lex = ley = l = 3000 mm
Minimum eccentricity
leff D
emin
500 30
In the longer direction
Minimum eccentricities are within the limits and hence code formula for axially loaded short
columns can be used.
w.E
Design of Longitudinal Reinforcement (39.3-71)
asy
Pu = 0.4 fck Ac + 0.67 fy Asc
or
En
Pu = 0.4 fck Ac + (0.67 fy - 0.4fck) Asc
gin
3000 X 103 = 0.4 × 20 × (450 × 600) + (0.67 × 415–0.4 × 20)Asc
ASC=3111mm 2
eer
ing
In view of the column dimensions (450 mm, 600 mm), it is necessary to place intermediate bars,
p = (100×3220) / (450×600)
ww
w.E
asy
En
gin
eer
ing
.ne
t
w.E
Factored load 2500 kN
Factored moment 200 kN.m
asy
Use M20 concrete and Fe 415 steel.
Arrangement of reinforcement
(a) On two sides En
( b) On four sides gin
eer
d 1 Assume 50mm ing
d1
50
0.11 .ne
D 450
Chart for
d1
0.15
t
D
Non Dimensional Parameters:
Pu 2500 103
0.494
f ck bD 25 450 450
Mu 200 106
0.088
f ck bD 2 25 450 4502
Percentage of reinforcement
ww Referring Chart 45
P
w.E f ck
0.10
P 0.10 25 2.5 %
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
En
gin
eer
ing
.ne
t
Determine the reinforcement to be provided in a circular column with the following data:
ww
Characteristic strength 250 N/mm2
Factored load 1600 kN
w.E
Lateral reinforcement:
(a)Hoop reinforcement
(b) Helical reinforcement
asy
(Assume moment due to minimum eccentricity to be less than the actual moment).
En
Assuming 25 mm bars with 40 mm cover,
d1 = 40 + 12.5 = 52.5 mm
d1/D - 52.5/50 = 0.105 gin
Charts for d'/D = 0.10 will be used.
Let b=D eer
(a) Column with hoop reinforcement ing
1600103
.ne
Pu
f ck D 2 20 500 2
0.32
t
Mu 125 10 6
0.05
f ck D 3 20 500 3
1.74 500 2
As 3416 mm 2
100 4
According to 38.4 of the Code, the strength of a compression member with helical
reinforcement is 1.05 times the strength of a similar member with lateral ties. Therefore,
the, given load and moment should be divided by 1.05 before referring to the chart.
Pu 1600103
0.31
f ck D 2 1.05 20 500 2
Mu 125 10 6
0.048
f ck D 3 1.05 20 5003
ww
Hence, From Chart 52, for fy = 250 N/mm2,
P
0.078
w.E f ck
p = 0.078 x 20 = 1.56 %
asy 1.56 500 2
En
As
100
4
3063 mm 2
gin
eer
According to 38.4.1 of the Code the ratio of the volume of helical reinforcement to the
volume of the core shall not be less than
Ag
0.36
f
1 ck
ing
Ac fy
.ne
t
where Ag is the gross area of the section and Ac is the area of the core measured to the
outside diameter of the helix. Assuming 8 mm dia bars for the helix
Ag 500
1.315
Ac 436
Ag f 500 20
0.36 1 ck = 0.36 1 0.0091
Ac fy 436 250
Ash 428 / / 4 436 2 s h
Ash
0.9
Sh
where, Ash is the area of the bar forming the helix and sh is the pitch of the helix. In
order to satisfy the coda1 requirement,
ww
Thus provide 48 mm pitch
w.E
asy
En
gin
eer
ing
.ne
t
Problem:
A 4 m high column is effectively held in position at both ends and restrained against rotation at
one end. Its diameter is restricted to 40 cm. Calculate the reinforcement if it is required to carry
ww
a factored axial load of 1500 kN Use M20 mix and Fe 415 grade steel.
w.E
Solution:
asy
Effective height = 0.80 L = 0.80 x 400 = 320 cm
Slenderness ratio=𝑙𝐷=32040=8<12
En
Hence, it is a short column. 𝑒𝑚𝑖𝑛=𝑙500+𝐷30=320500 +4030
𝐴𝑠𝑐=1830 𝑚𝑚2 ,
Pitch p ≤400 𝑚𝑚
≤ 300 mm
ww
w.E
asy
En
gin
eer
ing
.ne
t
Slender Columns
ww
Columns having both lex/D and ley/b less than twelve are designated as short and
otherwise, they are slender, where lex and ley are the effective lengths with respect to
w.E
major and minor axes, respectively; and D and b are the depth and width of rectangular
columns, respectively.
