Pro Em235 PM335 - 0
Pro Em235 PM335 - 0
BG0612 Rev. A6
Always open or disconnect circuit from power-distribution system (or service) of building
before installing or servicing current transformers.
Secure current transformer and route conductors so that they do not directly contact live
terminals or bus.
Ensure that all incoming AC power and other power sources are turned OFF before
performing any work on the instrument. Failure to do so may result in serious or even fatal
injury and/or equipment damage.
Before connecting the instrument to the power source, check the labels at the front of the
instrument to ensure that your instrument is equipped with the appropriate rating input
voltages and currents.
Under no circumstances should the instrument be connected to a power source if it is
damaged.
Any use or operations not specified by this manual may cause a protection impairment to
the device.
To prevent potential fire or shock hazard, do not expose the instrument to rain or moisture.
While installing HACS to the secondary of an external third party current transformer, the
external current transformer secondary output must never be allowed to be open circuit
when the primary is energized. An open circuit can cause high voltages, possibly resulting in
equipment damage, fire and even serious or fatal injury. Ensure that the current transformer
wiring is secured using an external strain relief to reduce mechanical strain on the screw
terminals, if necessary.
Only qualified personnel familiar with the instrument and its associated electrical
equipment must perform setup procedures.
Do not open the instrument under any circumstances when it is connected to a power
source.
Do not use the instrument for primary protection functions where failure of the device can
cause fire, injury or death. The instrument can only be used for secondary protection if
needed.
This equipment does not require cleaning for proper operation
This equipment is not intended to be directly connected to medium and high voltage power
lines, only using Listed Energy-Monitoring Current & Voltage Transformers, certified for this
purpose.
Read this manual thoroughly before connecting the device to the current carrying circuits.
During operation of the device, hazardous voltages are present on input terminals. Failure to
observe precautions can result in serious or even fatal injury or damage to equipment.
Features
The compact PRO Series meter is available as the PM335 panel mount (4-inch round /
92x92mm square cutouts) form factor design and the EM235 DIN-rail form factor design.
This series combines metering and control in one device, providing the ultimate solution for
substation / industrial automation and commercial energy management.
The PRO meters combine and bundle in one physical IED multiple features which ordinarily
would be found in several different pieces of equipment.
Primarily designed for integration in the substation substation, it is well suited for a wide
range of industrial applications, over a wide range of input currents whenever extensive
power monitoring is required.
The EM235/PM335 PRO series combins in a single compound device:
• Up to 26 external inputs, triggered by external sources; onboard zero-sequence
currents and volts, current and voltage unbalance; coincident volt magnitude, fault
waveforms and fast RMS trace; cross triggering between multiple devices via digital
inputs for synchronous event capture and recording.
• Event recorder for logging internal diagnostics events, control events and I/O
operations.
• Eight Fast Waveform recorders: 8-channel simultaneous recording; selectable AC
sampling rate of 32, 64, 128 or 256 samples per cycle; 20 pre-fault cycles; synchronized
waveforms from multiple devices in a single plot; exporting waveforms in COMTRADE
and PQDIF file formats (via PAS software).
• Thirteen Fast Data recorders: 1/2-cycle to 2-hour RMS envelopes; programmable data
logs on a periodic basis and on any internal and external trigger; triggering from PQ
recorder or control setpoints; exporting data trends in PQDIF file format (PAS).
• Three Special Data Recorders withfixed parameters: TOU Monthly Profile data log &
TOU Daily Profile data log. These data logs are read only.
• Embedded Programmable Controller: 64 control setpoints, OR/AND logic, extensive
triggers, programmable thresholds and delays, relay control, event-driven data
recording, cross triggering between multiple devices via ethernet for synchronous event
capture and recording – up to sixteen triggering channels.
• High-Class 3-phase Power meter: true RMS, volts, amps, powers, power factors,
unbalance, and neutral current.
• Class 0.2S IEC per 62053-22 / Class 0.2 per ANSI C12.20; four-quadrant active and
reactive energy polyphase static meter
• Demand Meter: amps, volts, harmonic demands.
• Precise Energy and Power Demand Meter: Time-of-Use (TOU), 16 Summary
(totalization) and TOU energy and demand registers for substation energy
management; accumulation of energy pulses from external watt-meters; block and
sliding demands; up to 64 energy sources.
• Harmonic Analyzer: up to the 63rd harmonic volts and amps; directional power
harmonics and power factor; phasor, symmetrical components.
• 32 digital counters for counting pulses from external sources and internal events.
• 16 programmable timers from 1/2 cycle to 24 hours for periodic recording and triggering
operations on a time basis.
• 1-ms satellite-synchronized clock
• Network time synchronization (SNTP)
• Backup/AUX power supply unit.
• 3 slots for plug-in I/O / COM modules.
• TCP notification client for communicating with a remote MODBUS/TCP server on
events or periodically on a time basis, with any IP enable communication port
• 16GB Memory for long-term waveform and data recording.
• Real Time Clock: Internal clock with backup battery for five years Real-Time Clock
retention time
Communications Interfaces
Built-in communication ports
• One serial communications port; RS-485, up to 115,200 bps, supporting MODBUS
RTU/ASCII, DNP3.0 and IEC 60870-5-101 protocols
• Infrared port; up to 19200 bps, supporting MODBUS RTU/ASCII, DNP3.0 protocols and
IEC 62056-21
• 2 Built-in ethernet 10/100Base-T ports (dual port ethernet) supporting MODBUS/TCP,
DNP3.0/TCP, IEC 60870-5-104 protocols and IEC 61850 Ed2 protocol, up to 10 non-
intrusive simultaneous connections per ethernet port (2 reserved for Expert power
communiation)
• Daisy chain capability with RSTP support or 2 independent Ethernet port. The Meter
supports as default 20 chained connected devices
• USB 2.0 port (type C), supporting MODBUS RTU protocol
• See below
Displays options
The EM235/PM335 PRO SERIES can be ordered with a super bright LED Remote Display
Module (PM330 PRO) or an LCD Graphical Module (PM335/EM235 ).
PM335 PRO
The PM335 PRO is equipped with a 3.5’ TFT color graphics LCD display with extensive
dialog capabilities, allowing the user to view different fault and power quality information in a
graphical form, such as waveforms, harmonic spectrum, phasors and data trends, review
latest fault and power quality reports for fast fault analysis, and much more, using five
buttons.
In addition the PM335 PRO is equipped with two communication ports: USB and IR, for
monitoring and configuration, green led for CPU OK and red led for energy led pulse rate in
test mode. Three-color load bar LED.
PM235 PRO
The PM235 PRO is equipped with a 1.77’ TFT color graphics LCD display with extensive
dialog capabilities, allowing the user to view different fault and power quality information in a
graphical form, such as waveforms, harmonic spectrum, phasors and data trends, review
latest fault and power quality reports for fast fault analysis, and much more, using four
buttons.
In addition the PM235 PRO is equipped with two communication ports: USB and IR, for
monitoring and configuration, green led for CPU OK and red led for energy led pulse rate in
test mode.
Upgradeable Firmware
The EM235/PM335 PRO SERIES uses mass storage memory for storing device firmware.
This allows upgrading of your device without replacing hardware components. New features
can be easily added to your device by simply replacing firmware through any communication
port.
The firmware name is built of four different fields to define the version as described below:
EM235: V40.XY.ZZ.zz
PM335: V44.XY.ZZ.zz
Where:
X represents new features set version - current version is 0 (none)
Y represents metrology version 1 - current version is 1
ZZ represents minor version, this version number is incremented after each
release - current version is 3
zz represents build version, last firmware compilation version - current
version is 20.
1 Metrology version is not affected by any of other fields version – features set, minor and build versions
Meter Security
The EM235/PM335 PRO SERIES provides 3-level password security for protecting meter
setups and accumulated data from unauthorized changes. Meter readings are not software
protected.
Access to particular setup and control items is granted depending on the security level of the
password you entered. The passwords can be 1 to 8 digits long.
The EM235/PM335 PRO SERIES is also equipped with terminal connections sealed cover
to avoid unwanted electrical connections.
Table 1: Security Level and User access
Password Security
The setup menus are secured by 8-digit user passwords. Every time you enter programming
mode, you are prompted for a correct password. The meter is primarily shipped with all
passwords preset to “9” at the factory. See Meter Security in Chapter 2 for more information
on the meter security levels.
It is recommended that you change the factory set passwords as fast as possible to protect
your setups and accumulated data from unauthorized changes. See Configuring Meter
Passwords in Chapter 5 on how to change passwords in your meter.
Enter the password as you enter numeric values. As you move to the next place, the digit
entered is saved and then zeroed. If you missed a digit, you should re-type all preceding
digits before you reach the missed place again.
Once the password is set to the desired value, press and hold the SELECT/ENTER button
for more than 1 second. If the password you entered is correct, you move to the main device
menu, otherwise you return back to the data display.
NOTE
Access to the Reset menu entries is allowed depending on your security level as shown in
Section Reset of Accumulators and Log Files in Chapter 6.
