Hart
Hart
Hart
HART® is a registered trademark of the HART Communication Foundation. Any use of the word “HART” hereafter in this
document implies the registered trademark. All other trademarks used in this document are acknowledged to be trademarks of their
respective companies.
Table of Contents
Preface............................................................................................................................................................. 1
Theory of Operation........................................................................................................................................ 2
Communication Modes ................................................................................................................................... 3
Frequency Shift Keying .................................................................................................................................. 4
HART Networks .............................................................................................................................................. 5
HART Commands ........................................................................................................................................... 7
Benefits of HART Communications .............................................................................................................. 9
Improved Plant Operations........................................................................................................................... 10
Operational Flexibility.................................................................................................................................. 13
Instrumentation Investment Protection ....................................................................................................... 14
Digital Communication ................................................................................................................................ 15
Getting the Most out of HART Systems ....................................................................................................... 16
Wiring and Installation................................................................................................................................. 17
Intrinsic Safety .............................................................................................................................................. 18
HART Multidrop Networks .......................................................................................................................... 22
Control System Interfaces............................................................................................................................. 24
Multiplexers................................................................................................................................................... 26
Reading HART Data into NonHART Systems ............................................................................................ 28
Universal Handheld Communicator ............................................................................................................ 30
PC Configuration Software .......................................................................................................................... 31
Commissioning HART Networks ................................................................................................................. 32
Device Status and Diagnostics...................................................................................................................... 33
Connecting a PC to a HART Device or Network......................................................................................... 34
PC Application Development Tools.............................................................................................................. 35
Control in Field Devices ............................................................................................................................... 36
Use the Power of HART ............................................................................................................................... 38
Call for Information ..................................................................................................................................... 40
Hidden In HART........................................................................................................................................... 48
Leverage Your Assets .................................................................................................................................... 58
Unleash the Power of HART ........................................................................................................................ 63
Powerful Connections................................................................................................................................... 66
Put It To Work .............................................................................................................................................. 70
HART Plant of the Year ............................................................................................................................... 82
Get Started ..................................................................................................................................................... 86
Industry Applications................................................................................................................................... 89
Inventory-Management Applications...........................................................................................................90
Cost-Saving Applications..............................................................................................................................93
Remote-Operation Applications ...................................................................................................................98
Open-Architecture Applications................................................................................................................. 100
Where To Get More Information ............................................................................................................... 103
Appendix A: HART Checklist .................................................................................................................... 104
Appendix B: HART Revision 5................................................................................................................... 107
Appendix C: HART Revisions 2, 3, and 4.................................................................................................. 109
Appendix D: Common Practice Commands .............................................................................................. 111
Appendix E: Response Codes ..................................................................................................................... 116
Table of Contents
Appendix F: HART Field Control.............................................................................................................. 118
Appendix G: Technical Information.......................................................................................................... 120
Glossary ....................................................................................................................................................... 121
Preface
In today’s competitive environment, all companies seek to reduce operation
costs, deliver products rapidly, and improve product quality. The HART®
(highway addressable remote transducer) protocol directly contributes to
these business goals by providing cost savings in:
T Commissioning and installation
T Plant operations and improved quality
T Maintenance
Theory of Operation
The following sections explain the basic principles behind the operation of
HART instruments and networks:
T Communication Modes
T Frequency Shift Keying
T HART Networks
T HART Commands
Communication Modes
MASTER-SLAVE HART is a master-slave communication protocol, which means that during
MODE normal operation, each slave (field device) communication is initiated by a
master communication device. Two masters can connect to each HART
loop. The primary master is generally a distributed control system (DCS),
programmable logic controller (PLC), or a personal computer (PC). The
secondary master can be a handheld terminal or another PC. Slave devices
include transmitters, actuators, and controllers that respond to commands
from the primary or secondary master.
BURST MODE Some HART devices support the optional burst communication mode.
Burst mode enables faster communication (3–4 data updates per second). In
burst mode, the master instructs the slave device to continuously broadcast
a standard HART reply message (e.g., the value of the process variable).
The master receives the message at the higher rate until it instructs the slave
to stop bursting.
Use burst mode to enable more than one passive HART
device to listen to communications on the HART loop.
20 mA
Digital
Signal
“1” “0”
“1”
“1” “0”
“1”
“0” “0”
“1”
Analog
Signal
4 mA
Time
Note: Drawing not to scale.
HART Networks
HART devices can operate in one of two network configurations—point to
point or multidrop.
Control System
Multiplexer or Other Host
Application
Barrier
Handheld Terminal
Field Device
HART Networks
MULTIDROP The multidrop mode of operation requires only a single pair of wires and, if
applicable, safety barriers and an auxiliary power supply for up to 15 field
devices (Figure 3). All process values are transmitted digitally. In
multidrop mode, all field device polling addresses are >0, and the current
through each device is fixed to a minimum value (typically 4 mA).
Use multidrop connection for supervisory control
installations that are widely spaced, such as
pipelines, custody transfer stations, and tank farms.
Handheld Terminal
Input/Output (I/O)
System
Field Devices
Note: Instrument power is provided by an interface or external power source that is
not shown.
HART Commands
The HART command set provides uniform and consistent communication
for all field devices. The command set includes three classes: universal,
common practice, and device specific (Table 1). Host applications may
implement any of the necessary commands for a particular application.
UNIVERSAL All devices using the HART protocol must recognize and support the
universal commands. Universal commands provide access to information
useful in normal operations (e.g., read primary variable and units).
DEVICE SPECIFIC Device-specific commands represent functions that are unique to each field
device. These commands access setup and calibration information, as well
as information about the construction of the device. Information on
device-specific commands is available from device manufacturers.
SUMMARY TABLE
Universal Commands Common Practice Commands Device-Specific Commands
• Read manufacturer and • Read selection of up to four • Read or write low-flow cut-off
device type dynamic variables • Start, stop, or clear totalizer
• Read primary variable (PV) • Write damping time constant • Read or write density calibration
and units • Write device range values factor
• Read current output and • Calibrate (set zero, set span) • Choose PV (mass, flow, or
percent of range • Set fixed output current density)
• Read up to four predefined • Perform self-test • Read or write materials or
dynamic variables construction information
• Perform master reset
• Read or write eight-character • Trim sensor calibration
tag, 16-character descriptor, • Trim PV zero • PID enable
date • Write PV unit
• Write PID setpoint
• Read or write 32-character • Trim DAC zero and gain
message • Valve characterization
• Write transfer function (square
• Read device range values, root/linear) • Valve setpoint
units, and damping time • Write sensor serial number • Travel limits
constant • User units
• Read or write dynamic variable
• Read or write final assembly assignments • Local display information
number
• Write polling address
HART Commands
ESTABLISHING Each HART device has a 38-bit address that consists of the manufacturer
COMMUNICATION ID code, device type code, and device-unique identifier. A unique address
is encoded in each device at the time of manufacture. A HART master must
WITH A HART know the address of a field device in order to communicate successfully
DEVICE with it. A master can learn the address of a slave device by issuing one of
two commands that cause the slave device to respond with its address:
T Command 0, Read Unique Identifier—Command 0 is the preferred
method for initiating communication with a slave device because it
enables a master to learn the address of each slave device without user
interaction. Each polling address (0–15) is probed to learn the unique
address for each device.
T Command 11, Read Unique Identifier by Tag - Command 11 is useful
if there are more than 15 devices in the network or if the network
devices were not configured with unique polling addresses.
(Multidropping more than 15 devices is possible when the devices are
individually powered and isolated.) Command 11 requires the user to
specify the tag numbers to be polled.