asy
Design of Slender Columns En
gin
The design of slender compression members shall be based on the forces and the
eer
moments determined from an analysis of the structure, including the effect of deflections
ing
on moments and forces. When the effect of deflections are not taken into account in the
.ne
analysis, additional moment given in cl no 39.7.1 of IS 456:2000 shall be taken into
account in the appropriate direction.
t
The additional moments M, and My, shall be calculated by the following formulae:
Solution 1:
Step 1: Checking of slenderness ratios
lex/D = 7000/450 = 15.56 > 12,
w.E
Step 2: Minimum eccentricities and moments due to minimum eccentricities
asy
ex min = l/500 + D/30 = 8000/500 + 450/30 = 31.0 > 20 mm
ey min = l/500 + b/30 = 8000/500 + 350/30 = 27.67 > 20 mm
En
Mox (Min. ecc.) = Pu(ex min) = (1700) (31) (10-3) = 52.7 kNm
gin
Moy (Min. ecc.) = Pu(ey min) = (1700) (27.67) (10-3) = 47.04 kNm
Mox = 0.6M2 – 0.4M1 = 0.6(70) – 0.4(30) = 30 kNm, which should be ≥ 0.4 M2 (= 28 kNm). Hence, o.k.
Moy = 0.6M2 – 0.4M1 = 0.6(60) – 0.4(30) = 24 kNm, which should be ≥ 0.4 M2 (= 24 kNm). Hence, o.k.
Primary eccentricities:
ex = Mox/Pu = (30/1700) (103) = 17.65 mm
ey = Moy/Pu = (24/1700) (103) = 14.12 mm
ww
Mux = Mox + (Modification factor) (Max) = 52.7 + (0.55) (92.548)
= 52.7 + 50.9 = 103.6 kNm
w.E
Muy = Moy + (Modification factor) (May) = 47.04 + (0.55) (87.43)
= 47.04 + 48.09 = 95.13 kNm
ww
p/f ck
w.E
k1 = 0.19952 and k 2 = 0.243 (interpolated for d/ D = 0.134) for Pbx
asy
which gives Pbx= 0.216044(30)(350)(450)(10-3) = 1020.81 kN.
En
Similarly, for Pby : d/ D= 0.173, p/fck= 0.068. From Table 60 of SP-16, k1= 0.19048 and k2
gin
= 0.1225 (interpolated for d/ b= 0.173). This gives Pby/fckbD = 0.19048 + 0.1225(0.068) = 0.19881,
.ne
t
Step 9: Determination of Puz
or
kax = (3084.71 – 1700)/(3084.71 – 1020.81) = 0.671 and
or
kay = (3084.71 – 1700)/(3084.71 – 939.39) = 0.645
The two uniaxial moment capacities M ux1 and Muy1 are determined as stated: (i) For M ux1 , by
interpolating the values obtained from Charts 44 and 45, knowing the values of Pu/fckbD =0.3598
ww
(see Step 7),
w.E
p/fck= 0.068 (see Step 7), d’/ D= 0.134 (see Step 7), (ii) for Muy1, by interpolating the values
obtained from Charts 45 and 46, knowing the same values of Pu/fckbD and p/fck as those of (i)
asy
and d’/ D= 0.173 (see Step 7). The results are given below:
(i) Mux1/fckbD2 = 0.0882 (interpolated between 0.095 and 0.085)
En
(ii) Muy1/fckbb2= 0.0827 (interpolated between 0.085 and 0.08)
So, we have, Mux1= 187.54 kNm and Muy1= 136.76 kNm. gin
eer
Step 13: Value of n ing
We have Pu /Puz
.ne
= 1700/3084.71 = 0.5511.
We have n = 0.67 + 1.67 (Pu/Puz) = 1.59. t
Step 14: Checking of column for safety
ww
w.E
UNIT 5a syE
ngi
nee
rin
g.n
et
A foundation is a integral part of the structure which transfer the load of the superstructure to the soil.
