Column Hand Out
Column Hand Out
Columns are defined as members that carry loads chiefly in compression, even though the bending
action may produce tensile forces over part of their cross section.
On the basis of construction and lateral ties, three types of reinforced concretes compression members
are in use.
On the basis of the slenderness ratio columns may be classified as short or long (slender).
_ For multistory sway frames comprising rectangular sub frames, the following expression may be used
to calculate the slenderness ration of the columns in the same storey
Where; A= the sum of the cross-sectional areas of all the columns of the story.
Ki=the total lateral stiffness of the columns of the story (story rigidity)
With modulus of elasticity taken as unity,
L=the story height.
The effective height (length) of a column is the distance between the two consecutive points of
contra flexure or zero bending moments. The figure shown below may serve this purpose.
L
0.5L 0.7L 1.2L 0.8L
However in accordance with EBCS-2, 1995, the effective length Le for an RC Column is given
as,
a. Non-sway mode
b. Sway mode
Or Conservatively
For the theoretical model shown below.
Lc2 Ic2
Ib22 Ib21
Lc Ic
Ib12 Ib11
Lc1 Ic1
Where K1 and K2 are column stiffness coefficients (EI/L) for the lower and the upper column
respectively. Kc is the stiffness coefficient (EI/L) of the column being designed.
Kij is the effective beam stiffness coefficient (EI/L)
= 1.0 (EI/L) for opposite end elastically or rigidly restrained.
= 0.5 (EI/L) for opposite end free to rotate.
= 0.0 (EI/L) for a cantilever beam.
For the purpose of design calculations, structures or structural members may be classified as braced or
unbraced depending on the provision or not of bracing elements and as sway or non- sway depending on
their sensitivity to second-order effects due to lateral displacements.
In a sway frame, additional internal forces or moments due to the effects of the horizontal displacements
of its nodes shall be taken into account for design. Additional internal forces or moments are neglected
in a non-sway frame since its response to in-plane horizontal forces is sufficiently stiff.
For a non – sway frame
Where: Nsd – the design value of the total vertical load.
Ncr – critical vertical load for failure in a sway mode given as
Ec
I c= Moment of inertia of the concrete sections of the substitute column w.r.to centre
Is = Moment of inertia of reinforcement sections of the conc. section
A frame may be classified as braced if its sway resistance is supplied by a bracing system which is
sufficiently stiff to assume that all horizontal loads are resisted by the bracing system. (Not more than
10% of the horizontal loads are attracted by the frame)
Generally, the slenderness ratio of concrete columns shall not exceed 140.
Second-order effects in compressive members need not be taken into account in the following cases:
(a). For sway frames, the greater of the two
Where M1and M2 are the first-order (calculated) moments at the ends. M 2 being always positive and
greater in magnitude than M1, and M1 being positive if member is bent in single curvature and negative
if bent in double curvature.
15t 300mm
- Min. # of bars
- The diameter of longitudinal bars,
- The minimum lateral dimension of a column shall be at least 150mm and
the minimum diameter of a spiral column is 200mm.
- The Min. cover to reinforcement should never be less than
(a)
(b)
dg – the largest nominal maximum aggregate size.
The frame shown in figure below is composed of members with rectangular cross sections. All members
are constructed of the same strength concrete (E is the same for both beams and columns). Considering
bending in the plane of the frame only, classify column EF as long or short if the frame is (a) braced and
(b) unbraced. All girders are 300 x 600 mm.
600 525 KN
F I
C F M1 = 30 KNm
350
3.80 m 300 x 350
600
B E H
3.80 m 400
300 x 400 E M2 = 45 KNm
A D G
9m 7.5 m
Solution:
Moments of inertia
Girders:
Columns:
Stiffness Coefficients:
Columns:
Joint E:
Joint F:
In Compression, both the longitudinal steel and concrete contribute to the resistance of the
applied axial force. For the design of short columns in pure compression, EBCS-2 limits the
strain in the concrete to 0.002, since generally this is the strain at which the stress in the
concretes is maximum. The capacity to resist compressive force, Pult is approximately equal to:
Short columns usually fail by crushing. Slender column is liable to fail by buckling. The end moments
on a slender column cause it to deflect sideways and thus bring into play an additional moment. The
additional moment causes a further lateral deflection and if the axial load exceeds a critical value, this
deflection and the additional moment become self -propagating until the column buckles.