If your security level does not allow access to a menu, it will not be listed in the main menu
list, and you will not be able to highlight menu items that you are not allowed to change, but
you can still view their present settings.
The PTS converts the high voltage and current to a small voltage signal instead of the
normal 120 Volt and 5 Amp outputs of standard CTs and PTs. Based on SATEC Model Pro
Series-Power Quality / Energy Meter to fully interface with the low level sensor outputs for
line voltage and current.
Full measurements and data can be obtained from the Pro Series, including waveform,
harmonics, logs etc.
PRO meter shall be installed in an electrical cabinet according all safety requirements
NOTE:
The Pro Series meter in the PTS PRO MV Advanced Analyzer is factory setup as follows:
• Wiring mode: 4LL3
• CT Primary current (A): 300
• PT ratio:
- For 15kV: 22.5
- For 25kV: 53.1
- For 35kV: 160.9
• PT multiplier: x1
Each Pole Top Sensor set includes the manufacturer test report showing V & I gain linearity
and phase shift results, this information must be applied to the PRO meter through the
General Setup\Instrument Transformer Correction menu using PAS.
Supplemental Documents
• BG0613 EM235/PM335 PRO SERIES MODBUS Reference Guide
• BG0614 EM235/PM335 PRO SERIES DNP3 Reference Guide
• BG0615 EM235/PM335 PRO SERIES IEC60870-5 Reference Guide
• BG0619 EM235/PM335 PRO SERIES IEC61850 Reference Guide
• BG0337 PAS Getting Started Guide
Measured Parameters
Table 2: Measured and Displayed Parameters
Chapter 2 Installation
This chapter discusses the following types of physical installations for the EM235/PM335
PRO SERIES:
• Mechanical Installation
• Electrical Installation
• I/O Connections
• COM Port Connections.
Site Requirements
• Environmental conditions: as specified in Technical Specifications in Chapter 14
• Electrical requirements: as specified in Technical Specifications in Chapter 14
• See Technical Specifications in Chapter 14 for more details
Package Contents
The EM235/PM335 PRO SERIES package contains the following items:
• EM235/PM335 PRO SERIES unit
• Quick Start guide
• Optional accessories (depending on the options ordered, if any)
Mechanical Installation
Refer to the figures provided in this section to properly perform the mechanical installation.
Panel Mounting
To mount the meter in cutout (ANSI 4" round or DIN 92x92mm square cutout) switchgear
panel with width range of 1.0mm (0.04”) to 6.4mm (1/4”):
Position the Display unit in the
Panel cutout.
Affix the meter using the 4 screws
supplied.
Observe orientation !!
Snap and connect the main unit to
the mounted display unit .
Now the instrument is ready for
wiring .
113.40
108.70
91.5
108.70
44.80 20.40
60.00
91.50
Module mounting
Ensure that all incoming power sources are shut OFF before
installing a module. Failure to observe this practice can result in
serious or even fatal injury and damage to equipment.
Remove Module
connector cover before
assembling module
Electrical Installation
Note:
Typical Installation
PC1
RS-485
– +
RS-485
Line (+)
120/250 AC/DC (150mA max)
N (–)
SENSOR
LOAD
-
+
EM235
Up to 31 devices
SHORTING SWITCHES
LINE AC or DC(+)
N or DC (-)
SW1
2A
I4+ I4-
SW2 SHORTING SWITCHES
40-290V AC/DC 2A
L1
L2
L3 LOAD
N
Figure 2-9b EM235 Typical Installation Diagram
Only qualified personnel familiar with the instrument and its associated electrical equipment
must perform installation and setup procedures.
The equipment installation shall conform to the following
instructions:
a) Circuits Breakers (AC and DC) in the PTS PRO must
be "OFF"
b) HV Arresters must be installed closed to the PTS on
the MV lines.
c) HV Arresters and PTS must be directly grounded to
earth
d) The PTS PRO MV Analyzer must be directly grounded
to earth
Conductor size
Torque
Terminals PRO Minimum Maximum Notes
model [Nm]
AWG (mm²) AWG (mm²)
Aux. Power ALL 22 (0.5) 12 (2.5) 0.5-0.7 Use 600V insulated
Supply Inputs conductors
L/+, N/- Required crimped
ferrule:
Panduit (22AWG) F75-
10-M
Panduit (12AWG) F81-
10-M
Voltages Inputs ALL 22 (0.5) 12 (2.5) 0.5-0.6 Use 600V insulated
V1, V2, V3, Vn conductors
Required crimped
ferrule:
Panduit (22AWG) F75-8-
M Panduit (12AWG)
F81-10-M
Current Inputs ALL 14 (1.5) 12 (4) 0.35- Use 600V insulated
I1, I2, I3, I4 0.4 conductors
Required crimped
ferrule:
Panduit (26AWG) F75-8-
M Panduit (12AWG)
F81-10-M
COM1, I/O 26 (0.5) 12 (2.5) 0.5-0.6 Use 600V insulated
connections conductors
Required crimped
ferrule:
Panduit (22AWG) F75-8-
M Panduit (12AWG)
F81-10-M
The wires temperature rating should withstand the “Limited Operating temperature range”.
Terminals
All used terminals consist of detachable terminal, except for the current measurement inputs
terminals.
L/+ N/- V1 V2 V3 N I 1+ I 1- I 2+ I 2- I 3+ I 3-
I 1+ I 1- I 2+ I 2- I 3+ I 3-
PS VOLTAGE
The power source can be a dedicated fuse, or a monitored voltage if it is within the
instrument power supply range.
To connect an AC power supply:
Connect the Line wire to terminal
L/+.
Connect the Neutral wire to
terminal N/-.
To connect to a DC power supply:
Connect the positive wire to
terminal L/+
Connect the negative wire to
terminal N/-.
Before installing, ensure that all incoming power sources are shut
OFF. Failure to observe this practice can result in serious or even
fatal injury and damage to equipment.
690V Inputs
400
690
400
Voltages
V1 V2 V3 VN
690V inputs are usually used with direct connection. Use any of the seven wiring
configurations shown in Figures 2-8 through 2-15.
120V Inputs
120
120
120
Voltages
V1 V2 V3 VN
120V inputs usually imply use of a potential transformer (PT). The PT requires use of any of
the four wiring configurations shown in Figures 2-7 through 2-10.
Wiring Diagrams
For AC input ratings, see Technical Specifications in Chapter 14 for more details.
Table 4 presents the available wiring configurations in the meter. For more details, see
Basic Meter Setup in Chapter 5.
Table 4: Wiring Configurations
4-wire 3-element Wye connection using 3 PTs, 3 CTs 4Ln3 or 4LL3 2-13
3-wire 2-element Open Delta connection using 2 PTs, 2 CTs 3OP2 2-14
4-wire 2½-element Wye connection using 2 PTs, 3 CTs 3Ln3 or 3LL3 2-15
3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs 3OP3 2-16
3-wire 2½-element Broken Delta connection using 2 PTs, 3 CTs 3bLn3 or 3bLL3 2-18
L1
LOAD
L2
L3
3DIR2
Figure 2-11 3-Wire 2-Element Delta Direct Connection Using 2 CTs (Wiring Mode = 3DIR2)
L1
LOAD
L2
L3
N
4LN3/4LL3
Figure 2-12 4-Wire Wye 3-Element Direct Connection Using 3 CTs (Wiring Mode = 4LN3)
LOAD
L2
L3
N
4LN3/4LL3 w. PT
Figure 2-13 4-Wire Wye 3-Element Connection Using 3 PTs, 3 CTs (Wiring Mode = 4LL3 or 4LN3)
L2
L3
N
3OP2
Figure 2-14 3-Wire 2-Element Open Delta Connection Using 2 PTs, 2 CTs (Wiring Mode = 3OP2)
LOAD
L2
L3
N
3LN3/3LL3
This configuration provides accurate power measurements only if the voltages are balanced.
Figure 2-15 4-Wire Wye 2½-Element Connection Using 2 PTs, 3 CTs (Wiring Mode = 3LL3 or 3Ln3)
L2
L3
3OP3
Figure 2-16 3-Wire 2½-Element Open Delta Connection Using 2 PTs, 3 CTs (Wiring Mode = 3OP3)
POWER TRANSFORMER
2A
DELTA CONNECTION
L1*
L1
LOAD
240VAC
L2*
L2 120VAC 240VAC
240VAC
208VAC
L3*
L3 120VAC N*
N
4LL3 delta
Figure 2-17 4-Wire 3-Element Delta Direct Connection Using 3 CTs (Wiring Mode = 4LL3 or 4Ln3)
L2
L3
N
3BLL3/3BLN3
Figure 2-18 3-Wire 2½-Element Broken Delta Connection Using 2 PTs, 3 CTs (Wiring Mode = 3bLn3 or 3bLL3)
Configuring CT / PT ratio
Open PAS software, connect to the meter and the go to
Meter Setup -> General Setup -> Basic Setup
where you will find the needed parameters (figure 4)
DC voltage measurement
EM235/PM335 PRO enables measuring 1-4 independent DC sources via 3 independent DC voltage Inputs.