A foundation is that member which provides support for the structure and it's loads.It includes the soil
and rock of earth's crust and any special part of structure that serves to transmit the load into the rock
or soil.
ww
w.E
asy
En
gin
eer
ing
.ne
t
Spread Footing
ww
w.E
asy
En
Strap Footing
gin
It consists of two isolated footings connected with a structural strap or a lever. The strap connects the
eer
footing such that they behave as one unit. The strap simply acts as a connecting beam. A strap footing
is more economical than a combined footing when the allowable soil pressure is relatively high and
distance between the columns is large.
ing
.ne
t
Combined Footing
It is used when the two columns are so close to each other that their individual footings would overlap.
A combined footing is also provided when the property line is so close to one column that a spread
footing would be eccentrically loaded when kept entirely within the property line. By combining it with
that of an interior column, the load is evenly distributed. A combine footing may be rectangular or
trapezoidal in plan. Trapezoidal footing is provided when the load on one of the columns is larger than
the other column.
ww
w.E
asy
En
gin
Strip/continuous footings
eer
ing
A strip footing is another type of spread footing which is provided for a load bearing wall. A
strip footing can also be provided for a row of columns which are so closely spaced that their spread
.ne
footings overlap or nearly touch each other. In such a cases, it is more economical to provide a strip
footing than to provide a number of spread footings in one line. A strip footing is also known as
“continuous footing”
t
Deep Foundations
The shallow foundations are used in case of small buildings or structures, which carry lesser
loads, and hence the loads are dissipated into the soil mass at much lower depth. However when we are
considering large structures, which carry heavy loads, the loads are dissipated at greater depths where
usually the soil bearing capacity is quite high. One guideline of differentiating between the shallow and
deep foundations is that in case of the deep foundations the depth of foundations is more than the
dimension of the structure (usually the width is considered as the dimension).
• Deep footings.
• Piles.
• Piers.
•
ww Caissons /Well foundations.
•
•
w.E
Huge vertical load with respect to soil capacity.
Very weak soil or problematic soil.
•
• asy
Huge lateral loads eg. Tower, chimneys.
Scour depth criteria.
•
•
En
For fills having very large depth.
Uplift situations (expansive zones)
•
gin
Urban areas for future large and huge construction near the existing building.
eer
CLASSIFICATION OF PILES
1. Based on material
• Timber piles
• Steel piles
• Concrete piles ing
• Composite piles (steel + concrete)
2. Based on method of installation .ne
• Driven piles (i) precast (ii) cast-in-situ.
• Bored piles.
3. Based on the degree of disturbance
• Large displacement piles (occurs for driven piles)
t
• Small displacement piles (occurs for bored piles)
3
ww Cost
of foundation is less than
the footing with.
A shallow foundation is Deep foundations are
4
w.E Feasibility
cheaper.
ing
needed, construction lateral support and resists
procedure is simple at an uplift, effective when
affordable cost, etc. foundation at shallow depth
.ne
is not possible, can carry a
huge load, etc.
7 Disadvantages Possibility of a settlement,
usually applicable for
lightweight structure, weak
against lateral loads, etc.
t
More expensive, needs
skilled labors, complex
construction procedures, can
be time-consuming and
some types of deep
foundations are not very
flexible, etc.
8 Types Isolated foundation, strip Pier foundation, pile
foundation, mat foundation, foundation, caissons etc.
combined foundation, etc.
1. Foundation structures should be able to sustain the applied loads, moments, forces and
induced reactions without exceeding the safe bearing capacity of the soil.
2. The settlement of the structure should be as uniform as possible and it should be within the
tolerable limits. It is well known from the structural analysis that differential settlement of
supports causes additional moments in statically indeterminate structures. Therefore, avoiding
the differential settlement is considered as more important than maintaining uniform overall
settlement of the structure.
In addition to the two major requirements mentioned above, the foundation structure should
provide adequate safety for maintaining the stability of structure due to either overturning
ww
and/or sliding It is to be noted that this part of the structure is constructed at the first stage
before other components (columns / beams etc.) are taken up. So, in a project, foundation
w.E
design and details are completed before designs of other components are undertaken.
However, it is worth mentioning that the design of foundation structures is somewhat different
asy
from the design of other elements of superstructure due to the reasons given below. Therefore,
foundation structures need special attention of the designers.
En
1. Foundation structures undergo soil-structure interaction. Therefore, the behaviour of
foundation structures depends on the properties of structural materials and soil. Determination
gin
of properties of soil of different types itself is a specialized topic of geotechnical engineering.
