ProFace WinGP and S7-1500
Created by: mattsalz at: 2/15/2017 11:08 AM (3 Replies)
Rating (0)
Thanks 0
Actions New post
4 Entries
2/15/2017 11:08 AM Rate (0)
mattsalz Hello,
I want to connect a S7-1500 with a ProFace panel. I can import and select tags
from my Datablock (Gobal DB with "32 single Bits") but after loading to the panel,
this message appears:
"RHAA052:PLC1:Out of range devices exist in write devices (Adress:PLC1)"
The description on ProFace Website was not really helpfull. I've already checked
the tag names (PF doesn't accept --> .,!"$%^&*()-+=#/ \......). I'm not sure if I may
Advanced Member
use "Optimized block access" (support doesn't really know).
Hardware:
Joined: 7/28/2015
PLC: CPU 1516F-3 PN/DP (6ES7 516-3FN00-0AB0), Firmware V1.8
Last visit: 4/18/2019
HMI: Pro-Face PS5000 (PFXPPD5900WP)
Posts: 4
Rating: Software
(0) PLC: TIA V13 SP1 Update 9
HMI: Runtime WinGP 4.6.20, TIA Portal Ethernet Driver V1.10.00
Does anybody have experience with this setup?
Best regards
Suggestion To thank Answer Quote
2/16/2017 10:11 AM Rate (0)
stso Hi
I don't know the ProFace panel in details, but 2 things come to my mind
1. Switch off " Optimized Access" for your DB
2. Some panels use "Put and Get" to communicate with the PLC, enable "Put and
Get" in the HW Properties
Bronze Member
Joined: 10/4/2007
Last visit: 4/26/2018
Posts: 18
Rating:
(11)
Last edited by: stso at: 2/16/2017 10:11:39 AM
Suggestion To thank Answer Quote
2/16/2017 2:44 PM Rate (0)
2/16/2017 2:44 PM Rate (0)
mattsalz
stso
1. Switch off " Optimized Access" for your DB
2. Some panels use "Put and Get" to communicate with the PLC, enable
"Put and Get" in the HW Properties
I've tried, but it has no influence. I think that's for the "Simatic S7 Ethernet Driver".
Advanced Member I'm using the "TIA Portal Ethernet Driver".
Best Regards
Joined: 7/28/2015
Last visit: 4/18/2019
Posts: 4
Rating:
(0)
Suggestion To thank Answer Quote
3/6/2017 11:15 AM Rate (0)
mattsalz Now it's working. I had to select "Optimized Block Access". It's important to use
correct tag names and no "Struct" data types. After changing datatypes, you have
to copy the project file with "ProjectCopy".
Best regards
Advanced Member
Joined: 7/28/2015
Last visit: 4/18/2019
Posts: 4
Rating:
(0)
Suggestion To thank Answer Quote
4 Entries