F-2 Isolated: 1) Design Criteria

The document outlines the design criteria and calculations for an isolated footing, including unit weights, stress values, and required dimensions. It details the weight of the footing, total load, footing area, and checks for shearing and punching shear, concluding that the design is acceptable based on the calculations. Additionally, it specifies the required steel reinforcements and checks for bond stress, confirming that the design meets safety standards.

Uploaded by

ndjacadservices
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views3 pages

F-2 Isolated: 1) Design Criteria

The document outlines the design criteria and calculations for an isolated footing, including unit weights, stress values, and required dimensions. It details the weight of the footing, total load, footing area, and checks for shearing and punching shear, concluding that the design is acceptable based on the calculations. Additionally, it specifies the required steel reinforcements and checks for bond stress, confirming that the design meets safety standards.

Uploaded by

ndjacadservices
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Prepared by:

F-2 ISOLATED Engr. Nestor DJ. Roda TWS Page 1 of 3


Civil Engineer

1) Design Criteria:
Unit weight of Concrete, Wc = 23,537 N/m3
Steel tensile unit stress, Fs = 124.13 MPa
Compressive strength of concrete, Fc' = 20.69 MPa
Compressive stress of concrete, Fc = 9.31 MPa
Modulus of elaticity ratio, n = 9
Design constant, k = 0.40295
Design constant, j = 0.86568
Design constant, R = 1.62 MPa
Soil pressure (assumed), B = 150.0 KPa
Seismic Factor (Standard Occupancy Structure) = 1.50
Column load, P = 91661.00 N
column width,w = 0.20 m
Assumed column load as weight of the footing = 10%

2) Weight of footing:
Weight of footing = 10% of column load
Wft = 9166.10 N

3) Total load:

Total load = P + W ft
TL = 151240.65 N

4) Required footing area:


TL
A =
B
151.24 KN
A =
150.0 KPa

A = 1.01 sqm

5) Square footing dimension:

L = width of each side


L = A
L = 1.004 m
Say L = 1.30 m OK !

Try 1.30 m X 1.30 m

6) Solve for q (Net soil pressure)


P
q =
(L)(L)

91.66 KN
q =
1.69 sqm

q = 54.24 KN/m2

RCC DESIGNCOMPU 20/12/2024 6:02 am


Prepared by:
F-2 ISOLATED Engr. Nestor DJ. Roda TWS Page 2 of 3
Civil Engineer

7) Moment Computation:
(L - w)2
M = q X L X
2
M = 42.66 KN . m

8) Compute for d:
M
d =
Rb
d = 0.142 m
Say d = 0.250 m OK !

9) Check for shearing stress :

V allowable = 0.09 Fc'

V allowable = 0.409 MPa

Vd
V actual =
bd

where: Vd - is the shear at a distance "d"


from the support

L-w
V actual = q X L X - d
2
V actual = 0.021 MPa

Since V allowable > V actual , then it is OK !

10) Check for punching shear :

Vp allowable = 0.17 Fc'

Vp allowable = 0.773 MPa

Vp
Vp actual =
Ap

where: Vp = q X L2 - (w + d)2
Vp = 80.68 KN

Ap = 4(w+d)(d)
Ap = 0.45 sqm

Vp actual = 0.179 MPa

Since Vp allowable > Vp actual , then it is OK !

RCC DESIGNCOMPU 20/12/2024 6:02 am


Prepared by:
F-2 ISOLATED Engr. Nestor DJ. Roda TWS Page 3 of 3
Civil Engineer

11) Check for the actual weight of the footing:


2
Wact = h x L x Wc
Wact = 12927.70 N
Since W ft < Wact then it is NOT OK !

12) Steel Reinfocements:


M
AS =
Fs j d
AS = 0.001588 m2

Using 20 mm daimeter bar: A16 = 0.000314 m2

0.001588 m2
# of bars =
0.000314 m2
# of bars = 5.05 pcs

Say 13 pcs 16mm


20 mm
dai
Ø deformed
Steel Bar bar OK !

13) Check for bond stress:


10.14 Fc'
U allowable =
D

where: D - Daimeter of the bar used

U allowable = 2.306 MPa

Vt
U actual =
ojd

where: o - Sum of the perimeter of the bar used

U actual = 0.219 MPa

Since U allowable > U actual , then it is OK !

14) Details:

250 mm
325 mm
75 mm c/cover
13 - 20 mmØ
deformed bar
1.30 m
both ways