Understanding the interacting behaviour is also difficult. Hence, the different assumptions and
eer
simplifications adopted for the design need scrutiny. In fact, for the design of foundations of
ing
important structures and for difficult soil conditions, geotechnical experts should be consulted
for the proper soil investigation to determine the properties of soil, strata wise and its
settlement criteria.
.ne
2. Accurate estimations of all types of loads, moments and forces are needed for the present as
The two different types are explained below: (A) Shallow foundations Shallow
foundations are used when the soil has sufficient strength within a short depth
below the ground level. They need sufficient plan area to transfer the heavy loads to
the base soil. These heavy loads are sustained by the reinforced concrete columns or
walls (either of bricks or reinforced concrete) of much less areas of cross-section
due to high strength of bricks or reinforced concrete when compared to that of soil.
ww
Isolated footings
w.E
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
Figure: Stepped and rectangular footing
Source:https://nptel.ac.in/content/storage2/courses/105105104/pdf/m11l29.pdf
En
Combined footings
gin
eer
ing
.ne
t
combined footing
Source:https://nptel.ac.in/content/storage2/courses/105105104/pdf/m11l29.pdf
Design of axially and eccentrically loaded Square, Rectangular pad and sloped footings
Design of Isolated Column Footing
1 Area of footing
2 Thickness of footing
4
ww Reinforcement details of footing (satisfying moment and shear considerations)
asy
steel. The method of design is similar to the design of beams and slabs. Since footings are
buried, deflection control is not important. However, crack widths should be less than 0.3 mm.
En
gin
The steps followed in the design of footings are generally iterative. The important steps in the
design of footings are;
loads)
Check the adequacy of the assumed thickness
Find the reinforcement details
t
Check for development length
Check for bearing stresses
Limit state of collapse is adopted in the design pf isolated column footings. The various design
steps considered are;
Design for shear (one way shear and two way shear)
The materials used in RC footings are concrete and steel. The minimum grade of concrete to be
used for footings is M20, which can be increased when the footings are placed in aggressive
environment, or to resist higher stresses.
Cover: The minimum thickness of cover to main reinforcement shall not be less than 50 mm
for surfaces in contact with earth face and not less than 40 mm for external exposed face.
However, where the concrete is in direct contact with the soil the cover should be 75 mm. In
case of raft foundation the cover for reinforcement shall not be less than 75 mm.
Minimum reinforcement and bar diameter: The minimum reinforcement according to slab and