DEVICE Some HART host applications use device descriptions (DD) to obtain
DESCRIPTION information about the variables and functions contained in a HART field
device. The DD includes all of the information needed by a host application
to fully communicate with the field device. HART Device Description
Language (DDL) is used to write the DD, that combines all of the
information needed by the host application into a single structured file. The
DD identifies which common practice commands are supported as well as
the format and structure of all device-specific commands.
A DD for a HART field device is roughly equivalent to a printer driver for a
computer. DDs eliminate the need for host suppliers to develop and support
custom interfaces and drivers. A DD provides a picture of all parameters
and functions of a device in a standardized language. HART suppliers have
the option of supplying a DD for their HART field product. If they choose
to supply one, the DD will provide information for a DD-enabled host
application to read and write data according to each device’s procedures.
DD source files for HART devices resemble files written in the C
programming language. DD files are submitted to the HCF for registration
in the HCF DD Library. Quality checks are performed on each DD
submitted to ensure specification compliance, to verify that there are no
conflicts with DDs already registered, and to verify operation with standard
HART hosts. The HCF DD Library is the central location for management
and distribution of all HART DDs to facilitate use in host applications such
as PCs and handheld terminals.
Additional information, not provided by the DD, may be required by some
host applications for screen formatting and other uses.
COST SAVINGS IN HART-based field devices can be installed and commissioned in a fraction
COMMISSIONING of the time required for a traditional analog-only system. Operators who
use HART digital communications can easily identify a field device by its
tag and verify that operational parameters are correct. Configurations of
similar devices can be copied to streamline the commissioning process. A
loop integrity check is readily accomplished by commanding the field
transmitter to set the analog output to a preset value.
COST SAVINGS IN The HART protocol supports the networking of several devices on a single
INSTALLATION twisted wire pair. This configuration can provide significant savings in
wiring, especially for applications such as tank monitoring.
Use HART multidrop mode to connect multiple instruments to
a single cable and reduce installation costs.
Some HART field devices store historical information in the form of trend
logs and summary data. These logs and statistical calculations (e.g., high
and low values and averages) can be uploaded into a software application
for further processing or record keeping.
Operational Flexibility
The HART protocol allows two masters (primary and secondary) to
communicate with slave devices and provide additional operational
flexibility. A permanently connected host system can be used
simultaneously, while a handheld terminal or PC controller is
communicating with a field device (Figure 5).
Analog
HART Interface
Digital Data
(2–3 updates
per second)
COMPATIBILITY OF As HART field devices are upgraded, new functions may be added. A basic
HART REVISIONS premise of the HART Protocol is that new HART instruments must behave
in precisely the same manner as older versions when interfaced with an
earlier revision host system.
Digital Communication
A digital instrument that uses a microprocessor provides many benefits.
These benefits are found in all smart devices regardless of the type of
communication used. A digital device provides advantages such as
improved accuracy and stability. The HART protocol enhances the
capabilities of digital instruments by providing communication access and
networking (Table 2).
CABLE LENGTH Most installations are well within the 3,000 meter (10,000 ft) theoretical
limit for HART communication. However, the electrical characteristics of
the cable (mostly capacitance) and the combination of connected devices
can affect the maximum allowable cable length of a HART network. Table
3 shows the affect of cable capacitance and the number of network devices
on cable length. The table is based on typical installations of HART
devices in non-IS environments, i.e. no miscellaneous series impedance.
Detailed information for determining the maximum cable length for any
HART network configuration can be found in the HART Physical Layer
Specifications.
Intrinsic Safety
Intrinsic safety (IS) is a method of providing safe operation of electronic
process-control instrumentation in hazardous areas. IS systems keep the
available electrical energy in the system low enough that ignition of the
hazardous atmosphere cannot occur. No single field device or wiring is
intrinsically safe by itself (except for battery-operated, self-contained
devices), but is intrinsically safe only when employed in a properly
designed IS system.
Zener Barrier
Power Supply
1–5 V Output
Transmitter Signal
Intrinsic Safety
HAZARDOUS SIDE SAFE SIDE
Power
Isolator Supply
1–5 V Output
4–20 mA Signal
Transmitter
Intrinsic Safety
While it is difficult to meet the two requirements noted above for a network
using shunt-diode barriers, it can be done. Following are two possible
solutions to the problem:
1. Shunt the load resistor with a large inductor so that the load resistor
impedance is still high (and mainly resistive) at HART signal
frequencies, but much lower at direct current. This solution, while it
does work, is physically somewhat inconvenient.
2. Use an IS isolator rather than a shunt-diode barrier. The output voltage
on the hazardous side is usually specified as greater than X Vdc at
20 mA (typically 14–17 V). This value already includes the voltage
drop due to the internal safety resistor, so the only extra voltage drop is
that due to cable resistance. System operation at 22 mA requires
reducing the 20 mA voltage by 0.7 V (340 Ω × 2 mA).
Intrinsic Safety
MULTIDROP IS HART multidrop networks are particularly suitable for intrinsically safe
NETWORKS installations. With a multidrop configuration, fewer barriers or isolators are
required. In addition, because each field device takes only 4 mA (for a total
of 16 mA in a four-device loop), plain zener barriers can be used. With a
250 Ω load, 25 V – (340 + 250 Ω) × 16 mA = 15.5 V, which is well above
the transmitter lift-off voltage and leaves a margin for cable resistance.
IS OUTPUT LOOPS For output devices such as valve positioners, direct-current voltage
considerations will vary depending on the drive requirements of the device.
Zener barriers may be possible. If not, modern HART-compatible output
isolators are appropriate.
IS NETWORK The cable length calculation must include the resistance of both the zener
CABLE LENGTH barrier and the load resistor.
CALCULATIONS
Master Device
Modem
Auxiliary Power
Supply
Transmitters
Handheld
Terminal Computer or
DCS
Power HART Interface
Supply Power Supply
Impedance
4–20 mA
+ – + – + – + – + – + –
HART
Transmitter
Control Valve
CONFIGURING Using the polling address structure of the HART protocol, up to 15 devices
DEVICES FOR can be connected in a multidrop network. The analog current of a HART
device can be fixed by setting its polling address to a number other than
MULTIDROP zero. With the HART protocol, each field instrument should be configured
OPERATION with different polling addresses or tag numbers before being connected to a
multidrop network—otherwise, the master will not be able to establish
communication with the slave devices.
HART I/O Many HART-compatible I/O subsystems have multiple analog channels on
SUBSYSTEMS each I/O card. Suppliers choose whether to provide one HART interface per
channel or to share one HART interface among several channels. The
number of shared channels per HART interface impacts the frequency of
data updates from a HART field device and the HART functionality that is
supported.
HART I/O FOR For the best performance and flexibility, one HART interface should be
MULTIDROP dedicated to each I/O channel. Systems that share only one HART interface
among several I/O channels may not support multidrop networks. The
SUPPORT effective update rate of a multiplexed interface is slow enough that the
performance of multiplexed multidrop networks would not be practical.
Some suppliers enable multidrop support by fixing the HART interface to
one specific I/O channel. However, the other channels on that card may
then not be available for HART communications.
HART I/O FOR Burst mode is an optional implementation in a field device. Receiving burst
BURST MODE mode messages is optional in a host as well. To take full advantage of burst
mode, the I/O system should have one HART interface for each channel. If
SUPPORT the HART interface is shared by more than one channel, messages sent by
the field device may not be detected by the control system. If the system
does not have the ability to configure burst mode in the field device, a
handheld terminal or other configuration tool is required.