When the Pro device is used as a single DC meter V1 and I1 shall be used. V2 and V3 must be connected
to GND.
When the Pro device is used as a multichannel DC meter. V1/I1, V2//I2, V3/I3 and V3/I4 serve as
independent channels/meters.
EM235/PM335 PRO Measures up to 800V DC via direct connection to the Pro meter:
Measuring 1500V DC and 2500V DC systems is possible via the SATEC Voltage Ratio Module (VRM).
When using the VRM, it is recommended that the distance between the SATEC VRM and SATEC meter
should not exceed 2 meters, using cabling featuring minimum 600V insulation.
• Accuracy = 0.1%
• 3 Independent voltage inputs
• DIN-rail installation
When using the SATEC VRM, the correct ratio coefficient must be set with PAS software
(“basic configuration” tab): “PT ratio” = 3.5
Notes:
• It is mandatory to use cabling featuring double insulation (600V) when connecting
HE sensors to PRO Series meters.
• It is mandatory to use a separate power supply for each sensor.
DC setup
DC setup is defined through PAS or through the meter basic setup menu
Setup menu
Note: DC option will appear in the menu for HACS input meters only
PAS menu
Note: DC option will appear in the menu for HACS input meters only
I/O Connections
Built-in I/O connections
The EM235/PM335 PRO are equipped with 2 built-in optional digital inputs, 1 relay output
and 1 analog input, for I/O ratings see Technical Specifications in Chapter 14.
• Two optically isolated status inputs are provided for status monitoring, pulse counting,
external power demand period, and time synchronization at 1ms sampling rate
• One Solid State relay output provided for energy pulsing, alarms, or remote control
• One optically isolated analog input with an internal power supply and current input
sensing of -1mA to 20 mA
Warning: Restriction of the built-in relay output to use mains circuits switching
Module oper
Temperature__ 8DI-DRY 8DI-WET 4DO CELL AUX PS
-40…50⁰C 2 NO NO NO NO
-40…50⁰C NO 3 NO NO NO
-40…50⁰C NO NO 2 NO NO
-40…50⁰C 1 NO 1 NO NO
-40…50⁰C NO 1 1 NO NO
-40…50⁰C NO NO NO 1 NO
-40…70⁰C 1 NO NO NO NO
-40…70⁰C NO 1 NO NO NO
-40…70⁰C NO NO 1 NO NO
-40…70⁰C NO NO NO 1 NO
-40…70⁰C 3 NO NO NO YES
-40…70⁰C NO 3 NO NO YES
-40…70⁰C NO NO 3 NO YES
-40…70⁰C 2 NO 1 NO YES
-40…70⁰C 1 NO 2 NO YES
-40…70⁰C NO 2 1 NO YES
-40…70⁰C NO 1 2 NO YES
-40…70⁰C 1 1 1 YES
-40…70⁰C NO 1 1 1 YES
-40…70⁰C 2 NO NO 1 YES
-40…70⁰C NO 2 NO 1 YES
-40…70⁰C NO NO 2 1 YES
8 DI Module
Eight optically isolated status inputs are provided for status monitoring, pulse counting,
external power demand period, and time synchronization.
The EM235/PM335 PRO series can be equipped with up to 3 x 8DI modules
8DI
RDY
Figure 2-21 8 DI – Front view & Digital Input Connection – Dry contact model
In case of Dry contact module the internal 24VDC power supply is operated.
In case of Wet contact module the extenal power supply is operated: 24V, 48V, 125V, 250V.
The wet contact source may have any polarity (or AC: 50/60Hz).
The Voltage Inputs must have the one common wire.
4RO Module
The 4RO module has four electro-mechanic relays (EMR) or solid state relays (SSR)
outputs provided for energy pulsing, alarms, or remote control. Up to 3 modules can be
installed
4 DI/2 RO Module
Four optically isolated status inputs are provided for status monitoring, pulse counting,
external power demand period, and time synchronization.The PRO series can be equipped
with up to 3 x 4DI modules.
The 2RO module has two electro-mechanic relays (EMR) or solid state relays (SSR) outputs
provided for energy pulsing, alarms, or remote control. Up to 3 modules can be installed.
AUX_PS Module
The AUX_PS module designed to increase the power ability of the meter. In case of three
optional modulesconnected to meter use Auxiliary Power Supply as a fourth module.
Voltage range of AUX PS: 88-264AC, 125-300 VDC.
Communications Connections
Before installing any Communication Module, ensure that
all incoming power sources are shut OFF. Failure to
observe this practice can result in serious or even fatal
injury and damage to equipment.
Several communication module options are available for the EM235/PM335 PRO:
• Built-in serial Communication COM1: RS-485
• Built-in Infra-Red serial Communication COM4: IR
• Built-in USB Device Communication: USB-C connector
• Built-in 2 x 10/100Base T ETHERNET Communication – Daisy Chain or double
independent Ethernet ports: RJ-45 connector
• 3 x 5mm pitch detachable terminal block
for COM2 RS485 connection
A full description of the communication protocols is found in the EM235/PM335 PRO
protocol guides that come with your meter.
IR port – COM4
IR port – COM4
Ethernet Connection
The external equipment TERMINAL connection type is RJ-45
The RATING of the insulation of the external equipment for use with the
ETH port, shall comply according to Installation Category III for
insulation to be suitable for SINGLE FAULT CONDITION
ETHERNET 1 connection
Figure 2-30: Ethernet Daisy Chain Connection with fall back (RSTP support)
Figure 2-31: Ethernet Daisy Chain Connection with fall back (RSTP support)
USB connection
To prevent potential differences between the Personal Computer (PC) USB port and
the EM235/PM335 PRO USB device port, it is recommended to use a galvanic isolated
USB adaptor before connecting the EM235/PM335 PRO USB port to a Personal
Computer (PC), or to use battery powered PC.
Indicator LEDs
The EM235/PM335 PRO has three status indicator LEDs that show present device
operation status and give diagnostics indication; one energy pulsing LED that output
kWh/kvarh pulses, located on the attached Display; and Load bar.
Modes of Operation
The EM235/PM335 PRO can run in the following modes:
Operational Mode
Operational Mode is the common operation mode. All device features are available.
When the device is in Operational Mode the CPU LED flashes for 1 second with a 1-second
pause.
Service Mode
Service Mode is used for local upgrading of EM235/PM335 PRO firmware. When the device
enters Service Mode, the CPU LED briefly flashes 2 times with a 1-second pause.
In Service Mode, all device operations are stopped.
Diagnostics Mode
The device enters Diagnostics Mode when the internal diagnostics detects a critical error
that affects the normal device operation. All device operations are stopped until the critical
error is cleared. All communications ports are still available. See Device Diagnostic Codes in
Chapter 20 for the list of diagnostic events that cause a critical error. See Device
Diagnostics for more information on the EM235/PM335 PRO built-in diagnostics.
When the device is in Diagnostics Mode, the CPU LED briefly flashes 3 times with a 1-
second pause, and the display unit shows a diagnostic message.
For more information on indication and clearing the device diagnostics, see Status
Information Display in Chapter 3, Viewing and Clearing Device Diagnostics in Chapter 3,
and Viewing and Clearing Device Diagnostics in Chapter 10.
Ethernet Port
One or two 10/100Base-T Ethernet ports provide a direct connection of the EM235/PM335
PRO to a local area network through the TCP/IP protocols. The device has three onboard
TCP servers configured for the Modbus/TCP (at TCP port 502), DNP3.0/TCP (at TCP port
20000) and IEC 60870-5-104 (at TCP port 2404) communications. The TCP servers can
support up to 10 simultaneous connections with MODBUS/TCP, DNP3.0/TCP and IEC
60870-5-104 client applications.
Connection through the Ethernet port does not require device identification. The
EM235/PM335 PRO responds to any device address and returns the received address in
the response message.
The two Ethernet ports can either be configured for separate and independent ethernet port
or used for daisy chain configuration
Note
To provide simultaneous file services for all ports, the EM235/PM335 PRO keeps
independent file pointers for each communications port. For a TCP port, the EM235/PM335
PRO holds separate file pointers for each active TCP socket. The TCP server automatically
closes a connection if a socket is idle for more than 5 minutes. There is no guarantee that a
new connection is established at the same socket, so do not make any assumptions
regarding the current file status when starting a new connection from your application.
Always initialize a file pointer to a record from where you expect to begin reading a file. For
more information, see “File Transfer” in the EM235/PM335 PRO MODBUS Communications
Guide.
Using PAS
PAS is the support software supplied with the EM235/PM335 PRO that gives the user basic
tool for programming the device, performing remote control operations, monitoring real-time
measurements, retrieving and analyzing historical data files, reviewing fault and power
quality reports, and more.
PAS can communicate with the devices through any EM235/PM335 PRO port using the
MODBUS RTU, MODBUS ASCII and DNP3.0 protocols. For information on installing and
using PAS, see Chapter 5 “Using PAS”.