beam elements as appropriate should be followed, unless otherwise specified. The diameter of
main reinforcing bars shall not be less 10 mm. The grade of steel used is either Fe 415 or Fe
500.
ww
Problem
w.E
Design an isolated footing of uniform thickness for RCC bearing a vertical load 600
KN and having a box of size 500mm x 500mm. The Safe Bearing Capacity of soil is
asy
take is 120 𝑲𝑵⁄𝒎𝟐 , M20 , Fe415.
Step 1:
En
Size of column =
gin
500 x 500 mm
Weight of column ‘w’ =
S.B.C =
600 KN
120 𝐾𝑁⁄𝑚2 eer
fy = 415 𝐾𝑁⁄𝑚𝑚2 ing
fck = 20 𝑁⁄𝑚𝑚2
.ne
Step 2:
Size of footing
t
W = 600 KN
Self weight of footing = 10% of column load
600 ×10
=
100
= 60 KN
Total load = 600 + 60
= 660 KN
𝐿𝑜𝑎𝑑
Area of footing =
𝑆𝐵𝐶
= 5.5𝑚2
Area of Square = 𝑎2 = 5.5
⇒ 𝑎 = √5.5
= 2.35m
Size of Footing = (2.35 x 2.35) m
Step 3:
w.E po =
=
𝑊𝑖𝑑𝑡ℎ (𝐴𝑟𝑒𝑎 𝑜𝑓 𝑓𝑜𝑜𝑡𝑖𝑛𝑔)
600
asy=
5.5
109.01 𝐾𝑁⁄𝑚2
Step 4: En
a) Depth on basis of Bending Compression
gin
M =
PO
8
(B – b) (B - b/4 ) eer
=
109.01
8 ing
[(2.35 – 0.5) (2.35 – 0.5⁄4 )]
M = 56.08 KNm
.ne
Factored Moment
Mu
=
=
1.5 x 56.08
84.12 KNm
t
0.36 𝑥𝑢 𝑚𝑎𝑥 0.42 𝑥𝑢 𝑚𝑎𝑥
Mu lim = fck [1 - ] 𝑏𝑑 2
𝑑 𝑑
D = 175mm
w.E
Critical section lies ‘d’ distance from the face of the unit,
𝐵 𝑏
𝑎
asy=
2
2350
−
2
−
500
𝑎 En
=
2
425 𝑚𝑚2
2
Vu
=
= 1.5 Po a gin
= 1.5 x 109.01 x 0.925 eer
Vu = 151.36 𝑁⁄𝑚2
ing
𝜏v =
Vu
𝑏𝑑
.ne
0.475
d
=
=
355.44
2350 ×𝑑
318.7mm ≅ 320mm
t
c) Depth on basis of two way shear,
𝑑 𝑑
b0 = + +b
2 2
d = 320mm
b0 = 820mm
Shear force, F = Po [ 𝐵2 − 𝑏0 2 ]
= 110 [2.352 − 0.8202 ]
F = 532.61 KN≅ 530 𝐾𝑁
Fu = 1.5 x 530
= 795 KN
Shear stress
Fu
𝜏v =
4 ×𝑏0 ×𝑑
795 × 103
=
4 ×820 ×320
𝜏v = 0.757 𝑁⁄𝑚𝑚2
Permissible shear stress
𝜏v ≤ ks𝜏𝑐
ks = 0.5 + Bc
ww Bc =
𝑠ℎ𝑜𝑡𝑒𝑟 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛
𝐿𝑜𝑛𝑔𝑒𝑟 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛
w.E =
500
500
=1
ks
asy= 0.5 + 1
ks
Take, ks En
=
=
1.5
1
𝜏𝑐 = 0.25 √𝑓𝑐𝑘 gin
= 0.25√20 eer
𝜏𝑐 = 1.118 𝑁⁄𝑚𝑚2
ing
.ne
k s x 𝜏𝑐 =
=
1 x 1.118
1.118 𝑁⁄𝑚𝑚2 t
𝜏v < ks𝜏𝑐
Hence Safe
Step 4: Design of Reinforcement
𝑓𝑦 𝐴𝑠𝑡
Mu = 0.87 fy Ast d [1− ]
𝑏𝑑 𝑓𝑐𝑘
415 × 𝐴𝑠𝑡
84.195 x 106 = 0.87 x 415 x Ast x 320 [1− ]
20 ×320 ×2350
Step 5:
Check for development length
i. Ld = 47 x ∅
= 47 x 12
= 564 mm
ii. Length of bar, Lo = 1⁄ (B−𝑏) − dc
2
= 1⁄ (2350 – 500 ) − 60
2
= 865 mm
∵ Lo >Ld
w.E
Step 6:
Transfer of load at column base
asy 2
1
=
𝑏′
385
En 𝑏 ′ = 770mm
A1 =
5002
gin
(500 + 770 + 770)2 = 20402
A2 =
=√
20402
5002
= 4.08
.ne
Adopt value of 1 𝐴
√𝐴 = 2
2
t
𝐴1
Permissible bearing pressure = 0.45 fck√
𝐴2
= 0.45 x 20 x 2
= 18 N/mm2
Step 7:
Actual bearing pressure
𝐿𝑜𝑎𝑑 600 × 103
A.B.P = =
𝐴𝑟𝑒𝑎 500 ×500
= 2.8 N/mm2
Check :
Actual bearing pressure & permissible bearing pressure
2.4 < 18
Hence safe
Reinforcement Details
ww
w.E
asy
En
gin
eer
ing
.ne
t
Problem
Design a footing for 250mm thick has masonry wall with supports to carry a design
load of 200kn/m at service state. Consider unit weight of soil 20KN/𝒎𝟑 . Angle of
repose = 30°. Allowable bearing capacity 150KN/𝒎𝟐 , M20, Fe415 .