GATEWAYS Gateways can be used to bring HART digital data into control systems that
do not support HART-capable I/O. Some systems support HART gateways
with communication protocols such as Modbus, PROFIBUS DP, or TCP/IP
Ethernet. The typical HART gateway supports all universal commands and
a subset of the common practice commands. Support varies depending on
the gateway supplier. Some gateways support access to device-specific
information.
Multiplexers
HART-compatible multiplexers are ideal for users who want to interface
with a large number of HART devices. Multiplexers can be modular and are
capable of supporting both point-to-point and all-digital (multidrop) HART
communication modes. Communication between a multiplexer and a host
application depends on the multiplexer capabilities (e.g., RS232C, RS485,
Modbus, and TCP/IP Ethernet).
When installing HART multiplexer systems, the following capabilities
should be considered:
T Number of HART channels supported
T Number of HART channels that share a HART modem
T Burst mode support
T Multidrop support
T Method of communication with the host computer or control system
MULTIPLEXER AS HART multiplexers can be used as the primary I/O front end for a
THE PRIMARY I/O HART-based control or monitoring system (Figure 10). Typically, a PC acts
as the host, providing the human-machine interface and performing other
SYSTEM high-level functions. The multiplexer continuously monitors the field
devices, reports the current readings and instrument status to the host, and
passes HART commands from the host computer to the field devices.
Multiplexer
Field
Devices
SCADA
Field Device
PARALLEL When a traditional 4–20 mA control system is using the analog signals for
MONITORING WITH measurement and control outputs, a HART multiplexer can be added to the
network to gain access to the digital HART signal. Using a multiplexer
A MULTIPLEXER enables a supervisory computer to monitor diagnostics and device status,
access configuration information, and read any additional process inputs or
calculations not provided by the 4–20 mA signal.
Multiplexers
Use a HART multiplexer to gain access to the digital
HART signal.
Automation and
Display System
Supervisory
Controllers Computer
I/O
Transmitter Multiplexer
Control Valves
Controller
I/O
HART The Tri-Loop module monitors a HART loop for a bursting message and
DATA-CONVERSION converts three of the four possible variables in HART command number
three to analog outputs (Figure 13). The conversion enables the field device
PRODUCTS to provide a total of four analog signals over a single pair of wires run from
the field.
.
Channel 1
4–20 mA
Channel 2 Signals for
Secondary
Channel 3 Variables
Field Terminals
Rail-Mounted
Tri-Loop Module Control System
Control
System
Process
and
Diagnostic
Data
Annunciator
Event
Recorder
PC Configuration Software
Many instrument manufacturers, as well as some independent software
developers, offer HART communication software for PCs with capabilities
similar to and beyond those offered by a HART handheld communicator.
Use special software applications to continuously
monitor the status of connected field devices and log
status changes as they occur, which may help
reduce the costs of regulatory compliance.
DEVICE Before installation, manufacturers usually enter device tags and other
VERIFICATION identification and configuration data into each field instrument. After
installation, the instrument identification (tag and descriptor) can be
verified in the control room using a configurator (handheld terminal or PC).
Some field devices provide information on their physical configuration
(e.g., wetted materials)—these and other configuration data can also be
verified in the control room. The verification process can be important in
conforming to governmental regulations and ISO quality requirements.
The commissioning process can be further streamlined by connecting a PC
configurator to each HART loop online, either by integration with the
control system or by using one of the many available HART multiplexing
I/O systems (see Multiplexers on page 26). With this centralized approach,
there is no need to move the configuration device from one termination
point to the next while commissioning all devices on the network.
LOOP INTEGRITY Once a field instrument has been identified and its configuration data
CHECK confirmed, the analog loop integrity can be checked using the loop test
feature, which is supported by many HART devices. The loop test feature
enables the analog signal from a HART transmitter to be fixed at a specific
value to verify loop integrity and ensure proper connection to support
devices such as indicators, recorders, and DCS displays.
Use the HART protocol loop test feature to check
analog loop integrity and ensure a proper physical
connection among all network devices.
PC/Host
Application
RS232 HART
Interface Handheld Terminal
Field
Device
Power
Supply
PC-Based Operator
Interface
Modbus Link
(RS232) Muiltiplexer (HART Master)
4–20 mA to
Position Valve
Bypass
Capacitor
+ Smart
Power Transmitter
Supply
Control
Resistor Valve
But many end users haven’t made the connection. HART can do
much more than serve as an occasional information bridge for
device configuration and troubleshooting. In many applications it
can serve as the primary means of two-way communications for
system integration.
Resources Are Rising When HART technology was introduced in the early 1990s, control
engineers realized information from intelligent devices was
valuable, but at the time there was no easy or clean way to integrate
this data into control systems. For years, valuable information in
these devices has languished in parts of subsystems, in limited
applications such as maintenance and loop checkout tools, or
ignored altogether.
Over the past 10 years, companies of all sizes have created HART-
capable devices that operate in a hybrid fashion. These devices
offer a powerful bridge between the analog and digital worlds by
using the 4-20 mA signal to feed the control system as initially
designed, and simultaneously carry digital HART information¡ª
which in most cases is free - with additional process variables,
enhanced alarms and diagnostics information.
Talk with your suppliers about how their products support the full
power of HART. If they don’t, ask why. Discuss your current
installation with your suppliers to ascertain the degree of HART
compatibility of your system. Then map out a plan to use your
assets to the fullest.
Corporations have spent billions of dollars over the past few years
installing ERP and asset management systems. A tremendous
amount of pressure is now being applied to process plant managers
and engineers to provide data to these systems. SCADA systems
must also be upgraded to improve performance and reduce costs.
SCADA Can Do More The market for SCADA applications continues to grow. According
With to Russ Novak, director of consulting for the ARC Advisory Group,
Dedham, Mass., “The worldwide SCADA systems market for the
oil & gas and water &wastewater industries exceeded $650 million
in 2000. This market will reach almost $780 million by the end of
2005,growing at an annual rate of 3.5%.” HART devices can be
expected to play a significant role in this growth.
The Calumet gas plant receives raw natural gas from offshore
pipelines and separates out liquids such as propane, ethane, and
methane. The plant consumes natural gas in the process and is
charged for the energy usage by its suppliers. “Our firm designed a
gas flow measurement system for Calumet to internally verify the
amount of energy used in various parts of the process. Calumet
needed to provide check metering for gas usage,” says Jon Tandy, a
project engineer for Arcom.
In this application (Figure 1), each field device must have the
capability to transmit a signal to each of the two independent
control systems. “A Foxboro I/A system is the DCS and a PLC was
used for the safety shutdown system. In the I/A system, the fieldbus
module interfaces to the HART digital communication signal from
the field device. The PLC uses the 4-20 mA signal from the field
device for its analog I/O as the primary input of the safety shutdown
The DCS analyzes the HART signal information and distributes this
information throughout the control system. “The HART protocol is
used for diagnostic information from the field device. This
information can provide an active status word to the system and
alert the operator of a device fault before it impacts the performance
of the process. The status word is integrated into the analog input
block of the control system and propagated throughout the control
strategy if an error or device fault is detected,” adds Gray.
ERP Needs HART ERP and e-business systems from vendors such as SAP, Baan, and
Oracle cannot perform as designed without extensive information
from plant-floor control systems. This information is often available
through existing HART devices. Plant engineers can extract data
from these existing devices and provide it to ERP systems. The
expenses of purchasing and installing new devices often can be
avoided.
HART Helps Manage Record keeping also extends to instrument calibration activities.