Device Inputs
AC Inputs
The AC voltage and current input terminals are connected to the internal device circuits
through high impedance input voltages and transformers input current that isolate the device
from external wiring.
Voltage Inputs
The device has four high-impedance voltage inputs (direct 690V RMS phase-to-phase
voltage, ×140% overload). Voltage channels are designated as V1 through V3 and Vn.
The secondary voltage rating and primary to secondary voltage ratio (PT ratio) of the
external potential transformers must be specified in your device to provide correct voltage
measurements. For more information on specifying voltage input ratings in your device, see
Basic Device Setup in Chapter 6.
The secondary rating of the voltage inputs is used as a reference for calculating thresholds
for the power quality and fault triggers.
Current Inputs
The device is provided with current input transformers with either 5A or 1A rated current in
the standard model.
For more information on specifying input ratings in your device, see Basic Device Setup in
Chapter 6.
Sampling
7 AC channels (3 voltages and 4 currents) are continuously and simultaneously sampled at
a rate of 256 samples per cycle (12.8 kHz at 50Hz or 15.36 kHz at 60Hz).
The sampling rate is precisely synchronized with the power frequency. The reference
frequency signal is taken from one of the phase voltage inputs V1-V3, band-pass filtered,
and then sampled at 12.5 MHz providing a 0.0004% cycle measurement error.
Waveform Tracing
The sampled waveforms are stored to the circular trace buffer whose depth is sufficient to
provide up to 20 pre-fault cycles for the waveform recorder. The waveform recorder is
synchronized with the sampling circuitry and can store unlimited number of post-event
cycles. The length of the captured waveforms is only restricted by the size of the allocated
logging memory.
Digital Inputs
The EM235/PM335 PRO can monitor 2 digital inputs in the device (optional) and up to 3
removable 8-channel digital input modules with a total of 26 inputs. The modules may be
ordered with input options for dry contacts, or ±24V, ±125V and ±250V wet inputs.
All digital inputs are sampled at a rate of 16/20 (60/50 Hz) samples per cycle and
synchronized to the AC sampling circuitry. This gives time stamping of the input transitions
with a 1-ms resolution.
Digital inputs have a programmable debounce time from one to 100 milliseconds in groups
of two inputs. Each input can be independently linked to any device counter, Energy/TOU
system register, and setpoints.
Analog Inputs
The EM235/PM335 PRO monitors 1 on-device universal analog input (AI) and up to 3
removable
6-channels analog input modules (future), with a total of 19 AI, which may be used for
measuring DC and low frequency currents and volts, temperature through temperature
sensor.
Device Outputs
Analog Inputs/Outputs
The EM235/PM335 PRO supports up to three removable 4AO modules with a total of 12
analog output versatile channels that can output DC currents proportional to the measured
analog quantities. All outputs are optically isolated and have an internal power supply. The
0-1mA and ±1mA analog outputs provide 200% overload currents up to 2 mA and ±2mA.
Update time for analog outputs is 2-cycles (32 ms at @ 60Hz and 40 ms @ 50Hz).
Each analog output can be independently scaled to provide the desired engineering scale
and resolution (see Programming Analog Outputs in Chapter 2).
Relay Outputs
The EM235/PM335 PRO provides one on-device relay output (SSR) and up to 12 digital
outputs through three plug-in 4-channel relay output modules. Each module has eight
electro-mechanical relays 2-contact SPST Form A.
The following table shows timing characteristics of the relays and their expected lifetime.
Remote Commands
A remote operate command forces a latched or unlatched relay to move to its active state.
The relay is held in active state until the command is removed by a remote release
command. The remote release command also removes the local commands that hold a
latched relay in active state.
A remote operate command sent to a pulse or KYZ relay forces the relay to produce a pulse
or changes its state. A remote release command sent to a pulse or KYZ relay has no effect
since the operate command is cleared automatically for these relays.
Retentive Relays
Latched relays can be set to operate in retentive mode. Retentive mode affects the behavior
of the relay after loss of power.
After restoring power, all non-retentive relays are in inactive state until local conditions are
reevaluated. All active remote commands for non-retentive relays are cleared.
Retentive relays retain their status after restoring power, and all active remote commands
that were issued before loss of power are still effective.
Critical Faults
When a critical error is detected by the device diagnostics, all relays are released regardless
of their operation mode and all remote relay commands are removed.
Metering
RMS Measurements
All RMS quantities are based on 1/2-cycle true RMS measurements performed over 64
samples of the acquired waveforms. The 1/2-cycle quantities are values (normally, RMS
volts, RMS currents and unbalances) measured over one cycle and updated each half cycle
. This allows fast response to power quality and fault events.
RMS Trace
The EM235/PM335 PRO handles a circular RMS trace buffer that stores the last forty 1/2-
cycle RMS, unbalance, zero-sequence and frequency readings. This allows the data
recorder to provide 1/2-cycle trending of up to 20 pre-fault cycles when it is triggered from
the Power Quality.
The following table lists parameters that are available for pre-fault tracing.
Parameter Label
Phase-to-neutral volts V1, V2, V3
Phase-to-phase volts V12, V23, V31
Standard range currents I1, I2, I3, I4
Standard range neutral current In
Voltage zero sequence V ZERO-SEQ
Standard range current zero sequence I ZERO-SEQ
Parameter Label
Extended range current zero sequence Ix ZERO-SEQ
Voltage unbalance V UNB%
Standard range current unbalance I UNB%
Extended range current unbalance Ix UNB%
Power frequency Frequency
Data logs #13 (fault data trend) and Data logs #14 (PQ data trend) are internally linked to
the RMS trace buffer. The number of pre-fault cycles for data trending is defined when
configuring the Power Quality and Fault recorders. See Configuring the Power Quality
Recorder and Configuring the Fault Recorder in Chapter 7.
Harmonic Measurements
The EM235/PM335 PRO provides harmonic measurements on three voltage channels V1-
V3 and four standard range current channels I1-I4. To avoid erroneous harmonic readings
when the high fault currents saturate current channels, the harmonics registers are not
updated at the time of the fault.
The FFT analysis is performed over a 10-cycle waveform for 50Hz and 12-cycle waveform
for 60Hz system, sampled at a rate of 256 samples per cycle. This gives spectrum
components up to the 63rd harmonic.
The following table lists harmonic quantities provided by the device.
Parameter Label
Total Harmonics
Voltage THD V1 THD – V3 THD
Current THD I1 THD - I4 THD
Current TDD I1 TDD - I4 TDD
Current K-factor I1 KF - I4 KF
Voltage Crest-factor V1 CF – V3 CF
Current Crest-factor I1 CF - I4 CF
Total Interharmonics
Voltage THD V1 THD/I – V3 THD/I
Current THD I1 THD/I - I4 THD/I
Individual Harmonics
V1 Odd/even-harmonic distortion V1 %HD1 - V1 %HD63
V2 Odd/even-harmonic distortion V2 %HD1 - V2 %HD63
V3 Odd/even-harmonic distortion V3 %HD1 - V3 %HD63
I1 Odd/even-harmonic distortion I1 %HD1 - I1 %HD63
I2 Odd/even-harmonic distortion I2 %HD1 - I2 %HD63
I3 Odd/even-harmonic distortion I3 %HD1 - I3 %HD63
I4 Odd/even-harmonic distortion I4 %HD1 - I4 %HD63
V1 Odd-harmonic voltage V1 H01 - V1 H63
V2 Odd-harmonic voltage V2 H01 - V2 H63
V3 Odd-harmonic voltage V3 H01 - V3 H63
I1 Odd-harmonic current I1 H01 - I1 H63
I2 Odd-harmonic current I2 H01 - I2 H63
I3 Odd-harmonic current I3 H01 - I3 H63
I4 Odd-harmonic current I4 H01 - I4 H63
Three-phase total odd-harmonic kW kW H01 - kW H63
Three-phase total odd-harmonic kvar kvar H01 - kvar H63
Three-phase total odd-harmonic PF PF H01 - PF H63
Symmetrical Components
Positive-sequence voltage V PSEQ
Negative-sequence voltage V NSEQ
Zero-sequence voltage V ZSEQ
Negative-sequence voltage V NSEQ UNB%
unbalance
Zero-sequence voltage unbalance V ZSEQ UNB%
Positive-sequence current I PSEQ
Negative-sequence current I NSEQ
Zero-sequence current I ZSEQ
Negative-sequence current unbalance I NSEQ UNB%
Zero-sequence current unbalance I ZSEQ UNB%
Parameter Label
Fundamental Phasors
Voltage magnitude V1 Mag – V3 Mag
Current magnitude I1 Mag - I4 Mag
Voltage angle V1 Ang – V3 Ang
Current angle I1 Ang - I4 Ang
The device provides individual voltage and current harmonic measurements both in percent
of the fundamental component, and in corresponding engineering units. Quantities in
engineering units are calculated only for odd harmonics.
Angles for phasor vectors are given relative to the V1 phase voltage.
Aggregation Intervals
The device provides electrical measurements using a number of fixed aggregation time
intervals from 1/2 cycle to 2 hours. The demand measurements use programmable
aggregation intervals of up to 2.5 hours. The following table shows aggregation intervals
available for different electrical quantities.
