AirDiffusionUnitsOct2011 Pages 8
AirDiffusionUnitsOct2011 Pages 8
65
25 CTRS FRONT CORE
FACE SIZE = NECK SIZE +47
ADCFDD
NECK SIZE
APPLICATIONS
65
Truly unique, curved face registers are
designed for direct mounting to horizontal
runs of circular or oval duct work for either
supply, return or exhaust applications. 25 CTRS FRONT CORE
FACE SIZE = NECK SIZE +47
Registers needs to be sized so the height
of the grille is at least 100mm less than the ADCFDD (to suit convex curve)
diameter of the duct to which it is fitted,
allowing sufficient room for the grille frame.
FEATURES
Two cores with adjustable horizontal and vertical blades at 25mm centres.
Details of duct diameters are required at time of order to establish curvature requirements
35
Supply Air
O
0 Deflection
O
22.5 Deflection
500 x 300 600 x 300 750 x 300 750 x 350 900 x 350
Nominal
600 x 250 750 x 250 900 x 250 900 x 300 1000 x 300
Size
750 x 200 900 x 200 1200 x 200 1000 x 250 1200 x 250
Core 0.15 sqm 0.18 sqm 0.24 sqm 0.27 sqm 0.30 sqm
m/s L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m)
1.0 150 1 5 180 1 5 240 1 7 270 1 7 300 1 7
1.5 225 3 7 270 3 8 360 3 10 405 3 10 450 2 11
2.0 300 5 9 360 5 10 480 6 13 540 5 13 600 4 14
2.5 375 7 11 450 7 13 600 9 16 675 7 16 750 7 17
3.0 450 10 14 540 10 15 720 12 19 810 11 20 900 10 20
3.5 525 14 16 630 14 18 840 17 22 945 15 23 1050 14 24
4.0 600 18 18 720 18 21 960 22 25 1080 19 26 1200 18 27
5.0 750 29 22 900 28 26 1200 35 31 1350 30 32 1500 28 34
36
Supply Air
O
45 Deflection
Core m/s 0.045 sqm 0.050 sqm 0.060 sqm 0.075 sqm
L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m)
1.0 45 2 2 50 1 2 60 1 2 75 2 3
1.5 68 4 3 75 3 3 90 3 4 113 4 4
2.0 90 6 4 100 6 4 120 6 5 150 6 6
2.5 112.5 10 5 125 9 5 150 9 6 188 10 7
3.0 135 15 6 150 13 6 180 13 7 225 14 9
3.5 157.5 20 7 175 18 8 210 17 9 263 20 10
4.0 180 26 8 200 24 9 240 22 10 300 26 12
5.0 225 41 10 250 37 11 300 35 13 375 40 15
Core m/s 0.090 sqm 0.100 sqm 0.120 sqm 0.15 sqm
L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m)
1.0 90 2 3 100 1 3 120 1 3 150 1 3
1.5 135 4 5 150 3 5 180 2 5 225 3 5
2.0 180 6 6 200 6 7 240 5 7 300 6 7
2.5 225 10 8 250 9 8 300 9 8 375 9 9
3.0 270 15 10 300 13 10 360 12 10 450 13 11
3.5 315 20 11 350 17 12 420 17 12 525 17 12
4.0 360 26 13 400 22 13 480 22 13 600 23 14
5.0 450 41 16 500 35 17 600 34 17 750 36 18
Core m/s 0.18 sqm 0.24 sqm 0.27 sqm 0.30 sqm
L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m) L/s Pa Throw(m)
1.0 180 1 4 240 2 5 270 2 5 300 1 5
1.5 270 3 6 360 4 7 405 4 8 450 3 8
2.0 360 5 8 480 7 10 540 6 10 600 5 11
2.5 450 8 10 600 11 12 675 10 13 750 8 14
3.0 540 11 12 720 16 15 810 14 16 900 12 16
3.5 630 16 14 840 22 17 945 19 18 1050 16 19
4.0 720 20 16 960 28 20 1080 25 21 1200 21 22
5.0 900 32 21 1200 44 25 1350 39 26 1500 33 27
Throw (m) is to a terminal velocity of 0.25m/s. Throw to a terminal velocity of 0.5m/s is approximately 70% of the above.
37
Supply Air
Register Size
Register Size
n o p q r
500x300, 600x300, 750x300, 750x350, 900x350,
600x250, 750x250, 900x250, 900x300, 1000x300,
750x200 900x200 1200x200 1000x250 1200x250 38
Supply Air
Register Size
n o p q r
500x300, 600x300, 750x300, 750x350, 900x350,
600x250, 750x250, 900x250, 900x300, 1000x300,
750x200 900x200 1200x200 1000x250 1200x250
Register Size
n o p q r s t
250x200, 300x200, 350x200, 450x200, 400x250, 500x250,
300x150 350x150, 400x150, 500x150, 600x150, 500x200, 600x200,
500x100 600x100 750x100 900x100 750x150 900x150 39