Assets Asset management programs can use HART capabilities to
automate much of the calibration and recordkeeping required for
critical processes.
accomplished.”
Hidden In HART
Most users know HART provides for communication of multiple
data items between field devices and a host controller or computer.
Many also know that integrating additional field device data into
control or maintenance strategies can improve system
performance.
The most important data items available from HART devices are
the process variables. The primary process variable is continuously
transmitted in two formats: 4-20 mA analog and digital as part of
the HART protocol.
One of the best ways to improve plant profitability is to use the on-board
temperature sensor located in virtually all HART devices. This sensor
measures the internal temperature inside the field device, not the ambient
or process temperature. The manufacturer uses internal device
temperature to characterize the output during wide temperature
fluctuations, thereby eliminating most of the temperature-related error of
the device. A user can also digitally transmit the on-board device
temperature to the control system using the HART protocol.
“Our clients often use the on-board temperature sensor for freeze
protection alarming,” says Meyer. “During the winter months in cold
climates, every process plant has some type of freeze protection on
various production lines. The protection can be electric heaters, steam, or
just insulation to keep the process fluid from freezing.”
The temperature errors of the dual seals tend to offset each other because
the error on one side is canceled by a similar error on the other side. But
there still is one error that is not compensated: a shift in the output
caused by a temperature-driven change in the density of the fluid inside
the capillary between the two seals. As the ambient capillary temperature
changes, the change in the fluid density creates an error.
The low-cost solution is to take the on-board temperature inside the basic
differential pressure transmitter as a good approximation of the seal fill
fluid temperature. A user can then program a software compensation
block with a table of the fill fluid density vs. temperature. A few basic
math calculations using the distance between the seals, the span of the
level measurement, and the density vs. temperature chart greatly enhance
level measurement accuracy.
Valves Vie for The multivariable features of HART are used extensively for valve
Attention control. “The management of final control elements through digital
communication offers significant advantages,” says James Gray, director
of I/A systems marketing, Invensys Process Systems, Foxboro, Mass.
“Intelligent valve positioners provide real-time feedback of valve
position, measurement of pneumatic supply pressure, and measurement
of the positioner’s output signal to the actuator.” Operators can use the
secondary variable information to perform remote diagnostics on valves.
Users do not stroke these valves because partial valve actuation without
position monitoring can be hazardous. “A prudent strategy is to upgrade
the valve with a smart HART positioner and a HART loop monitor,”
says Adler. “With this combination, the presence of adequate air supply
can be verified and the valve can be partially stroked on a regular basis
to ensure its ability to move off of the seat.” The loop monitor reads the
HART secondary variable and provides stem position feedback to ensure
that the valve is only partially stroked.
The mill uses the Smart Adviser plant health monitor from Thermo
Measurement, Winchester, England, to enhance the existing process
monitoring and control system and to provide significant benefits in
three areas: valve maintenance, valve failure, and multiplexing. “A large
number of valve positioners with HART communication are in operation
at the mill,” reports Peter Vincent, sales and marketing director for
Thermo Measurement. “Some are installed on minor applications but
many perform critical safety tasks.”
Available: Advanced HART devices provide eight diagnostic status bits (16 bits with the new
Diagnostics HART 6 enhancement). These status bits can be used to provide early
warning of device problems. Handheld communicators can access this
information when connected to the instrument loop, but most
applications would benefit from continuous monitoring of these status
bits.
This monitoring function is provided with some DCS and HMI software
packages, but not all control and monitoring systems have this
functionality. “Moore Industries provides loop monitors that are
typically panel-mounted and connected just like a handheld calibrator.
When a HART status bit changes, the loop monitor provides both LED
indication and a relay output,” says Adler.
Configuration Is Easy Most HART users are aware that HART instruments can be configured
With a PC remotely from any point on the HART data highway. This can be
performed with handheld calibrators or through a host computer.
If the system and level transmitter had been HART-enabled, the erroneous
signal could have been detected and the operator would have been alerted to the
problem before it shut down the plant. You can create those kinds of
capabilities in your plant. You may already have much of what you need to get
started, particularly if you purchased new smart field instrumentation in the
past 10 years. That's because just about every smart field instrument built these
days is capable of HART Communication.
And if you have devices with HART Communication, you also have a good
start on what you need to run your plant more efficiently. You're ready to begin
an asset management program, obtain early alarms on process upsets, and
increase the reliability of your processes.
What's more, it won't be a major investment to obtain the information you need,
because it's already there, ready to be accessed via HART Communication
More Than Maintenance technicians appreciate HART because it makes their jobs easier.
Maintenance Techs can interrogate devices directly from the control room, eliminating many
unnecessary trips out into the plant.
What you may not realize is that simplifying maintenance and calibration tasks
is just the tip of the iceberg. Your HART devices also have the power to push
your existing plant instrumentation and control systems into the 21st Century.
You can use HART technology to get started in asset management, for
example. HART devices have all the information you need to determine device
status, health, and the need for field maintenance. HART devices can also
determine the health of other process equipment, such as control and safety
shutdown valves.
One of the finalists for this year's HART Plant of the Year Award, a Solutia
plant in Chocolate Bayou,Texas, that started up in 2000, has lots of HART-
enabled instrumentation. All the HART data is logged to an Aspen Tech data
historian and to an asset management system. "Our design decision was to use
as much smart instrumentation as possible,” says John Forbis, Engineering
Fellow at Solutia's Integrated Nylon Div., St. Louis.” Ninety-nine percent of all
instruments are HART-enabled. The only non-HART instruments are on OEM
systems, such as chillers and air compressors. We tried another communication
technology, and it just did not work for us."
The HART of the What can you do with all that data?
Matter Here are a few ideas:
Where Do You HART communication enables intelligent I/O systems to identify and diagnose
Go From Here? process problems such as:
Loop fault: With a standard 4-20 ma signal, I/O systems can detect a
Finding problem only if the signal is outside the 4-20 ma range, and only if it is
Problems constant; they can easily miss intermittent problems. A HART system
can periodically check the 4-20 ma signal to ensure its agreement with
the field I/O device. It detects intermittent problems and performs loop
tests whenever needed.
Critical Facts About • Traditional 4-20 mA analog signal is used for control
HART and/or monitoring.
• Digital signal carries additional information on the same
wiring.
• All HART smart devices continuously provide process data
for plant operation—24/7.
• HART provides access to all device data while the 4-20 mA
analog signal is being used for control.
• Information about the status (health) of the field device and
quality of the 4-20 mA signal is in every message.
• The Process or Primary Variable (PV) is transmitted as a 4-
20 mA signal and also as a digital value.
• Many devices have measured or calculated process
variables in addition to the PV.
• The more you communicate with HART devices, the more
value you receive from your investment.
HART Device Data Every HART device, regardless of the supplier, comes standard
with the ability to communicate 35-40 data items you can use to
improve your operations. These data items include:
• Device Identification
Instrument tag, device type, etc.
• Calibration Information
Date of last calibration
Upper & lower range value PV damping
Loop current transfer function & alarm action
Write protect status
A Choice of Migration There are many ways to benefit from the power of HART
Strategies communication and leverage the intelligence in your smart field
devices. The figures show several simple and cost-effective
migration strategies to get more from currently installed HART
equipment
Serve HART to Plant The HART Communication Foundation has developed the HART
Networks Server Tool to facilitate serving HART data to plant networks and
other high-level OPC-compliant applications. The tool provides
easy access to HART device data anywhere on a plant network.
