0% found this document useful (0 votes)
22 views4 pages

Pdvsa: Temperature Instruments (Filled System)

The document provides specifications and instructions for filling out forms related to temperature instruments in filled systems for PDVSA. It includes details on item specifications, mounting, enclosure types, power supply, transmitter outputs, and alarm functions. Additionally, it outlines the classification of filled thermal systems and provides guidance on how to specify various parameters for the instruments.

Uploaded by

AngelZepol
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views4 pages

Pdvsa: Temperature Instruments (Filled System)

The document provides specifications and instructions for filling out forms related to temperature instruments in filled systems for PDVSA. It includes details on item specifications, mounting, enclosure types, power supply, transmitter outputs, and alarm functions. Additionally, it outlines the classification of filled thermal systems and provides guidance on how to specify various parameters for the instruments.

Uploaded by

AngelZepol
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

To fill the data sheet, click here

PDVSA
TEMPERATURE INSTRUMENTS (FILLED SYSTEM)

ITEM N° QUANTITY OFF PROJECT REFERENCE SHEET OF

SPECIFICATION REFERENCES N° By REVISED DATE


I.S.A S
PDVSA–K–

GENERAL 1. Tag N° Service

2. Function Record Indicate Control Trans Temp. Switch

4. Mounting Flush Surface Yoke


5. Enclosure Safe area Classified Class Group Div.
Weatherproof Ex. proof Intr. safe STD

Temp. Class T1 T2 T3 T4 T5 T6

6. Power Supply 110 V 60 Hz 24 Volts d.c.


7. Chart Circular Range Drive–Elec Spring Speed
9. Scale Range 1 2 3

XMTR 10. Transmitter 4–20 mA 3–15 psig Other

CONTR 11. Control Modes P PI PID Other Reversible Action

12. Auto–man MFR.STD switch Manual Regulator

13. Set Point Adj. Manual Remote

14. Output 4–20 mA 21–103 kPa (3–15 psig) Other

ELEMENT
17. Fill SAMA Class Full compensation
18. Process Data Temp.: Min. Max. Max. Press
19. Range To Overrange Protection to

20. Bulb Type Mtl. Extension: Length Type


21. Capillary Length Mtl. Armor
22. Thermowell Mtl. Insertion Lag. Ext.
Const: Drilled Process Conn.

ALARMS 23. Switches Function on meas. High and low No. of alarms Form: DPDT /amp. @ 24 v.d.c.

OPTIONS 24. Options Filt–Reg. Charts

MFR 26. Model N°

Notes: 1. All items shall be corrosion resistant to marine atmosphere and tropicalised.
2. Alarm contact shall be normally closed and open on alarm condition

20.11a
To fill the data sheet, click here

PDVSA
TEMPERATURE INSTRUMENTS (FILLED SYSTEM)

ITEM N° QUANTITY OFF PROJECT REFERENCE SHEET OF

SPECIFICATION REFERENCES N° By REVISED DATE


I.S.A S
PDVSA–K–

Item Tag. N5 Range Thermowell Insertion Lagging Capillary


N5 Notes
Process Conn. Length Ext. Length

Notes:

20.11b
ENGINEERING SPECIFICATION PDVSA doc.20.11
REVISION DATE
PDVSA INSTRUCTIONS TO FILL FORMS
20.11A AND 20.11B 0 AUG.94
Page 1

Menú Principal Indice manual Indice volumen Indice norma

TEMPERATURE INSTRUMENTS (FILLED SYSTEMS)

1. To be used for a single item. Use secondary sheet for multiple listing.
2. Check as many as apply.
3. Nominal size refers to approximate front of case dimensions; width x height.
4. Yoke refers to a bracket designed for mounting the instrument on a pipe stand.
5. Enclosure class refers to composite instrument. If electrical contacts are in the
case, they must meet this classification inherently or by reason of enclosure.
Use NEMA identification or ISA identification RP8.1.
6. Specify electrical power to the entire instrument from an external source.
7. Specify chart size, range and number applicable.
8. Chart drive mechanism assumed to be synchronous motor operating in 117V
60 Hz and suitable for ENCLOSURE CLASS specified on line 5. If the chart
drive is pneumatic so state –identify pneumatic pulser under options. Note
deviations from standard (MFR) under notes i.e., dual speed or special speeds.
9. The scale type may be SEGMENTAL VERTICAL, HORIZONTAL, DIAL
(CIRCULAR) or other. Ranges 1, 2, 3 and 4 are used for multiple inputs. The
first listed (No. 1) is assumed to be the controller input, if a controller is used.
10. Specify transmitter output if applicable.
11. See explanation of terminology given on specification sheet. For further
definition refer to American National Standard C85.1–1963, ‘‘Terminology for
Automatic Control’’. Specific ranges of control modes can be listed after
‘‘OTHER’’, if, required.
12. For multiple items specify on second sheet.
13. If standard auto–manual switching is not known or not adequate, specify
particular requirements, such as BUMPLESS, PROCEDURELESS,
4–POSITION, or as required.
14. Remote set point adjustement assumes full adjustment range. Specify limits
required.
15. Specify if applicable.
16. Specify if applicable.
17. Filled thermal systems can be of the following SAMA classification:
ENGINEERING SPECIFICATION PDVSA doc.20.11
REVISION DATE
PDVSA INSTRUCTIONS TO FILL FORMS
20.11A AND 20.11B 0 AUG.94
Page 2

Menú Principal Indice manual Indice volumen Indice norma

Class 1A: Liquid filled, uniform scale, fully compensated.


Class IB: Liquid filled, uniform scale, case compensated only.
Class IIA: Vapor pressure, non–linear scale with measured temperature
above case and tubing temperature.
Class IIB: Vapor pressure, non–linear scale with measured temperature
below case and tubing temperautre.
Class IIC: Vapor pressure, non–linear scale with measured temperature
above and below case and tubing temperature.
Class IIIA: Gas filled, uniform scale, fully compensated.
Class IIIB: Gas filled, uniform scale, case compensated only.
Class VA: Mercury filled, uniform scale, fully compensated.
Class B: Mercury filled, uniform scale, case compensated only.

18. Range refers to process input span for which an output is desired.
Adjustable range means that the unit can give its normal output over a
range of inputs.
19. Bulb type can be plain, averaging, rigid, adjustable union connections, fixed
union connection. Capillary extension length can be rigid or flexible, etc.
20. Capillary tube specifications.
21. Well specifications.
22. Form may be SPST, SPDT, DPDT, etc. Rating is electrical rating of switch
in volt amps.
23. Check if alarm is to be actuated by measured variable or by deviation from
controller set piont. Give contact action if single throw from.