Given Data:
150𝐾𝑁⁄𝑚2
ww q0
𝛾
=
= 20 KN/𝑚3
w.E B = 250mm
pu
∅
=
= asy
200 KNm
30°
fck =
En
20 N/𝑚𝑚2
fy = 415 N/𝑚𝑚2
gin
Step 2:
Determination of depth of foundation eer
h =
𝑞0
x [ 1 − 𝑠𝑖𝑛∅⁄1 + 𝑠𝑖𝑛∅ ]2 ing
=
𝛾
150
x [ 1 − 𝑠𝑖𝑛30⁄1 + 𝑠𝑖𝑛30 ]2 .ne
=
20
0.83 ≅ 1m t
Step 3:
Find width of footing
𝐿𝑜𝑎𝑑
B =
𝑆.𝐵.𝐶
200
= = 1.35 m
150
Step 4:
Find total load
Self weight of footing = (L × B × D) 𝛾
= (1 × 1.35 × 1) 25
= 33.75 ≅ 34
Total Load = pu + self weight
= 200 + 34
= 234 𝐾𝑁⁄𝑚2
Step 5:
Actual width of footing
234
Actual width = = 1.56≅ 1.6 m
150
Step 6:
Net upward pressure
ww Po =
𝐿𝑜𝑎𝑑(𝑔𝑖𝑣𝑒𝑛)
𝑊𝑖𝑑𝑡ℎ ×1(𝑚 𝑔𝑖𝑣𝑒𝑛)
w.E =
200
1.6
= 125𝐾𝑁⁄𝑚2 /𝑚 𝑙𝑒𝑛𝑔𝑡ℎ
Step 7:
asy
a) Depth of Basis of Bending Compression
M = En
𝑃𝑂
x (B – b) x (B - )
𝑏
8
125 gin 4
M
=
=
8
= 192.78 mm
D = 200 mm
b) Depth on basis of one way shear
Assume, pt = 0.3%
𝜏v = 𝜏c x K
𝜏c ref IS456 Pg No: 73 0.25 → 0.36
0.50 → 0.48
𝜏c = 0.38
Permissible shear stress, 𝜏v = 0.38 K
ww K ref IS 456 Pg No : 73
K = 1.20
w.E 𝜏v
𝜏v
= 0.38 x 1.20
=
asy0.456
c)Critical section lies ‘d’ distances from face of wall
Vu =
En
1.5 Po a
a =
𝐵
2
-
𝑏
2 gin
=
1.35
2
-
250
2 eer
a = 675 mm
ing
a = 0.675 m
.ne
Vu =
=
1.5 x Po x a
1.5 x 125 x 0.675 = 126.56 𝑁⁄𝑚2
𝑉𝑢
t
𝜏v =
𝑏𝑑
126.56 × 103
0.456 =
1000 ×𝑑
Ast = 519.83
Provide 12mm ∅ at 200mm C/C.
Distribution Reinforcement
0.12
= x 1000 x 250
100
= 300mm
ww
w.E
asy
En
gin
eer
ing
.ne
t
ww d
w
=
=
600 mm
600 KN
60 KN .ne
Total load =
=
600 + 60
660 KN
t
𝐿𝑜𝑎𝑑
Area of footing =
𝑆.𝐵𝐶
660
120
= 5.5 m2
A = 5.5
BxL= A = 5.5 m2
2
B = L
3
2
xLxL = 5.5
3
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
L = 2.87 m ≅ 3m
B = 1.91 m ≅ 2m
B = 2m , L = 3m
Step 3: Section Design
a) Depth on basis of Bending compression
𝐺𝑖𝑣𝑒𝑛 𝑙𝑜𝑎𝑑
Net upward pressure Po =
𝐴𝑟𝑒𝑎 𝑜𝑓 𝑓𝑜𝑜𝑡𝑖𝑛𝑔
600
=
3×2
= 100 KN/m2
Mx = Po x B x 1.2 x
1.22
asy
Mx = 172.8
Mux
En = 1.5 x M = 259.2
Along y−y axis
gin 0.82
My = Po x L x 0.8 x
2
0.82
eer
= 100 x 3 x 0.8 x
2
ing
Muy
=
=
76.8
115.2 .ne
Mu lim
Mu lim
=
=
Take greater one
259.2 ≅ 260 KNm
t
b) Depth from Mulim
𝑀𝑢 𝑚𝑎𝑥 0.42 𝑥𝑢 𝑚𝑎𝑥
Mu lim = 0.36 fck (1− ) bd2
𝑑 𝑑
D = d + 𝑑′
= 220 + 60
= 280 mm
ww 𝜏v
𝜏v
=
𝑏𝑑
360−300d
⇢ ①
w.E Assume, Pt
=
= 0.3%
2𝑑
asy
( 𝜏c ref IS 456 Pg No: 73) 0.25 → 0.36
En 0.50 → 0.48
𝜏c =
Permissible shear stress, 𝜏v
0.38 N/mm2
=gin 𝜏c x K
eer
K = 1.05
D=280mm ⇢ (IS 456 Pg: 72)
ing
.ne
275 → 1.05
300 → 1.00
𝜏v = K x 𝜏c t
= 0.38 x 1.05
= 0.4 N/mm2
𝜏𝑣 = 400 KN/m2 ⇢ ②
Eqn ①&②
360−300𝑑
= 400
2𝑑
360−300d = 800d
360 = 1100d
d = 0.327 m
d = 3.27 ≅ 330 mm
D = 390 mm
Depth on basis of 2 way shear
Area of footing, AF = 6m2 (3 x 2)
𝑑 𝑑
BC = B+ +
2 2
330 330
= 400 + +
2 2
BC = 730mm
330 330
AB = 600 + +
2 2
AB = 930mm
