Modulo Gsa cc1 Kidde Manual Instalacion
Modulo Gsa cc1 Kidde Manual Instalacion
Installation Sheet
Personality codes
The module requires the loop controller to download the
personality code that determines how the module operates.
Use the personality codes described below to configure the
GSA-CC1. See Table 1 for listing information.
© 2017 United Technologies Corporation 1/6 P/N P-047550-1802-EN • REV 05 • ISS 03FEB17
Installation Figure 2: Bell circuit showing bipolar transient protector
placement
Notes
(1) (2)
• The module is shipped from the factory as an assembled
unit; it contains no user-serviceable parts and should not
be disassembled.
• This module does not operate without electrical power. As
fires frequently cause power interruption, discuss further
safeguards with the local fire protection specialist.
Install in accordance with all applicable local codes and 10 9
standards and the local authority having jurisdiction.
1. Normal state 2. Active state
To install the module:
1. Wire in accordance with “Wiring” below. Wiring
2. Write the address assigned to the module on the label Wire in accordance with applicable requirements of the latest
provided, and then apply the label to the module. Remove editions of the local codes and standards and the local
the serial number label from the detector and, and then authority having jurisdiction.
attach it to the project documentation.
Strip 1/4 in. (about 6 mm) from the ends of all wires that
3. Using the screw provided, mount the wall plate on the connect to the terminal block of the module.
module. See Figure 1 for mounting details.
Note: When stripping wire ends, exposing more wire may
4. Using the screws provided, mount the wall plate (with the cause a ground fault; exposing less wire may result in a faulty
module attached) on one of the compatible electrical connection.
boxes listed in “Specifications” on page 6.
General wiring notes
Figure 1: Mounting the GSA-CC1 module • Refer to the Signature loop controller installation sheet for
SLC wiring specifications. Refer to the firefighter phone
(1)
installation sheet for additional details.
(2) • Each terminal on the module is limited to a single
conductor.
• Test resistors are supplied with the GSA-CC1 to prevent
(3)
trouble signals on unused circuits during installation.
When connecting field wires, remove the test resistors and
(4) install a UL/ULC Listed 47 kΩ EOLR at the end of the
circuit.
(5) • The module does not support conventional smoke
detectors.
Protection from transient spikes • Circuit and riser wiring is different when four-state
firefighter telephones are installed on three-state circuits.
For installations in which the output circuit connects to Before replacing a GSA-CC1 module, tag the wires to
electromechanical bells or horns, install a Bipolar Transient ensure correct reconnection.
Protector (P/N 235196P) to prevent inductive loads from
causing transient spikes. • The GSA-CC1 module does not supervise the riser; the
fire alarm control panel provides this function.
To install a bipolar transient protector:
1. Install the transient protector on the output of the module.
Fit the transient protector into the electrical box with the
module. See Figure 2.
(5)
+
(1)(2)(3)(4)
+ +
(10) (6)
+
+ (7)
(9)
(3)(8)
(1) Signal polarity is shown when the circuit is in supervisory state. (4) If using a G1-P Genesis series horn while connected to a
Polarity reverses when the circuit is active. compatible fire alarm control panel, a CDR-3 Bell Coder must
(2) Supervised. be used to comply with NFPA 72 standard alarm evacuation
signal.
(3) Power-limited unless connected to a nonpower-limited source. If
(5) 47 kΩ EOLR.
the source is nonpower-limited, eliminate the power-limited mark (6) Signaling line circuit (SLC) to next device.
and maintain a minimum of 0.25 in.
(7) AUX riser (to next module or riser supervisory device).
(6.4 mm) space from power-limited wiring. For other mounting
(8) Power-limited regulated, power supply UL/ULC Listed for fire
methods, see enclosure and bracket installation sheets to protective signaling systems.
maintain separation of power-limited and nonpower-limited
(9) AUX riser (from previous device).
wiring. The wire size must be capable of handling fault current
(10) Signaling line circuit (SLC) from previous device. Supervised
from nonpower-limited source. and power-limited.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending beyond
the jacket are separated by a minimum of 0.25 in. (6.4 mm)
space or by a nonconductive sleeve or nonconductive barrier
from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
(5)
(1)(2)(3)(4)
+ +
(10) (6)
+
(7)
+
(9)
(1) Signal polarity shown when the circuit is in supervisory state. (4) Unshielded twisted pair.
Polarity reverses when the circuit is active. (5) 47 kΩ EOLR (P/N EOL-47).
(2) Supervised. (6) Signaling line circuit (SLC) to next device.
(3) Power-limited unless connected to a nonpower-limited source. If (7) Audio riser (to next module or supervisory end of line device).
the source is nonpower-limited, eliminate the power-limited mark (8) Unshielded twisted pair. Use shielded twisted pair when
and maintain a minimum of 0.25 in. installed in the same conduit as with a telephone riser.
(6.4 mm) space from power-limited wiring. For other mounting (9) Audio riser (from previous device).
methods, see enclosure and bracket installation sheets to (10) Signaling line circuit (SLC) from previous device. Supervised
maintain separation of power-limited and nonpower-limited and power-limited.
wiring. The wire size must be capable of handling fault current
from nonpower-limited source.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending beyond
the jacket are separated by a minimum of 0.25 in. (6.4 mm)
space or by a nonconductive sleeve or nonconductive barrier
from all other conductors. Refer to the NFPA 70 National
Electrical Code for more details.
Three-state telephone circuit (personality code 6) (1) Telephone circuit. The plus and minus symbols indicate
signal polarity.
(2) Supervised.
(3) Power-limited unless connected to a nonpower-limited
source. If the source is nonpower-limited, eliminate the
(5) power-limited mark and maintain a minimum of 0.25 in.
(6.4 mm) space from power-limited wiring. For other
(1)(2)(3) mounting methods, see enclosure and bracket installation
(4) sheets to maintain separation of power-limited and
nonpower-limited wiring. The wire size must be capable of
handling fault current from nonpower-limited source.
— or —
Use type FPL, FPLR, FPLP, or permitted substitute cables,
provided these power-limited cable conductors extending
beyond the jacket are separated by a minimum of 0.25 in.
(6.4 mm) space or by a nonconductive sleeve or
nonconductive barrier from all other conductors. Refer to
the NFPA 70 National Electrical Code for more details.
(10) (6) (4) Required if the distance from the GSA-CC1 to the phone is
(9) (7) greater than 5 ft. Shield must be continuous, insulated, and
isolated from ground, except for the connection to chassis
(3)(8) ground in the control panel.
(10) (6)
(9) (7)
(3)(8)