s71500 and PROFACE

The document discusses a user's experience connecting a Siemens S7-1500 PLC with a ProFace panel, specifically addressing issues with tag selection and communication errors. The user initially faced an 'Out of range devices' error but later resolved the issue by selecting 'Optimized Block Access' and ensuring correct tag names without 'Struct' data types. The conversation includes suggestions from other users regarding settings and configurations for successful communication between the devices.

Uploaded by

mapleleaves2222
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views2 pages

s71500 and PROFACE

The document discusses a user's experience connecting a Siemens S7-1500 PLC with a ProFace panel, specifically addressing issues with tag selection and communication errors. The user initially faced an 'Out of range devices' error but later resolved the issue by selecting 'Optimized Block Access' and ensuring correct tag names without 'Struct' data types. The conversation includes suggestions from other users regarding settings and configurations for successful communication between the devices.

Uploaded by

mapleleaves2222
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ProFace WinGP and S7-1500

Created by: mattsalz at: 2/15/2017 11:08 AM (3 Replies)


Rating (0)
Thanks 0

Actions New post

4 Entries

2/15/2017 11:08 AM Rate (0)


mattsalz Hello,

I want to connect a S7-1500 with a ProFace panel. I can import and select tags
from my Datablock (Gobal DB with "32 single Bits") but after loading to the panel,
this message appears:

"RHAA052:PLC1:Out of range devices exist in write devices (Adress:PLC1)"


The description on ProFace Website was not really helpfull. I've already checked
the tag names (PF doesn't accept --> .,!"$%^&*()-+=#/ \......). I'm not sure if I may
Advanced Member
use "Optimized block access" (support doesn't really know).

Hardware:
Joined: 7/28/2015
PLC: CPU 1516F-3 PN/DP (6ES7 516-3FN00-0AB0), Firmware V1.8
Last visit: 4/18/2019
HMI: Pro-Face PS5000 (PFXPPD5900WP)
Posts: 4
Rating: Software

(0) PLC: TIA V13 SP1 Update 9

HMI: Runtime WinGP 4.6.20, TIA Portal Ethernet Driver V1.10.00

Does anybody have experience with this setup?

Best regards

Suggestion To thank Answer Quote

2/16/2017 10:11 AM Rate (0)


stso Hi

I don't know the ProFace panel in details, but 2 things come to my mind

1. Switch off " Optimized Access" for your DB

2. Some panels use "Put and Get" to communicate with the PLC, enable "Put and
Get" in the HW Properties
Bronze Member

Joined: 10/4/2007
Last visit: 4/26/2018
Posts: 18
Rating:

(11)
Last edited by: stso at: 2/16/2017 10:11:39 AM

Suggestion To thank Answer Quote

2/16/2017 2:44 PM Rate (0)


2/16/2017 2:44 PM Rate (0)
mattsalz
stso

1. Switch off " Optimized Access" for your DB


2. Some panels use "Put and Get" to communicate with the PLC, enable
"Put and Get" in the HW Properties

I've tried, but it has no influence. I think that's for the "Simatic S7 Ethernet Driver".
Advanced Member I'm using the "TIA Portal Ethernet Driver".

Best Regards

Joined: 7/28/2015
Last visit: 4/18/2019
Posts: 4
Rating:

(0)

Suggestion To thank Answer Quote

3/6/2017 11:15 AM Rate (0)


mattsalz Now it's working. I had to select "Optimized Block Access". It's important to use
correct tag names and no "Struct" data types. After changing datatypes, you have
to copy the project file with "ProjectCopy".

Best regards

Advanced Member

Joined: 7/28/2015
Last visit: 4/18/2019
Posts: 4
Rating:

(0)

Suggestion To thank Answer Quote