ww Area = BC x AB
w.E =
=
730 x 930
678900 mm2
Shear force asy= Po [AF – Area of ABCD]
En
= 100[6 – 678900 x (10-3)2]
= 532.11 KN
gin
Fu =
=
1.5 x 532.11
798.17 KN eer
ing
Length of ABCD = (930 x 2) + (730 x 2)
.ne
𝜏𝑣
=
=
3320 mm
𝐹𝑢
𝐿𝑒𝑛𝑔𝑡ℎ 𝑜𝑓 𝐴𝐵𝐶𝐷 ×𝑑
t
798.17 × 106
= = 0.73 N/mm2
3320 × 330
Permissible stress = k s x 𝜏𝑐
ks = 0.5 + 𝛽𝑐
𝑆ℎ𝑜𝑟𝑡 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛
𝛽𝑐 =
𝐿𝑜𝑛𝑔 𝑠𝑖𝑑𝑒 𝑜𝑓 𝑐𝑜𝑙𝑢𝑚𝑛
400
= = 0.667
600
ks = 0.5 + 0.667
= 1.167
ww
Find Astx :
𝑓𝑦 𝐴𝑠𝑡𝑥
w.E Mux =
260 x 106 =
0.87 fy Astx d [1−
𝑏𝑑 𝑓𝑐𝑘
asy
Astx = 2356.82 mm2
20 ×2000 ×330
En
12mm Ø bar @ 50mm in x- direction C/C spacing.
Muy = gin
0.87 fy Asty d [1−
𝑓𝑦 𝐴𝑠𝑡𝑦
𝑏𝑑 𝑓𝑐𝑘
]
= 47 x 12 = 564 mm
Lo = 1⁄ × (B – b) − dc
2
= 1⁄ × (2000 – 400) – 60
2
= 740mm
A1 = 2160 x 1960
A2 = 600 x 400
A 2160 ×1960
√𝐴 1 = √
600 ×400
2
= 4.2
A1
ww
Adopt values,√
𝐴2
= 2
w.E
Permissible bearing stress = 0.45 fck√
A1
𝐴2
asy = 0.45 x 20 x 2
En = 18 N/mm2
600 × 103
eer
=
600 ×400
ing
= 2.5 N/mm2
.ne
Actual bearing pressure
2.5
<
<
t
Permissible bearing stress
18 N/mm2
Hence safe.
Reinforcement details
ww
w.E [Source:R.C.C Designs by Dr.B.C.Punmia,page 1091]
asy
En
gin
eer
ing
.ne
t
Whenever two or more columns in a straight line are carried on a single spread footing, it
is called a combined footing. Isolated footings for each column are generally the economical.
Combined footings are provided only when it is absolutely necessary, as
1.When two columns are close together, causing overlap of adjacent isolated footings
2.Where soil bearing capacity is low, causing overlap of adjacent isolated footings
3. Proximity of building line or existing building or sewer, adjacent to a building column.
Problem
ww
Two interior columns A and B carry 700 kN and 1000 kN loads respectively. Column A
is 350 mm x 350 mm and column B is 400 mm X 400 mm in section. The centre to centre
w.E
spacing between columns is 4.6 m. The soil on which the footing rests is capable of
providing resistance of 130 kN/m2. Design a combined footing by providing a central
asy
beam joining the two columns. Use concrete grade M25 and mild steel reinforcement.
Solution: Data
En
fck = 25 N/mm2,
fy= 250 N/mm2, gin
fb = l30 kN/m2 (SBC),
eer
Column A = 350 mm x 350 mm,
Column B = 400 mm x 400 mm,
ing
.ne
c/c spacing of columns = 4.6 m, PA = 700 kN and PB = 1000 kN
Ultimate loads
P = 1.5 x 700 = 1050 kN,
ua
t
P = 1.5 x 1000 = 1500 kN
ub
For uniform pressure distribution the C.G. of the footing should coincide with the C.G. of
column loads. Let x be the distance of C.G. from the centre line of column A
Then x = (PB x 4.6)/(PA + PB) = (1000 x 4.6)/(1000 +700)
= 2.7 m from column A.