Parameter 1/2 cycle 1 cycle 200 ms 1 sec 3 sec 10 min 2 hours
RMS volts and
× × × × × ×
currents
Powers × ×
Zero-sequence × × × × × ×
Unbalance × × × × × ×
DC Voltage × × × × × ×
Frequency × × 10 sec × ×
Total
Harmonics/Interh × × × ×
armonics
Individual
×
Harmonics
K-factor × × × ×
Crest factor × × × ×
Symmetrical
× ×
components
Phasors ×
The 200 ms RMS and unbalance quantities are integrated over a 10-cycle time for 50 Hz
and 12-cycle time for 60 Hz power system. The data for the 3 sec time interval is aggregated
from fifteen 200 ms time intervals. All RMS quantities aggregated from lower time intervals
represent true RMS readings over the entire aggregation interval.
Demands
Demand measurements are provided for volts, amps, total harmonics and powers. Two
different demand measurement techniques are used: block interval demand and sliding
window demand.
Maximum Demands
Every demand parameter is provided with the maximum demand register, which contains a
time-stamped peak demand value recorded since the last reset. Maximum power demand
registers are linked to the corresponding sliding demand source registers. If you wish to use
block interval demands instead of sliding window demands as a source, set the number of
the block intervals in the sliding window to 1.
For the TOU demand registers, the device allows automatic recording (profiling) of the daily
and monthly maximum demands to the data log together with the TOU energy readings.
Energy Metering
The EM235/PM335 PRO provides true four-quadrant energy measurements for kWh
imported and exported, kvarh imported and exported, and kVAh, with Class 0.2 ANSI C12-
20:2015 or Class 0.2S IEC 62053-22:2003 accuracy. Net and total energy measurements
for kWh and kvarh, and volt-hours and ampere-hours calculations are provided.
The device provides nine-digit energy counters by default. You can set the counters to have
fewer digits by changing the default energy roll value in your device (see General Setup
Device Option in Chapter 6).
Energy Pulses
The EM235/PM335 PRO outputs energy pulses through relay contacts with a user-
selectable pulse rate (see Producing Energy Pulses and Programming Relay Outputs in
Chapter 6). The pulse type (complete pulse or KYZ pulse), pulse width and polarity are
freely programmable.
Time-of-Use
The EM235/PM335 PRO TOU system handle a 10-year calendar with up to 16 types of
days and up to eight tariff changes per day in each daily profile.
The device provides 16 TOU energy and 16 parallel maximum demand registers that
receive data from the corresponding summary registers. Each TOU energy and TOU
maximum demand register stores the accumulated energy and corresponding peak
demands for up to 16 tariffs. See Chapter 8 “Totalization Energy and TOU Registers” for
information on how to configure the TOU registers and define the tariff scheme in your
device.
The device allows automatic daily and monthly profiling of the TOU energy readings and
TOU maximum demands to the data log files. Data log files #15 and #16 are dedicated to
the TOU system profile log and can be configured to automatically record TOU daily and
monthly profiles (see Configuring Data Log Files in Chapter 7).
Monitoring
Memory Backup Battery
The hardware circuit monitors the status of the memory backup battery. When the battery
level drops below the minimum allowed threshold, the icon on the display status bar will
lit up, indicating that the battery should be replaced.
Logical Controller
The embedded logical controller allows monitoring any measured quantity or external
contacts to provide indication, counting and recording events when the monitored value
exceeds the predefined threshold or when status transitions are detected on the device
inputs. See Using Control Setpoints in Chapter 6 for information on programming the logical
controller.
The logical controller launches the Waveform recorder and Data recorder to record the input
waveforms and measured quantities at the time of the event. Control setpoints can also be
linked to the Event recorder to record setpoint transition events into the event log files.
Recording
Event Recorder
The Event recorder automatically records time-tagged self-supervision events related to
configuration changes, resets and device diagnostics. The logical controller can also be
programmed to trigger the Event recorder in order to put the events monitored through
programmable setpoints into the event report. See Configuring the Event Recorder in
Chapter 7 for more information on programming the Event recorder.
Device Diagnostics
Device diagnostic messages may appear as a result of the EM235/PM335 PRO built-in
diagnostic tests performed during start-up and device operation.
All diagnostic events are recorded in the device Event log and can be inspected via PAS
(see Viewing the Event Log in Chapter 13). The diagnostics status is also stored in a non-
volatile register, which is not affected by loss of power and may be read and cleared via
PAS, from the RDM, or from a user application. Refer to the EM235/PM335 PRO
communication guides for the diagnostic register address and layout. See Device Diagnostic
Codes in Chapter 20 for the list of diagnostic codes and their meanings.
Device failures are divided into three categories:
1. Non-critical intermittent faults with auto-
reset. They do not cause the device to
restart but may cause temporary
degradation of device functionality,.
These faults are cleared automatically
as the condition that caused the fault
disappears.
2. Non-critical recoverable hardware or
configuration faults with manual reset.
These faults normally cause the device
to restart followed by repairing of the
configuration data. These faults must be
cleared manually via PAS, from the
RDM, or from a user application.
3. A critical unrecoverable hardware or
configuration failure. The reason may be
an unrecoverable sampling failure, or
corruption of the time, the factory device
configuration or the calibration setup
data. A critical error causes the device
to release all its outputs and to stop
normal operation until the faults that
caused the critical error are cleared.
Hardware failures are normally non-critical recoverable faults that do not cause a system
failure but may cause data loss. Hardware failures are often caused by excessive electrical
noise in the region of the device.
A configuration reset may also be a result of the legal changes in the device configuration
whenever other configuration data is affected by the changes made.
In the event of a device fault, check the fault reason and clear the device diagnostics. If the
reason is a time fault, update the device clock. In the event of a configuration reset,
determine the device setup affected by the fault via the event log, and then verify the setup
data.
See Viewing and Clearing Device Diagnostics in Chapter 10, Viewing and Clearing Device
Diagnostics in Chapter 3, and Status Information Display in Chapter 3 on how to inspect and
clear the device diagnostics status.
If the device continuously resets itself or an unrecoverable critical error occurs, contact your
local distributor.
Device Fault Alarm
The EM235/PM335 PRO provides a global "DEVICE FAULT" event flag that is asserted all
the time while one of the non-critical diagnostics events exists. It can be checked from a
Setpoint (see Using Control Setpoints in Chapter 6) to give a fault indication via a relay
output. If the alarm relay is programmed for failsafe mode using inverting polarity, then its
normally closed contacts will be open if either the device looses power or a non-critical
device fault occurs. Note that in the event of a critical system failure, all relay outputs are
automatically released.
NOTE
The IRIG-B time faults may not be masked and may not be cleared externally. If the IRIG-B
time code signal is not provided, set the device time synchronization input to any unused
digital input (see Local Settings in Chapter 6) to avoid fault alarms caused by the IRIG-B
port.
Meter Security
The PM335/EM235 PRO SERIES provides 3-level password security for protecting meter
setups and accumulated data from unauthorized changes. Meter readings are not software
protected.
Access to particular setup and control items is granted depending on the security level of the
password you entered. The passwords can be 1 to 8 digits long.
The PM335/EM235 PRO SERIES is also equipped with terminal connections sealed cover
to avoid unwanted electrical connections.
The following table shows the meter security levels and user access rights.
The present passwords settings are never uploaded from the meter via the Passwords
setup. When you open the dialog, all passwords are zeroed.
To setup new passwords:
1. Enter the first (lower-level) password in the “Password 1” box and repeat it
in the following “Confirm password” box.
2. In the same manner, enter Password 2 and
Password 3 for the medium and high-level
security passwords.
3. Click “Save as” to save the passwords to the site
database. The passwords are stored in an
encrypted form.
4. Click “Send” to update passwords in your meter.
To setup a password online:
1. From the Monitor menu, select Administration ->
Change Password, and then click on the
password you wish to change.
Display Operations
The EM235/PM335 PRO has a high-contrast graphical TFT LCD display for local data read outs,
meter setup and servicing.
The display operates in two modes:
• Multi-page data display mode with Auto-Scroll feature allows you to scroll through display
screens and pages to view various billing, instrumentation and status data.
• Programming mode allows you to enter menu-driven device setups for inspecting and
changing factory set meter parameters, or resetting maximum demands, counters and device
diagnostics messages.
The display is normally updated once per second.
Navigation Buttons
The EM235/PM335 PRO is provided with five/four navigation buttons as described below:
Button Operation
Display Menus
The EM235/PM335 PRO has 6 multi-page displays listed in the following table.
Display Menus Display Icon Display Contents
Favorites Favorites Monitor Favorites Favorites
ꭞ ꭞ ꭞ
Favorites Monitor Consumpt. Favorites Monitor Consumpt. Favorites Monitor Consumpt. Favorites Monitor Consumpt.