Powerful Connections
New Products Seamlessly Connect HART Field Devices to Any Control System
In essence, HART’s value proposition is moving more data from
the process into the control system with an infrastructure you
already own, then leveraging that information to increase plant
efficiency. A range of connection options make it relatively easy.
Control Systems Get Most of the major DCS and control system vendors already have
HART HART Communication capability in their newer systems, and many
have upgrade paths for older systems. For example, in May the
Foxboro division of Invensys announced new I/A Series HART
modules. Each module can accept up to eight 4-20 mA inputs and
fully integrates HART Communication.
Clever Devices Fill If your existing DCS is not HART enabled, and if immediate plans
Gaps do not call for a new DCS or an upgrade to your DCS to make it
HART-capable, there are many other options. Signal extractors can
access portions of HART data from a device and send it to your
plant control system via 4-20 mA signals and/or discrete outputs.
The 2002 HART Plant of the Year (page S-21) makes extensive use
of Moore Industries’ SPA loop monitor and alarm. Signal extractors
like the SPA extract the HART data superimposed on a 4-20 mA
signal and retransmit virtually any combination of the process
variable values, the status and diagnostic alerts, and the device
identification information contained in the HART data.
Virtually all HMI, asset management, and soft logic software has a
built-in OPC client interface, so the HART Server Tool can be used
to connect just about any application to HART field devices. The
HART server also allows several systems to access data from a
HART device at the same time, and it can even be used to transmit
data to handheld wireless devices such as PDA’s.
Put It To Work
Take Advantage of HART Communications by Connecting Instruments
to Control Systems, Laptop PCs, or Wireless Networks
You will be happy to learn that not only is instrument information
readily available; it is downright easy to get. What’s more, you
don’t have to be a programmer. We’ll walk you through the various
options available, starting with handheld terminals and working up
to the most complex networking systems.
Calibrating Field Devices Virtually everyone who owns HART instrumentation knows how to
connect a handheld terminal to calibrate or diagnose a field device.
Essentially, you find any convenient location along the 4-20 mA
signal line—between the instrument and its termination in the
control room or remote data acquisition system—and clamp on an
adapter. The adapter is able to read the analog and embedded digital
signal without affecting the signal in any way.
Owners of the 275 HART terminals often send the unit off to the
manufacturer to have the necessary DDs loaded. This is much
easier for some plants than loading DDs locally. Fortunately, the
latest handheld terminals and PC software packages are able to load
from CD-ROMs, disks, or Internet sources, simplifying the update
process. At present, there are more than 250 unique HART
instruments from 70 vendors, all with individual DDs.
Getting Connected For a simple connection, a HART modem interface from MACTek
will connect your PC’s RS-232 port to a HART field device. The
modem connects to the 4-20 mA signal line just like the handheld
communicators, and provides an RS-232 signal containing all the
digital HART information.
Hooking Up a HART If you have more than one HART device, connecting them to your
Multiplexer control system can be done in one of two ways. The first is to run
the HART signals to a HART I/O board in your control system.
The HART device embeds the requested information into the 4-20
mA signal, and the multiplexer strips out the digital data and sends
it on to the control system. Issues to be considered with HART
multiplexers primarily involve speed. A multiplexer with 255
channels and a single modem operates much slower (on a
channelby- channel basis) than does a 32-channel multiplexer with
one modem. If a control system needs faster access to data, it can
use smaller, eight or 16-channel multiplexers, or you can purchase
multiplexers with multiple modems
Getting More Complex So far, we’ve only looked at HART networks that connect to a
single PC. Much more capability is available for a serious user. It’s
possible to connect your HART instruments into most major
networks, the Internet, and even into wireless systems.
Connecting to Controls HART devices can connect directly to control systems and devices,
allowing users to make use of instrument data for monitoring,
alarming and control purposes. Allen-Bradley, Wickliffe, Ohio,
provides a HART interface module for its PLC 5 and SLC
programmable controllers that allows a PLC to see HART data.
Installed as a remote I/O device, the module acquires data from a
HART instrument, strips out the HART signals, and puts the data
into a format that can be addressed by ladder logic programming.
Pat Moyer, product manager at A-B, explains that the system is
Here’s a step-by-step procedure for getting started with the HART Server. This
By the Numbers
should get you up and running in a matter of just a few minutes:
1. Load and install the HART Server software on your PC. You can
download it from the Internet or load it from a CD-ROM.
2. Configure your PC’s COM port to communicate with the HART
network. You need to tell the PC port if it will be seeing RS-232, RS-
485, or RS-485 with an Ethernet adapter. The HART Server
configuration screens help you do this.
3. Configure the HART Server to set up links between the data sources
and the data users (what programs want to see what data?). Again, the
HART Server configuration screens ask the right questions.
4. Verify and test the HART Server using the GnHost diagnostic
software tool, supplied by the HART Foundation.
Most of the configuration menu screens are similar to Windows Explorer. With a
series of mouse clicks, you should be able to complete the configuration quickly.
The HART Server will automatically detect and learn the HART devices
connected to the port. At the end of the configuration process, two-way
communication between the HART Server and the HART instruments will be fully
established. The HART Server pass-through software lets OPC client applications
send HART commands to HART instruments. Therefore, any software such as
configuration or valve analysis packages that run on handheld terminals can run on
a PC equipped with HART Server.
Likewise, HMI and SCADA software can access data using standard OPC
functions. The OPC client browses the data items available from the server and
subscribes to the data items of interest. This is a standard OPC function that is
supported by all software packages that claim to be OPC clients or servers, such as
HMI/SCADA systems. When you get the HART system connected to the HART
Server, simply go to the part of your HMI or SCADA system that defines I/O
points. You will be adding the HART instruments the same way you configured
your plant when you first installed the HMI/SCADA system: that is, you’ll
probably use a menu-based configuration screen to define the path, device, tag
name, and so on, and your HMI/SCADA system will lead you through the process.
You will also be able to define how often you want each parameter or groups of
parameters updated, or “turned on.” When a group is turned on, the HART Server
will publish the data items (i.e., update, acquire, and send the group to the client).
This allows processing packages from loop controllers to process historians to
obtain instrument information from the field as often as necessary, simply by
making the appropriate definitions in an OPC software package
Using Specialty Several HART instrument vendors have developed specialty
Devices processors and loop monitors that perform unique diagnostic and
analysis functions. In many cases, this allows you to take advantage
of the information contained in your HART instruments without
making a network connection or using PC software. In other words,
you can solve local problems without involving the plant’s main
control system.
But how do you get to this data, and what do you do with it? You
can install a HART loop monitor to monitor any of these variables,
and to sound an alarm if it sees a condition that could result in
dangerous process upsets. For example, excess friction in a valve
can lead to surging conditions. Loss of actuator pressure from a
clogged air filter or torn diaphragm can cause a dangerous or costly
control offset. A loop monitor can be set to alarm on any of these
conditions.
Control systems that are not fitted with a HART modem and HART
Server cannot obtain any data other than the 4-20 mA signal from
HART instruments. Here, loop monitors can serve as an
intermediary. For example, Moore Industries’ SPA monitor can
read all the data from a HART device, extract digital data, and
produce additional signals (Figure 4). It provides up to four
independent relay outputs that can be used as alarms when process
conditions fall outside of user-selected high or low limits. It can
also pick off any of the four dynamic (analog) variables from the
HART data and transmit it to the control system as a 4-20 mA
signal. For example, it could take the density value from a Coriolis
flowmeter, the stem position for a valve, or it can calculate an
analog variable as a function of two or more other variables.