If the cantilever projection of footing beyond column A is ‘a’
then, a + 2.7 = Lf /2 = 7.2/2, Therefore a = 0.9 m
asy
En
gin
eer
ing
.ne
t
Total ultimate load from columns = Pu= 1.5(700 + 1000) = 2550 kN.
Upward intensity of soil pressure wu= P/Af= 2550/14.4 = 177 kN/m2
Design of slab
ww
w.E
asy
En
gin
For M25 and Fe 250, Q u max = 3.71 N/mm2 eer
Required effective depth = √ (60.2 x 10 /(3.71 x 1000)) = 128 mm
6
ing
.ne
Since the slab is in contact with the soil clear cover of 50 mm is assumed.
Using 20 mm diameter bars
Required total depth = 128 + 20/2 + 50 =188 mm say 200 mm
Provided effective depth = d = 200-50-20/2 = 140 mm
t
Check the depth for one - way
shear considerations- At ‘d’ from face
Design shear force=Vu=177x(0.825-0.140)=121kN
Nominal shear stress=τv=Vu/bd=121000/(1000x140) =0.866MPa
Permissible shear stress
Pt = 100 x 2415 /(1000 x 140 ) = 1.7 %, τuc = 0.772 N/mm2
Value of k for 200 mm thick slab =1.2
Permissible shear stress = 1.2 x 0.772 = 0.926 N/mm2
Download From: www.EasyEngineering.net
CE8501 DESIGN OF REINFORCED CEMENT CONCRETE ELEMENTS
Download From: www.EasyEngineering.net
Rohini College of Engineering & Technology
Transverse reinforcement
ww
Required Ast=0.15bD/100
=0.15x1000 x 200/100 = 300mm2
w.E
Using Ф8 mm bars, Spacing=1000x50/300
= 160 mm
asy
Provide distribution steel of Ф8 mm at 160 mm c/c,<300, <5d
En
Design of Longitudinal Beam
gin
Load from the slab will be transferred to the beam.
eer
ing
As the width of the footing is 2 m, the net upward soil pressure per meter length of the beam
= wu = 177 x 2 = 354 kN/m
Shear Force and Bending Moment .ne
VAC= 354 x 0.9 =318.6 kN, VAB = 1050-318.6 =731.4 kN
VBD= 354 x 1.7 = 601.8kN, VBA = 1500-601.8 = 898.2 kN
t
Point of zero shear from left end C
X1 = 1050/354 = 2.97m from C or
X2 = 7.2-2.97 = 4.23 m from D
Maximum B.M. occurs at a distance of 4.23 m from D
MuE = 354 x 4.232 / 2 - 1500 (4.23 - 1.7) = -628 kN.m
Bending moment under column A= MuA=354x0.92 /2 = 143.37 kN.m
Bending moment under column B = MuB = 354 x 1.72 = 511.5 kN-m
Let the point of contra flexure be at a distance x from the centre of column A
Then, Mx= I050x - 354 (x + 0.9 )2/ 2 = 0
w.E
Effective depth provided = d= 750-70 = 680 mm
(Less than 750mm and hence no side face steel is needed
asy
En
gin
eer
ing
.ne
t
In this case b=D=400 mm, db=680 mm, ds=140 mm
Area resisting two - way shear
= 2(b x db + ds x d s) + 2 (D + d b)ds
= 2 (400 x 680+ 140 x 140) + 2(400+680) 140= 885600 mm2
Design shear=Pud= column load – W u x area at critical section
= 1500 - 177 x(b + ds) x (D + db)
=1500-177 x (0.400+0.140) x (0.400+ 0.680) =1377.65kN
τv=Pud/bod
= 1377.65x1000/885600=1.56 MPa
Shear stress resisted by concrete = τuc = τuc x K s
where, τuc = 0.25 √ f ck= 0.25√ 25 = 1.25 N/mm2
K s = 0.5 + d / D = 0.5 + 400/400 = 1.5 ≤ 1 Hence K s = 1
w.E
Therefore Unsafe
asy
En
gin
eer
ing
.ne
t
ww
w.E
asy
E ngi
nee
rin
g.n
et