Navigating in Sub-Menu
My App Name – Fl.32 T1 15/03/17 15:45 My App Name – Fl.32 T1 15/03/17 15:45 My App Name – Fl.32 T1 15/03/17 15:45
Custom Parameters
Voltage & Currents Custom Parameters
Voltage & Currents
Custom Parameters
Voltage & Currents
Favorites Monitor Power & PF Power & PF Voltage L-N
≡/ ≡/
Energy Energy Voltage L-L
≡/ Device I/O Device I/O Currents
Device Counters Device Counters Currents Max DMD
Comm. Status Comm. Status Averages
Power & PF
Energy
Device I/O
Device Counters
Comm. Status
ꭞ ꭞ ꭞ
Status Indicators
Graphical icons and indications on the top status bar give immediate meter status indication and
show the present tariff rate.
The present date and time are indicated at right on the status bar. The date order can be changed
according to local rules via the "Real Time Clock" device setup menu.
My App Name – Fl.32 T1 15/03/19 15:45 Screen status bar shows type of displayed parameters,
VOLTAGE L-L present date and time, NORMAL/TEST mode indication
alarms indication, communication activity and battery
Parameter value MAX/MIN status
161.0 KV
161.2
L12 159.3
L21
161.0 KV 160.5
158.0 Active page
Shows possible
no. of pages in
sub-menu
L31
161.0 KV 163.0
158.2
f
50.268 Hz
Test mode
Display Features
While energizing the device the display will show default screen line-voltages measurements as
described below:
161.0 KV
161.2
L12 159.3
L21
161.0 KV 160.5
158.0
L31
161.0 KV 163.0
158.2
f
50.268 Hz
The default screen can be changed using the Display Setup Menu
Display Setup
The EM235/PM335 PRO display has a number of programmable features that can be disabled,
enabled and adjusted via the meter Display Setup.
Using UP/DOWN/ENTER navigation buttons setup the desired display brightness and backlight
time in the SETUP/Diag>Display Setup\Adjustment menu as described below:
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Display Resolution
The resolution menu bestows the user to select number of decimal points for voltages,
currents,power and energy monitoring values.
Fundamental Component
The EM235/PM335 PRO can display total displacement power factor and active power for the
fundamental component if it is enabled through the display setup (see Configuring the Display).
When phase power readings are allowed, the EM235/PM335 PRO also displays per-phase
displacement power factor and active power for the fundamental component.
PF 0.98
Monitor Display
The Monitor Display menu consists of monitoring electric parameters, device resources status,
communication status and device diagnostics as described in table below.
Display Menus Display Contents
Custom Parameters Predefined screen that shows the custom parameters
Voltage & Currents Displays all voltage & current parameter values
Power % PF Displays all powers & power factor values
Device I/O Displays digital inputs status, relay outputs status and analogue
inputs/outputs
Device Counters Displays counters value
Communication Status Displays COM1-4 status, ETH1-2 IP address
Custom Parameters
The custom parameters menu displays up to 4 predefined parameters to be seen in one single
display. This custom display can be setup as default screen.
Acces Monitor form main menu, using the UP/DOWN button select Custom Parameters and press
OK/ENTER button to display the custom paramters screen.
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Voltage and Currents
Acces Monitor form main menu, using the UP/DOWN button select Voltage & Currents/Voltage L-N
and press OK/ENTER button to display the line-to-line voltage measurement screen, using
UP/DOWN button select the desired voltage/current parameter to display
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
12700
13.0
L1 11.5
V
12700
13.0
L2 11.5
V
12700
13.0
L3 11.5
V
f
50.268 Hz
22000
22.5
L12 20.1
V
L21
22000 V
22.5
20.1
L31
22000 V
22.5
20.1
f
50.268 Hz
120.1
120
L1
0
A
118.4
120
L2 0
A
L3
111.4 A
120
0
N
0.1 A
Power and PF
Acces Monitor form main menu, using the UP/DOWN button select
POWER & PF/Min/Max/Phase 1 and press OK/ENTER button to display the phase 1 min/max
power measurement screen, using UP/DOWN button select the desired power & pf parameter to
display
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
My App Name – Fl.32 T1 15/03/17 15:45 Phase 1 import energy.
ENERGY IMP.: PHASE 1
31.034 kWh
0 kvarh
31.034 kVAh
Device I/O
The Digital I/O display shows three sub-menus: "Digital Inputs" display to show status of each
digital input, "Pulse/Event Counters" display to count external pulses or setpoint events, or as time
counters to count setpoint operation time, "Relay Outputs" display to show status of each relay
output. Use the UP/DOWN button to move from one display to another.
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
1-2 # OF PULSES/STATUS
DI 1
0
DI 2
0
Analog inputs
Device Counters
The Device Counters display shows three sub-menus: "Digital Inputs" display to show status of
each digital input, "Pulse/Event Counters" display to count external pulses or Setpoint events, or as
time counters to count Setpoint operation time, "Relay Outputs" display to show status of each relay
output. Use the UP/DOWN button to move from one display to another.
Note:
The EM235 display menus is identical to the PM335 display menus
Communication Status
Acces Monitor form main menu, using the UP/DOWN button select Comm. Status and press
OK/ENTER button to display the device communications ports status
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Consumption Display
Billing Period Data Displays
The EM235/PM335 PRO provides billing period data displays for energy and general purpose
volume data as m³, cf or Ccf calculated using Digital Input for water and/or gas meter application.
Only registers you selected in the billing/TOU register setup and tariff rates listed in the TOU daily
profiles are included (see Configuring Billing/Tariff Registers and Configuring the Daily Tariff
Schedule in Chapter 5).
The following example demonstrates the present billing period displays for two configured billing
registers (kWh imported and kvarh imported) and for three active tariff rates. The actual register
contents in your installation may be different depending on your selection of register sources.
Each billing period display lists all total and tariff energy, maximum demand and cumulative
maximum demand registers for all configured billing registers and all active tariffs. Use the
UP/DOWN/ENTER button to navigate to the desired Billing/TOU period register display
TOT 123456789.3 kWh Billing period according to TOU predefined profile (Reg1 for TOU
active energy and Reg2 for TOU reactive energy are predefined
T1 123456000.0 kWh TOU/Register factory setup, can be changed by user, see
Configuring Billing/Tariff Registers and Configuring the Daily Tariff
Schedule in Chapter 5)
T2 789.3 kWh
Register 1 – tariff 1 readings:
T3
V1
I1
0 360.0 720.0
Harmonics Display
Harmonics display shows individual harmonics distortion for phase voltages and current, and phase
voltage/current harmonic spectrum graphs. Use the UP/DOWN button to scroll to the specific
harmonic number or voltage and current channels harmonic spectrum.
My App Name – Fl.32 T1 15/03/17 15:45 phase voltages and currents harmonics spectrum, %
VOLTAGE – PHASE 1
120%
100%
80%
60%
40%
20%
0%
1 3 5 7 9 11 13 15 17 19 21 23 25
Phasor Display
The Phasor display shows a three-phase network Phasor diagram. All phase angles are given
relatively to the V1 channel.
My App Name – Fl.32 T1 15/03/17 15:45 Three-phase voltage and current Phasor diagram
RT PHASOR
I3=108.0°
90°
V3 =120.0°
I1=-12.3°
I2=-132.0°
V2=-120.0°
270°
Trend Display
The Trend Display shows basic parameters trend – Voltage, Current, Power and Frequency
240
230
220
210
200
190
180
0.2
1.0
1.8
2.6
3.4
4.2
5.0
5.8
6.6
7.4
8.2
9.0
9.8
L1 L2 L3
230.34 V 232.30 V 230.04 V
Frequency trend
Alarms/Event log
The Alarms/Event log display shows the device events caused by external cause as setup
changes, memory clear operation, power outages. Every alarm/events is marked with time stamp
showing the alarm/event time occurance.
Note:
The EM235 display menus is identical to the PM335 display menus
Diagnostics
If there are diagnostic messages, the diagnostic green led on the device panel flashes until you
clear the device diagnostics. Some of the diagnostics events are cleared automatically as the event
source disappears. See Device Diagnostic Codes in Chapter 20 for a full list of diagnostic
messages and their meanings. See Clearing Device Diagnostics for information on how to clear the
device diagnostics from the display and via PAS.
The diagnostic Led indication can be disabled or enabled via the Display Setup menu.The
Diagnostics display shows the device faults as described in the Device Diagnostic codes
Note:
The EM235 display menus is identical to the PM335 display menus
Device Setup
The EM235/PM335 PRO setup is menu-driven. The device provides 12 menus that allow local
accessing a limited number of meter setups and control functions listed in the following table.
Access to particular menus is granted depending on the password you entered if enabled.
Menu Label Menu Function
General Setup Basic device setup, Demand setup, TDD, Device options,
Transformer correction, Digital inputs, Relay outputs and
Counters
Communication Setup COM1,2 and 3 serial port setup, Network 1 & 2 setup,
Dial-up network setup
Display Setup Custom name/ID setup, Adjustment setup, Localization
details, Localization DST, Engineering units and
Resolution setup
TOU display setup TOU source setup, Billing period display setup
Custom setup Default page, Custom parameters page setup
Reset Setup Reset of engineering maximum demands, Counters,
logs, energy and Billing/TOU energy
***
General Setup
Communication Setup
1 2 3 4
5 6 7 8
Setup/Diag
9 0 .