The best part is that all this diagnostic, status, and operations
information has been available all this time, so it requires no
additional investment by end users. All they have to do is go get it
with handheld devices, multivariable loop monitors, or PCs and
HART Servers.
Although HART has been available for 15 years, like Ethernet it is showing no
HART Marches On
signs of getting old. The current version is HART 5, but HART 6 has recently been
approved by the foundation’s members.
“HART 6 is an augmentation of the existing standard that allows the installed base
to continue while incorporating new features,” says Ben Cianfrone, engineering
development manager, Fluke Corp., Everett, Wash. “We will be able to use this for
at least 10 or 15 more years, or even longer.”
The upgrade was necessary because HART instruments are getting smarter all the
time, incorporating more self-diagnostics, saving more operational history data,
and reporting on the quality of the data they obtain. Someday, HART devices may
even have other HART devices embedded within, such as flow computers and
multi-channel temperature monitors. HART 6 makes all this possible, without
making any previous HART instruments obsolete.
Some of the new functions include Extended Device Status, which alerts users to
situations such as, “device needs maintenance;” Device Variable Status, which
allows field devices to self-validate and provide quality indicators on process data
(good, poor, bad, fixed); Long Tags, which allows international characters and
longer tag names; Configuration Change Counter, which determines if a field
device configuration has been changed; and Block Data Transfer, which moves
large blocks of data between masters and field devices. The new spec should be
available for all to review at the ISA Show in September.
Three main factors led the judges to select this DuPont application
as this year’s winner. First, the plant uses the power of HART even
though it does not have a HART-enabled control system. Second,
HART Communication is used full-time in daily operations.
Finally, the plant is migrating to using HART information for
additional cost-effective solutions that deliver significant benefits to
the enterprise today and into the future.
One of the main reasons DuPont selected the SPA instrument is that
Moore Industries submitted the SPA to an independent third party
for failure modes, effects, and diagnostic analysis (FMEDA).
“FMEDA is a detailed circuit and performance evaluation that
estimates the failure rates, failure modes, and diagnostic capabilities
of a device,” explains Bud Adler, director of business development
with Moore Industries. “Using the reliability data from the SPA’s
FMEDA report, DuPont is able to verify that required safety
integrity levels (SILs) are attained.”
HART Increases TiO2 production involves many critical and potentially hazardous
Uptime processes, so reliable operation of the safety shutdown systems is of
paramount concern. DuPont uses HART to provide key safety
interlock inputs to the DCS and to the hard-wired relay system.
The DCS compares the valve control output signal to the HART
valve-stem position data to ensure proper positioning. This data is
used to verify correct functioning of the valve in normal operations,
and to test the valve when DuPont performs periodically required
plant shutdowns to verify operation of the safety shutdown system.
Online Tests Reduce DuPont has plans to take valve testing to another level—a level that
Outages will reduce the number and lengths of outages required for safety
interlock testing. Certain valve testing requirements for safety
interlock systems can be met with partial valve-stroke testing of
emergency shutdown valves during normal operations. Performing
those tests during normal operations means fewer shutdowns are
required, and the required tests take less time so the shutdowns can
be shorter.
Get Started
The preceding articles have shown how HART is much more than
just a way to calibrate flowmeters. It provides an enormous amount
of plant-floor information not obtainable through any other means,
and you don’t need a complicated fieldbus system to get to that
data. In fact, since most of your instruments, valves, and controllers
already have a HART interface, obtaining real-time process
information is not only easy, it is very inexpensive. All you need to
do is learn how to use it.
All this vendor activity is useful and helpful, but what the industry
really needs is a better and more consistent way to teach end users
about HART.
Regarding Users in a The HART Communication Foundation (HCF) has been strictly a
New Light vendor group since its founding in 1993. During that time, HCF left
all the end user promotion to the marketplace while it concentrated
on helping the vendors design and develop new instruments,
software, interfaces, calibrators, and similar devices. All of HCF’s
educational efforts and training classes have been designed for
vendors, and all of its efforts toward standardization have been
aimed at solidifying and enhancing HART products.
It’s accomplished that, in spades. Today, HCF has more than 130
vendor members all over the world that offer a large number and
variety of HART-compliant products (Figure 1). Virtually every
process instrument built today has a HART interface. In spite of all
the publicity garnered by the various fieldbuses, the fact remains
that HART has the largest installed base in the industry, and it is
growing every day. This is in part because many fieldbus-
compatible instruments and devices also have a HART interface.
Fieldbus users may discover they actually have two plant networks
built into their devices: fieldbus and HART.
Educational Support Learning more about networking and HART Servers is a little bit
beyond a five-minute phone call from the rep. You need training
and non-vendor technical literature. HCF understands. Here’s what
they have in store for you:
available for free from HCF, and you should be able to get a copy at
the HART Foundation booth at the ISA or Interkama shows this
year. To obtain a free copy via the Internet, go to the HCF web site
(see next bullet). You can also call the HCF office in Austin, Texas.
To find out more about specific dates and times, contact HCF or
visit the web site.
After HCF runs the pilot classes, it plans to finalize the training
materials so that users will be able to conduct classes themselves.
This will put training out in the field, closer to end users.
Coming on Board The HCF also realizes that end users will determine the future of
HART. Already, many experienced users are asking for additional
capability and functions. Although HART has been available for 10
years for field communications, it is just now entering the early
adopter step in its lifecycle as a networking system. At this point in
HART development, user input is critical.
Industry Applications
Many companies in a wide variety of industries have already realized the
advantages of using the HART communication protocol. This section
describes some applications in detail and outlines the tangible benefits that
result. The applications have been grouped into the following sections:
T Inventory-management applications
T Cost-saving applications
T Remote-operation applications
T Open-architecture applications
Inventory-Management Applications
Accurate measurements for inventory management are essential in all
industries. The HART communication protocol enables companies to make
sure inventory management is as efficient, accurate, and low cost as
possible.
HART MULTIDROP Tank level and inventory management is an ideal application for a HART
NETWORK FOR multidrop network (Figure 19). The HART network digital update rate of
two PVs per second is sufficient for many tank-level applications. A
TANK LEVEL AND multidrop network provides significant installation savings by reducing the
INVENTORY amount of wiring from the field to the control room as well as the number
MANAGEMENT of I/O channels required. In addition, many inexpensive
process-monitoring applications are commercially available to further cut
costs.
Transmitters
Storage
Tanks
HART Field
Multiplexer
One company uses a HART multiplexer to digitally scan field devices for
level-measurement and status information. The information is forwarded to
the host application using the Modbus communication standard.
Multivariable instruments further reduce costs by providing multiple
process measurements, such as level and temperature, which reduces the
wiring and number of process penetrations required.
Inventory-Management Applications
MULTIDROP FOR In one tank farm application, 84 settlement tanks and filter beds on a very
TANK FARM large site (over 300,000 m2) are monitored using HART multidrop
networks and HART RTUs (see SCADA/RTU Systems on page 25). The
MONITORING HART architecture required just eight cable runs for 84 tanks, with 10–11
devices per run (Figure 20). Over 70 individual runs of over 500 m each
were eliminated. Cable savings were estimated at over $40,000 when
compared to a conventional installation. RTU I/O was also reduced, which
resulted in additional hardware and installation savings. The total installed
cost was approximately 50% of a traditional 4–20 mA installation.