For Pin ended columns:
Pcr=
A column is classified as short if both Lex/h and Ley/b are:
15 for a braced column
10 for an unbraced column
Example 5.2 The 300x400mm Column shown below is having eight 16mm diameter
bars. Calculate the ultimate capacity to resist compressive and tensile
force if (a) L=5.5m (b) L=7m
Take, fy =460 N/mm2
fck =35N/mm2
Es= 200GPa
The Column with this length and restrain Conditions is a short column.
Ag=300x400= 120000 mm2 (gross area).
As = (8 *162)/4= 1608mm2 (reinforcement area).
Taking c = 1.5
s =1.15
Nsd=
= 2991308 N = 2991.308 kN
Nsd =
(b) For L=7m.
Le=
Ncr =
40mm 220mm 40mm
16
400 mm
300 mm
5.4 Design of Short Members for Axial Force and Uniaxial Bending
General:
A column is subjected to uniaxial bending when the load applied to a column is eccentric about one axis
only. The presence of this form of bending in axially loaded members can reduce the axial load capacity
of the member. It is the combined effect of axial compression and bending at the ultimate limit state that
tends to govern the design.
fc’ Concrete
A A Section A-A
0 0.001 0.002 0.003
Strain
Pod
fc’
fy fy
In practice column loads will have eccentricities at least due to imperfect constructions.
Design Eccentricity
ed = ec + ea + e2
eo1 and eo2 are first order eccentricities at the ends with e o2 being positive and greater in magnitude than
eo1.
ea=additional eccentricity in account of geometric imperfections.
ea=
e2 = Second-order eccentricity.
For non – sway frames, e2=
Where d = the Column dimension in the buckling plane less the cover to the center of the longitudinal
reinforcement.
K2 =
Md = design moment at the critical section including second-order effects.
Mbal = balanced moment capacity of the column.
The sway moments found by a first-order analysis shall be increased by multiplying
them by the moment magnification factor:
Provided
As a loading approaches the ULS, the following valid assumptions are made.
Non elastic redistribution of stresses take place
Plane section before loading remain plane after loading
Failure of concrete is governed by the maximum strain criteria.
h d C
sy A
0.01 s c
0 -0.002
Strain Diagram at ULS
The maximum compressive strain in the concrete is taken to be: 0.0035 in bending (simple or
compound) 0.002 in axial compression.
The maximum tensile strain in the reinforcement is taken to be 0.01.
The strain diagram shall be assumed to pass through one of the three points A,B Or C.
The design stress – strain curve for concrete (fig. a) & steel (fig. b) are as shown below.
fc fs Idealized Diagram
Idealized Diagram
Design Diagram
Design Diagram
Consider the rectangular section when subjected under an axial load Pd with large eccentricity e, as
shown below. For the purpose of stress calculation, the actual non-linear stress distribution shown can
be replaced with equivalent rectangular stress distribution.
Pd Pd Pd
fcd c fcd
e Ns2 s’ Ns2
d’ As’ x Nc a a 0.8x
h e’ Nc
d
d’ As Ns1 s
b Ns1
Cross – section Actual stress Strain Simplified stress
Applying force equilibrium.
Design Criteria
Balanced Condition:
For a given cross-section a design axial force P da acts at one specific eccentricity e’ =eb’ (or e = eb) to
cause failure by simultaneous yielding of tension steel and crushing of concrete. For simplification
purpose symmetrical reinforcement is considered and compressive steel is assumed to be its limiting
stress level.
in which =
Again As = As’ assumed & both steel are stressed to fyd. The two equilibrium equations yield.
Pd = fcd bd
Where
Compression Failure Controls (very small eccentricity):
In this case fs < fyd & it is not known whether the steel furthest from the load is under compression or
tension. This situation makes the solution procedure more complicated. Column interaction diagrams
can be used to simplify the design.
Here ed & eb are design eccentricity & eccentricity for balanced condition respectively.
When Pd = 0
Md = fcd (0.8bx - As’ ) (d – 0.4x) + As’fs’ (d – d’).
in which
and x
- Thus, the trial shall be repeated until the value of Pdn is close enough and Pdn Pd
On the other hand, interaction chart are prepared using dimensional parameters such that
d’
=1.0 h
=0.2 d’
=0.1 b
h is in the direction of the bending moment.
- Families of curves are drawn for fixed ratio [ranges 0.5 to 0.25] each curve
representing a particular mechanical steel ratio.
- The cover to reinforcement should not be too large [problem of spalling – concrete
cover falling off ] & also not too small to prevent corrosion /fire. Usually for column,
cover 25mm.
In using the chart for design the following procedure can be used .
Given Pd and ed such that Md = Pded.