Note:
The EM235 display menus is identical to the PM335 display menus
If the password you entered is correct, you are moved to the Main menu, otherwise you return back
to the Device Setup menu.
Use the UP/DOWN button - to scroll through the menu list to the desired menu
entry
Use the UP/DOWN button - to scroll through the desired value, then press the
ENTER/OK button - ꭞ to store the selected value
Note: While being in the Device Setup operation mode, the EM235/PM335 PRO display will return
to normal operation, i.e. move to data display, during idle operation of one minute
Installing PAS
You need PAS V1.53 or higher to take an advantage of the meter data logging options.
To install PAS on your PC:
Download the latest PAS software from
Satec website:
https://www.satec-global.com/power-
analysis-software
Open My Computer on your Desktop.
Click on your CD drive icon, select the
PAS directory, and then double click on
Setup (shown as an Application type file).
Follow InstallShield® Wizard instructions
on the screen.
PAS is installed by default to the C:\Pas folder.
When installation is complete, the PAS icon appears on your Desktop. Double click on the PAS
icon to run PAS.
For general information on how to work with PAS, see the “PAS Getting Started” guide supplied on
the installation CD.
Setting up Communications
You can communicate with the EM235/PM335 PRO via a PC RS-232 serial port or through the
Internet.
To configure communications with the EM235/PM335 PRO:
Select Configuration from the Tools menu. Under the
Communication group on the Instrument Setup tab, select the
type of connection for your device.
Set the device communication address you assigned to the
EM235/PM335 PRO port. When communicating via the
Ethernet, the EM235/PM335 PRO responds to any address
you select.
In the Sampling Rate box, select a rate at which PAS updates
data on your screen when you continuously poll the device in
the PAS Data Monitor.
The communication protocol and port settings must match the settings you made in your meter.
In the Retries box, specify the number of retries PAS will use
to receive a response from the meter if communications fail.
Click OK.
To copy all setups from one site database to another site's database:
In the list box on the toolbar, select a
source device site from which you wish to
copy setups.
Select Copy to... from the Meter Setup
menu.
Select the target site database to which
you wish to copy setups, and click OK.
Individual Download
To update a particular setup in your meter:
Check the On-line button on the PAS
toolbar
Select a meter site from the list box on
the toolbar.
Select the desired setup group from the
Meter Setup menu. Click on the setup tab
you want to download to the meter. As
the setup dialog box opens, PAS
retrieves and displays the present meter
setup data.
If you wish to download a setup saved in
the site database, click Open, and then
click OK, or fill in the boxes with the
desired configuration data for your
device.
Click Send.
Batch Download
To download all setups to your device at once:
Check the On-line button on the PAS
toolbar
Select the device site from the list box on
the toolbar.
Select Download Setups from the Meter
Setup menu.
Batch Upload
To upload all setups from the device to the site database at once:
Check the On-line button on the toolbar.
Select the device site from the list box on
the toolbar.
Select Upload Setups from the Meter
Setup menu.
Authorization
If communications with your meter is secured, you are prompted for the password when you send
new setup data to the meter.
Configuring Communications
Setting Up Serial Communication Ports
Using the Front Display
Acces Communication Setup menu, Select COM1 or other and setup the communication port
desired parameters as described below using UP/DOWN navigation button and OK/ENTER button.
≡/
ꭞ
Note:
The EM325 display menus is identical to the PM335 display menus
Using PAS
Select Communications Setup from the Meter Setup menu, and then click on the Serial Ports Setup
tab. In the Port box, select the desired device port.
Figure 6-1: Communication Setup Dialog Box – Serial Ports Setup Tab
Baud rate 300 bps-115.2 kbps 19200 bps The port baud rate
Setting Up Ethernet
Using the Front Display
Access Communication Setup menu, Select Network 1/2 or other and setup the communication
port desired parameters as described below using UP/DOWN navigation buttons and OK/ENTER
button.
My App Name – Fl.32 T1 15/03/17 15:45 My App Name – Fl.32 T1 15/03/17 15:45 My App Name – Fl.32 T1 15/03/17 15:45
NETWORK 1
General Setup General Setup
≡/
COM 2 NETWORK SUBNET
TOU Display Setup
MASK
255.255.255.0
Custom Setup COM 3
Using PAS
Select Communications Setup from the Meter Setup menu, click on the Network Setup tab and then
select Network 1 or 2.
Figure 6-2: Communication Setup Dialog Box – Network 1/2 Setup Tab
NOTES:
The meter provides the permanent
MODBUS TCP server on port 502.
Selecting the DNP3 TCP service port
launches the second DNP3 TCP server
allowing simultaneous connections on
both TCP ports. Selecting the MODBUS
TCP port disables the DNP3 TCP server.
When you change the device network
settings through the Ethernet port, the
device port restarts so communication will
be temporarily lost. You may need to wait
some additional time until PAS restores a
connection with your device.
Using PAS
Select Communications Setup from the Meter Setup menu, click on the RSTP Setup. Enable the
capability by selecting YES for the RSTP Enabled field. Apply changes to all other default
configuration values as required by the network administrator.
Hello Time 1 - 10 2
Forward Delay 4 - 30 15
TX Hold Count 1 - 10 6
NOTES:
• Changing the RSTP default settings may have significant impact on network health
and stability. Consult with your network administrator
• The Meter supports as default 20 chained connected devices
The default SNTP server IP addresses belong to Stockholm and Berlin university servers.
SNTP can work only out of the 1st Ethernet interface. Navigate to the Communication Setup >
Network Setup. Verify that Network 1 has a valid IP address and a valid Gateway (that can
reach the SNTP Server).
Navigate to General Setup > Local Settings. Activate the Clock synchronization and select SNTP as
the method for synchronization. Make sure to set the Time Zone Offset, as the time provided by the
SNTP is UTC.
The following table lists available options. Refer to your eXpertPower service provider for the
correct eXpertPower settings.
Parameter Options Default Description
XPW Server IP Address 207.232.60.18 The IP address of
theeXpertPower server
XPW Server Port 0-65535 5001 The TCP service port of the
eXpertPower server
XPW Client Enabled NO, YES NO Enables operations of the
eXpertPower client
Time to Next Session, 1-99999 The time remaining to the
min next connection session
NOTES:
If you do not use the eXpertPowerTM
service, do not enable the eXpertPower
client in your device.
Do not change the connection period
setting. The eXpertPower server updates
it automatically.
eXpertPower works on ethernet port 1
and does not work on ethernet port 2
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
Select General Setup from the Meter Setup menu. See the table below for the Basic Setup tab.
1 Future option
Device Options
The Device Options setup allows changing user-configurable device options or putting the meter
into energy test mode.
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Device Options tab.
2 The number of digits after decimal points is part of total of digits of Energy roll value
S = P 2 + Q2
•
• This mode is recommended for electrical networks with low harmonic distortion, commonly with
THD < 5% for volts, and THD < 10% for currents. In networks with high harmonics, the second
method is preferable.
• When the non-active power calculation mode is selected, active power is measured directly,
apparent power is taken as product S = V x I, where V and I are the RMS volts and amps, and
reactive power (called non-active power) is calculated as:
• N = S2 − P2
Transformer Correction
While using external CT meter option, transformer correction allows you to compensate ratio and
phase angle inaccuracies of the user voltage and current instrument transformers.
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Transformer Correction
tab.
Figure 6-7: General Setup Dialog Box – Digital Inputs Dialog Box
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Digital Inputs tab.
Figure 6-8: General Setup Dialog Box – Digital Inputs Dialog Box
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Relay Outputs tab.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Analog Inputs tab.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Analog Outputs tab.
AO type 0-1mA The analog output type. When connected to the meter,
shows the actual AO type received from the device. When
±1mA working off-line, select the analog output option
0-20mA corresponding to your analog module.
4-20mA
Zero scale Defines the low engineering scale (in primary units) for the
analog output corresponding to a lowest (zero) output
current (0 or 4 mA)
Full scale Defines the high engineering scale (in primary units) for
the analog output corresponding to a highest output
current (1 or 20 mA)
When you select an output parameter for the analog output channel, the default engineering scales
are set automatically. They correspond to the maximum available scales. If the parameter actually
covers a lower range, you can change the scales to provide a better resolution on an analog output.
Using Counters
The EM235/PM335 PRO has 32 nine-digit signed counters that count different events. Each
counter is independently linked to any digital input and count input pulses with a programmable
scale factor. You can link a number of digital inputs to the same counter. Each counter can be
incremented or decremented through the Control Setpoints in response to any internal or external
event.
Using PAS
Select General Setup from the Meter Setup menu, and then click on the Counters tab.
Display Setup
Custom Name ID
This allows the user to define a general purpose name to the device to be displayed at the display
status bar.
Access Display Setup menu, Select Custom Name ID and setup the device custom name
identification as described below using UP/DOWN navigation buttons and OK/ENTER button.