Storage
Storage Tanks
Tanks
Inventory-Management Applications
UNDERGROUND Underground salt caverns are frequently used for crude oil storage. One
PETROLEUM customer pumps oil from barges into the storage caverns. An ultrasonic
flowmeter records the total flow. To get the oil out of the caverns, a brine
STORAGE WITH solution is pumped into the cavern through a magnetic flowmeter. Brine
HART and crude oil flowing in both directions are measured and reported to the
COMMUNICATION DCS using the HART communication protocol for accuracy. The DCS
tracks flow rate and total quantity to maintain a certain pressure inside the
FOR ACCURACY
caverns (Figure 21).
HART Transmitter
Interface
HART Transmitter
Interface
Cost-Saving Applications
Use HART multidrop networking to reduce
installation and maintenance costs.
Cost-Saving Applications
APPLIANCE A consumer appliance manufacturer used the networking capability of the
MANUFACTURING HART protocol to measure level, flow, and pressure. HART multidrop
provided substantial wiring and installation savings as well as digital
WITH MULTIDROP accuracy with the elimination of the analog to digital (A/D) and digital to
analog (D/A) conversions of the instrument and PLC I/O. Figure 22 shows
pressure transmitters connected to a PLC via smart transmitter interface
multiplexers.
Storage
Tanks
Highway
PLC
Communication
Module
Cost-Saving Applications
REMOTE The benefits of remote monitoring and rezeroing of smart transmitters
REZEROING IN A using the HART protocol are dramatically illustrated in this example of two
smart transmitters that control the fluid level in lauter tubs in a brewhouse
BREWERY application. Similar benefits would be realized in any application involving
a closed vessel.
Two smart transmitters are installed on each lauter tub—one on the bottom
of the tank and the other about nine inches from the bottom. The bottom
transmitter is ranged ±40 inH2O; the upper transmitter is ranged
0–30 inH2O. As the lauter tub is filled, the bottom transmitter senses level
based on pressure. When the level reaches the upper transmitter, that point
is marked as the new zero-level point, and the upper transmitter becomes
the primary sensing instrument for the lauter-tub level. The nine-inch
zero-level offset from the bottom of the tank is necessary to accommodate
loose grain that settles in the bottom of the tank.
Transmitters that are coordinated and working together control fluid level
in each lauter tub to within a few barrels. However, the upper transmitter
requires periodic maintenance or replacement and rezeroing. An undetected
false upper-transmitter level reading can cause a tank level error of up to
40 gallons.
The usual procedure for transmitter rezeroing takes about 95 minutes and
has been required as frequently as twice a day. Rezeroing a transmitter
using configuration software and PLC interface modules eliminates the
need to locate and identify the problem at the site as well as the need for
verification by control-room personnel and greatly reduces the chance for
inadvertent errors. Estimated total time to rezero each transmitter is
reduced to 15 minutes.
Through the configuration software’s instrument-status and diagnostic
capabilities, a false level indication can be automatically detected while a
lauter tub fill is in progress. The affected transmitter can then be
automatically rezeroed by programming logic in the programmable
controller to issue the appropriate command to the instrument.
Cost-Saving Applications
WATER TREATMENT HART transmitters and a control system with HART capability were
FACILITY UPGRADE chosen to upgrade a water treatment facility. The completed installation
reduced capital, engineering, and installation costs. The process dynamics
of the water treatment facility allowed the HART instruments to be used in
all-digital mode without compromising plant performance.
The water treatment plant is divided into two areas, each with 14 filters.
Each area is controlled by a separate control system for complete
autonomy. A HART network monitors each filter for filter level, filter bed
differential, and filter outlet flow. The multidrop installation used a
three-wire system in order to accommodate both the two-wire and the
four-wire devices (magnetic flowmeters) in use (Figure 23)
(see Multidrop on page 6).
4 mA Pressure
Transmitters
12 mA Main
Power
Magnetic
Flowmeter
4 mA
Cost-Saving Applications
IMPROVED A cleaning materials supplier required periodic checkup of the instrument
DIAGNOSTICS condition and configuration information as compared to the initial
installation. The field transmitters provided a historical record of status
changes along with current configuration information. Periodic download
of this information was made possible using PLC ladder logic developed
for HART instruments.
Remote-Operation Applications
UNMANNED Choosing the HART communication protocol for all-digital communication
OFFSHORE GAS in a wide-area network enabled one company to have real-time monitoring
and control, access to diagnostics, and maintenance capabilities—all from a
PRODUCTION WITH remote location.
HART NETWORKS
Over half of the 500 transmitters on 15 platforms could be multidropped
with update rates of three seconds (six devices), which resulted in
substantial savings in wiring, I/O, and installation. The remaining devices
(flowmeters) required a faster response and were wired point to point using
digital HART communications to transmit the process data. The flowmeters
used the optional burst mode, which provided an update rate of 3.7 times
per second. All-digital communications provided maximum accuracy and
eliminated potential errors from input scaling, conversion, and drift (see
Multidrop on page 6).
Radio Antennae
Modbus Link
HART
Multiplexers
Transmitters
Transmitters
Remote-Operation Applications
VENEZUELA In a Venezuela gas-lift project, HART multidrop technology was used for
GAS-LIFT PROJECT remote operation of offshore gas-lift production wells at considerable
savings (Figure 25):
T 30% decrease in installation costs
T 16:1 reduction of input modules
T Reduced cost of I/O cards in the RTU
T Remote reranging
T Remote access to the transmitter status for improved process uptime
Configuration
and
Maintenance
Tools
Control
Room
Electric Valve HART Transmitters
Open-Architecture Applications
OIL REFINERY The best way to judge the openness of a communication protocol is by the
EXPANSION number of products supported. By this standard, the HART protocol is
perhaps the most open of any field-communication protocol available
today.
In a major refinery expansion, an oil company weighed the advantages of
using either a proprietary system or a HART-based system. The results
indicated that the company could use HART digital instruments in 92% of
their applications, compared to only 33% with the proprietary system.
Choosing HART products resulted in an incremental $23,000 in savings
due to commissioning efficiencies and ongoing maintenance and diagnostic
capabilities.
The oil company used a traditional control system with analog I/O and
supplemented the control capability with an online maintenance and
monitoring system. All of the HART field devices were monitored from a
central location (Figure 26).
Controller
HART
Transmitter Control Valve
Fisher
Fisher
Open-Architecture Applications
HART WITHIN A HART field devices can be seamlessly integrated with PROFIBUS DP
PROFIBUS networks using the HART/DP Link, which enables the connection of four
HART devices and facilitates the passthrough of HART commands to host
NETWORK applications on the DP network (Figure 27). The HART/DP Link supports
IS installations.
PLC
PROFIBUS
DP
Profibus
PA
HART
Instruments
Open-Architecture Applications
HART/DDE Cost-effective level- and temperature-monitoring systems can be designed
SERVER using HART multidrop networks and commercially available HART/DDE
interface software. HART/DDE interface software allows any compliant
application (e.g., spreadsheet) to directly read the process data and status
information available in HART field devices. A HART interface module
connected to the PC’s serial port is needed for this HART monitoring
application (Figure 28).
Spreadsheet
Data Logging
RS232 HART
Interface
Power Supply
Transmitter
By Phone
Call 512-794-0369.
By Fax
Send correspondence to 512-794-3904.
By E-mail
Send correspondence to <[email protected]>.
Online
Visit the HCF website at <http://www.hartcomm.org>.
Some systems have the ability to act as a conduit or router between a software application running on a
separate platform and a HART field device. In effect, this ability gives the end user the functionality provided both
by the system and by the application.
Is passthrough supported? ❐ Yes ❐ No
If this is a system, what applications are
available with passthrough?