Assume a cross – section, d’ and evaluate
- Find and
- If the coordinates (, ) lies with in the families of the curve, the assumed cross-
section is feasible, which otherwise need to choose new large section.
- The coordinate (,) gives the value of .
Example 5.4
Design a column to sustain a design axial load of 1100KN & design bending moment of 160KNm,
which includes all other effects, assume concrete C-30, steel S- 400 class I work. Approximate b=0.6h.
Example 5.5
Design a column to sustain a design axial load of 550 KN acting with a design bending moment of 200
KNm including all other effects. Use the same materials example 1.4.2.
Circular Columns
Consider the cross – section shown reinforced with 6 longitudinal bars (the No of bars can vary from 6
to 10).
Pd a
Pd a
cu
a' 1 Ns1
a e x e a
2 Ns2
h
3 Ns3
4 Ns4
This approximate formula holds, for e eb & eb for this purpose may be approximated as
eb = (0.2 + 0.9gm’)h.
For practical problems interaction charts are available for use.
Example 5.6
Design a circular column for design axial load of P da=1225 kN & design bending moment of Md=180
KN.m. Use C-30, S-300, class I work.
Consider an RC column section shown when subjected to design axial force p d acting with eccentricities
edx & edy, such that
Pd
e dx Y cu
Asci f cd
e dy sci f sci Nci + Nsci
x ci f ci
Aci
A q B
C Q
edx
edy
R ex
ey
Consider the surface in the region of interest at pt. Q where e dx & edy for the respective
uniaxial eccentricities are approximated using pt. A & B. Let pt. c represent the reciprocal of the
concentric design load capacity.
The pt. Q on the interaction surface is approximated by a point of which generally gives a conservative
estimate of the strength. On this basis the strength may be obtained from
Where,
Pd = design axial force capacity under biaxial bending edy & edx .
Pdx & Pdy = Capacities for uniaxial bending with eccentricities edy & edx respectively.
Pdo = concentric axial force capacity.
B) Bresler’s Method II
i) Assume the cross- Sectional dimensions, area of steel and its distribution.
ii) Compute concentric load Capacity Pdo and
iii) Determine uniaxial moment capacities Mdxo and Mdyo of the section combined with given
axial load Pda with the use of interaction curves for axial load and unixial moment.
iv) Then the adequacy of the column section can be checked either with the interaction equation
or interaction curves. For checking the adequacy of column section with interaction equation,
determine which shall be 1< n <2. Then compute
modified and checked again. For checking the adequacy of section with interaction curves,
the values of Mdx/Mdxo and Mdy/Mdyo are plotted as Px and Py respectively. If the plot is within
the interaction curve for then the assumed section is safe.
However interaction charts prepared for this purpose can be used for actual design using the following
procedure.
Mb
h’
h
0
Mh
’
Range values of 0.05, 0.1, 0.15, … , 0.25 are available
h
b’ b’
b
Example 5.7
Design a column to sustain a factored design load of 900 KN and biaxial moments of
Mdx = 180 KNm, Mdy = 270 KNm including all other effects. Assume materials of concrete C-30, steel
S-300, class I work.
Slender Columns
Summary
The strength of Concentrically loaded Columns decreases with increasing slenderness ratio
In Columns that are braced against side sway or that are parts of frames braced against side sway,
the effective length , the distance b/n inflection points, falls between , depending
on the degree of end restraint.
The effective lengths of Columns that are not braced against side sway or that are parts of frames
not so braced are always larger than the more so the smaller the end restraint .In consequence,
the buckling load of a frame not braced against side sway is always substantially smaller than that
of the same frame when braced.
In flexural members the presence of axial Compression causes additional deflections and additional
moments Py. Other things being equal, the additional moments increase with increasing
slenderness ratio
In members braced against side sway and bent in single curvature, the maxima of both types of
moments, Mo and Py, occur at the same or at nearby locations and are fully additive, this leads to
large moment magnifications. If the M o moments result in double curvature (i.e., in the occurrence
of an inflection point), the opposite is true and less or no moment magnification occurs.
In members of frames not braced against side sway the maximum moments of both kinds, M o and
Py, almost always occur at the same locations, the ends of the column, they are fully additives,
regardless of the presence or absence of an inflection point. Here, too, other things being equal, the
additional deflections and the corresponding moments increase with increasing
Moment Magnification
1
Where Pu=Factored Load.
Pc=Critical Load
Cm=0.6+0.4
For members braced against side sway and without transverse loads between supports. Here M 2 is larger
of the two end moments, and is positive when the end moments produce single curvature and
negative when they produce double curvature.