0 "254" (expansion)
1 Manufacturer identification code
2 Manufacturer device type code
3 Number of preambles required
4 Universal command revision
0 Read unique identifier None
5 Device-specific command revision
6 Software revision
7 Hardware revision
8 Device function flags* (H)
9–11 Device ID number (B)
0 PV units code
1 Read primary variable None
1–4 Primary variable (F)
0
6 Write polling address Polling address As in command
(truncated after last requested code) (truncated after last requested variable)
38 Reset "configuration
None None
changed" flag
0 PV transmitter variable
code
1 SV transmitter variable
51 Write dynamic variable code
As in command
assignments 2 TV transmitter variable
code
3 FV transmitter variable
code
0 Transmitter variable
53 Write transmitter variable code
As in command
units 1 Transmitter variable units
code
0 Transmitter variable
code
55 Write transmitter variable
1–4 Transmitter variable (F) As in command
damping value
damping value
(seconds)
0 Transmitter variable
56 Write transmitter variable code
As in command
sensor serial number 1–3 Transmitter variable
sensor serial number
(truncated after last requested code) (truncated after last requested level)
0 Transmitter variable
code for slot 0
1 Transmitter variable
107 Write burst mode
code for slot 1
transmitter variables (for As in command
2 Transmitter variable
Command #33)
code for slot 2
3 Transmitter variable
code for slot 3
0
Burst mode control code
109 Burst mode control As in command
(0 = exit, 1 = enter)
0 PV units code
1–4 PV value (F)
5 SV units code
6–9 SV value (F)
110 Read all dynamic variables None
10 TV units code
11–14 TV value (F)
15 FV units code
16–19 FV value (F)
RESPONSE CODES
First Byte
Note: Hexadecimal equivalents are quoted assuming only a single bit is set. In reality, several bits may
be set simultaneously, and the hex digits can be or’ed together.
Power
Supply Handheld
Terminal
DVC:FCV101B DVC:FCV101B
Fisher Dig Vlv Ctrl Fisher Dig Vlv Ctrl
1 Main 1 Main
2 Analog In 12.13 mA 2 Analog In 12.13 mA
3 Travel 50.36 % 3 Travel 50.36 %
4 Drive Sgl 31.54 % 4 Drive Sgl 31.54 %
5 Instrument Status 5 Instrument Status
F1 F2 F3 F4
F1 F2 F3 F4
4-20 mA
HART Communicator HART Communicator
Valve
Positioner
A B C D E F G H I
A B C D E F G H I
7 8 9 7 8 9
J K L M N O P Q R
J K L M N O P Q R
4 5 6 4 5 6
S T U V W X Y Z /
S T U V W X Y Z /
3 2 1 3 2 1
Power
Supply
DVC:FCV101B
Fisher Dig Vlv Ctrl
DVC:FCV101B
Fisher
Fisher Dig Vlv Ctrl
1 Main 1 Main
2 Analog In 12.13 mA 2 Analog In 12.13 mA
3 Travel 50.36 % 3 Travel 50.36 %
4 Drive Sgl 31.54 % 4 Drive Sgl 31.54 %
5 Instrument Status 5 Instrument Status
F1 F2 F3 F4
F1 F2 F3 F4
Invalid
Connection
A B C D E F G H I
A B C D E F G H I
7 8 9 7 8 9
J K L MN O P Q R
J K L M N O P Q R
4 5 6 4 5 6
S T U V W X Y Z /
S T U V W X Y Z /
3 2 1 3 2 1
Handheld
0 . -
Terminal or PC
Interface
Data integrity:
T Two-dimensional error checking
T Status information in every reply message
SIMPLE COMMAND
STRUCTURE Type of Command Structure
Universal Common to all devices
Common practice Optional; used by many devices
Device specific For unique product features
Glossary
275 HART A handheld master device that uses the HART communication protocol and
Communicator DDL to configure or communicate with any HART smart device
Bell 202 A U.S. telephone standard that uses 1,200 Hz and 2,200 Hz as 1 and 0,
respectively, at 1,200 baud; a full duplex communication standard using a
different pair of frequencies for its reverse channel; HART uses Bell 202
signals but is a half-duplex system, so the reverse channel frequencies are
not used
Burst (Broadcast) Mode A HART communication mode in which a master device instructs a slave
device to continuously broadcast a standard HART reply message
(e.g., value of a process variable) until the master instructs it to stop
bursting
Cable Capacitance Per The capacitance from one conductor to all other conductors (including the
Unit of Length shield if present) in the network; measured in feet or meters
Cable Resistance Per The resistance for a single wire; meausred in feet or meters
Unit of Length
Closed-Loop Control A system in which no operator intervention is necessary for process control
Communication Rate The rate at which data are sent from a slave device to a master device;
usually expressed in data updates per second
Device Description A program file written in the HART Device Description Language (DDL)
that contains an electronic description of all of a device’s parameters and
functions needed by a host application to communicate with the device
Glossary
Field The area of a process plant outside the control room where measurements
are made, and to and from which communication is provided; a part of a
message devoted to a particular function (e.g., the address field or the
command field)
Field Device A device generally not found in the control room; field devices may
generate or receive an analog signal in addition to the HART digital
communication signal
Frequency Shift Keying Method of modulating digital information for transmission over paths with
poor propagation characteristics; can be transmitted successfully over
telephone systems
HART Command Set A series of commands that provide uniform and consistent communication
for all master and slave devices; includes universal, common practice, and
device-specific commands
HART Loop A communication network in which the master and slave devices are
HART smart or HART compatible
Host Application A software program used by the control center to translate information
received from field devices into a format that can be used by the operator
Intrinsic Safety Barrier A network or device designed to limit the amount of energy available to the
protected circuit in a hazardous location
Glossary
Master Device A device in a master-slave system that initiates all transactions and
commands (e.g., central controller)
Master-Slave Protocol Communication system in which all transactions are initiated by a master
device and are received and responded to by a slave device
Miscellaneous Series The summation of the maximum impedance (500 Hz–10 kHz) of all
Impedance devices connected in series between two communicating devices; a typical
nonintrinsically safe loop will have no miscellaneous series impedance
Multidrop Network HART communication system that allows more than two devices to be
connected together on a single cable; usually refers to a network with more
than one slave device
Multimaster Multimaster refers to a communication system that has more than one
master device. The HART protocol is a simple multimaster system
allowing two masters; after receiving a message from a slave device, the
master waits for a short time before beginning another transmission, which
gives the second master time to initiate a message
Multiplexer A device that connects to several HART loops and allows communication
to and from a host application
Multivariable Instrument A field device that can measure or calculate more than one process
parameter (e.g., flow and temperature)
Parallel Device The summation of the capacitance values of all connected devices in a
Capacitance network
Parallel Device The parallel combination of the resistance values of all connected devices
Resistance in the network; typically, there is only one low-impedance device in the
network, which dominates the parallel device-resistance value
PID Proportional-integral-derivative
Glossary
Point to Point A HART protocol communication mode that uses the conventional
4–20 mA signal for analog transmission, while measurement, adjustment,
and equipment data are transferred digitally; only two communicating
devices are connected together
Polling Address Every HART device has a polling address; address 0 is used for
point-to-point networks; addresses 1–15 are used in multidrop networks
Process Variable A process parameter that is being measured or controlled (e.g., level, flow,
temperature, mass, density, etc.)
Remote Terminal Unit A self-contained control unit that is part of a SCADA system
Slave Device A device (e.g., transmitter or valve) in a master-slave system that receives
commands from a master device; a slave device cannot initiate a transaction
Supervisory Control and A control system using communications such as phone lines, microwaves,
Data Acquisition radios, or satellites to link RTUs with a central control system