My App Name – Fl.32 T1 15/03/17 15:45 My App Name – Fl.32 T1 15/03/17 15:45 My App Name – Fl.32 T1 15/03/17 15:45
CUSTOM NAME ID
CUSTOM NAME/ID
General Setup General Setup
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
Ensure that the On-line button on the PAS toolbar is checked, and then select RTC from the
Monitor menu or click on the PAS toolbar Real-Time Clock Button.
The RTC dialog box displays the current PC date and time and the time in your meter.
Figure 6-15: Real Time Clock Dialog Box – Time and Date setup
LOCALIZATION DST
General Setup General Setup
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
To configure the local time options in your device, select the device site from the list box on the
PAS toolbar, select General Setup from the Meter Setup menu, and then click on the Local Settings
tab.
Figure 6-16: Real Time Clock Dialog Box – Time and Date setup
Using SNTP
Enable SNTP client operation and configure it if required (see Setting-Up SNTP Client).
When an SNTP server is not available or when a connection with a server is restored, the
corresponding event is automatically recorded to the device Event log.
Resolution setting
This display setup menu allows the user to setup the voltage, current, power and energy display
resolution (V or kV, A or kA, kW or MW and kWh or MWh).
Access Display Setup menu, Select Resolution and setup the device electrical parameter value
resolution as described below using UP/DOWN navigation buttons and OK/ENTER button.
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
The following table shows how to calculate a file size for different files.
File Record Size, Bytes File Size, Bytes
Event Log 20 Record Size × Number of Records
Data Log 2 + 4 × Number of Parameters Record Size × Number of Records
TOU Profile Log 12 + 4 × Number of Season Tariffs Record Size × Number of TOU
(Data log #15-#16) Registers × Number of Records x 2
Waveform Log 1072 Record Size × Number of Channels
× Number of Series × Number of
Records per Series
PQ Log 32 Record Size × Number of Records
…. …. …. …. …. … ….
.
Data log free
#13
The device memory is pre-configured for regular data trending and fault recording applications as
shown in the following table.
Figure 7-2: Memory/Log Setup Dialog Box – Event Log configure file partition
Figure 7-3: Memory/Log Setup Dialog Box – Data Log 1 configure file partition
Figure 7-4: Memory/Log Setup Dialog Box – Data Log 1 setup recorder
Data Log #2
kW Import Sliding I1 Demand
Demand
2kvar Import Sliding I2 Demand
Demand
3KVA Sliding Demand I3 Demand
8kVAh RT (1-cycle) V4
Setpoints #1 is preset at the factory to trigger Data logs #1 and #2 in 15 min intervals.
The generic data group represents generic volts, amps, etc., regardless of the data integration time.
The PQ recorder can use different time envelopes to record data integrated over intervals from a
half cycle to 10 minutes depending on the duration of the power quality event (see Configuring the
Power Quality Recorder). The Fault recorder uses only the half-cycle RMS trend.
Figure 7-5: Memory/Log Setup Dialog Box – Data Log 16 configure file partition
Figure 7-6: Memory/Log Setup Dialog Box – Waveform Log 7 configure file partition
For example, if you want to record a 64-cycle waveform sampled at a rate of 32 samples per cycle,
the number of records required for one waveform series would be:
Number of Records per Series = (32 x 64)/512 = 4.
If you want to allocate space sufficient to store 20 waveform events (series), you should set up the
waveform log file for 4 x 20 = 80 records.
5. Click OK, and send your setup to the device or
save to the database.
6. Click “Setup Recorder”, or click on the
“Waveform Recorder” tab.
The following table lists available waveform options.
Figure 7-7: Memory/Log Setup Dialog Box – Waveform Log 7 setup recorder
Figure 7-8: Memory/Log Setup Dialog Box – Waveform Log 7 selected channels
PQ Events Evaluation
The events are classified in accordance with the IEEE 1159 power quality categories. The table
below shows the categories recorded by the device, the metering data used to detect voltage and
frequency faults, their typical triggering thresholds and event durations.
Impulsive transients
Impulsive transients are detected as impulses with a rise time less than 0.5 ms and duration from
80 us to ½ cycle. The impulse magnitude is measured as the overshoot voltage magnitude above
the normal voltage wave shape. It is referenced to the nominal peak voltage (1.414 Un).
Sags and swells
A voltage sag or swell is classified as one polyphase event regardless of the shape and of the
number of phases affected (as per IEC 61000-4-30). An event can begin on one phase and end on
another phase. The fault magnitude is recorded separately for each phase involved. The event
duration is measured from the instant at which the voltage falls/rises below/above the start
threshold on one of the phases to that at which it becomes greater/lower than the end threshold on
all affected phases including a threshold hysteresis.
Voltage Interruptions
The voltage interruption is detected when the voltages on all phases fall below the interruption
threshold (as per IEC 61000-4-30).
Event PQ category Trigger parameter Reference Typical Event
ID value thresholds, % duration
PQE11 Impulsive transients Instantaneous overshoot Un peak 20-200% 80 us–
voltage voltage 10 ms
PQE211 Instantaneous sag ½ cycle RMS voltage Un RMS 80-90% < 30 cycles
PQE212 Instantaneous swell ½ cycle RMS voltage Un RMS 110-120% < 30 cycles
PQE221 Momentary interruption ½ cycle RMS voltage Un RMS 0-10% < 3 sec
PQE222 Momentary sag ½ cycle RMS voltage Un RMS 80-90% < 3 sec
PQE223 Momentary swell ½ cycle RMS voltage Un RMS 110-120% < 3 sec
PQE231 Temporary interruption ½ cycle RMS voltage Un RMS 0-10% < 1 min
PQE232 Temporary sag ½ cycle RMS voltage Un RMS 80-90% < 1 min
PQE233 Temporary swell ½ cycle RMS voltage Un RMS 110-120% < 1 min
PQE31 Sustained interruption ½ cycle RMS voltage Un RMS 0-10% > 1 min
PQE32 Undervoltage ½ cycle RMS voltage Un RMS 80-90% > 1 min
PQE33 Overvoltage ½ cycle RMS voltage Un RMS 110-120% > 1 min
PQE4 Voltage unbalance 3-sec negative No 1-5% Steady
sequence unbalance state
PQE52 Harmonics THD 3-sec harmonic THD No 5-20% Steady
state
PQE53 Interharmonics THD 3-sec interharmonic No 2-8% Steady
THD state
PQE6 Voltage fluctuations 10-min Pst No 1-5 Steady
(flicker) state
PQE7 Frequency variations 3-sec frequency Nominal 1-6% Steady
frequency state
Un – nominal device voltage
PQ Recorder Setup
The PQ recorder setup allows you to adjust thresholds and hysteresis for PQ triggers, to define the
waveform and data log options for PQ events, and to enable or disable the PQ recorder in your
device.
To configure the PQ recorder:
1. Select Memory/Log from the Meter Setup
menu, and then click on the PQ Recorder tab.
2. If you want to change the default settings,
adjust thresholds and hysteresis for PQ triggers
3. Select the waveform and data logging options
for PQ events
4. Download your setup to the device.
The Sag, Swell and Interruption triggers use the same waveform and data log options. If you
change one of them, the others are automatically adjusted to the same setting.
The waveform log option allows recording waveforms both at the start and the end of a PQ event.
Since the voltage variations may last from some seconds to minutes, this allows capturing and
analyzing the voltage transitions using short time waveform recording at the start and the end of the
voltage sag or swell.
The data log option allows concurrent recording of the RMS data at a variable rate depending on
the PQ event duration. To reduce the memory consumption for recording long duration events, the
PQ recorder uses different time envelopes (aggregation intervals) for data tracing and changes the
recording rate accordingly. You can specify for each PQ trigger how much time to record data using
one or more time envelopes.
To enable or disable the PQ recorder:
1. Check or uncheck the “Recorder Enabled”
checkbox.
2. Send your setting to the device.
Figure 8-2: Energy/TOU Setup Dialog Box – TOU Daily Profiles setup
The profile setup allows you to specify the daily tariff change points with a 15-minute resolution.
To configure your daily profiles:
1. Select the desired season and day type
2. Select the start time for each tariff change point and the corresponding
active tariff number.
3. Repeat the setup for all seasons and types of day.
The first tariff change point is fixed at 00:00 hours, and the last tariff change you specified will be in
use until 00:00 hours on the next day.
Note: The billing monthly and daily profile files, and your billing data display are automatically
configured for the number of active tariffs you defined in the meter TOU daily profile
The meter TOU calendar allows you to configure any tariff schedule based on any possible utility
regulation. The calendar provides 48 entries that allow you to specify profiles for working days and
holidays through all seasons in any order that is convenient for you, based on simple intuitive rules.
There are no limitations on how to define your schedule. The meter is able to automatically
recognize your settings and to select a proper daily tariff schedule for any day within a year.
To configure your season tariff schedule:
1. In the “Season/Period” box, select the season,
and in the “Day Type” box, select a day type for
this calendar entry.
2. Select the time interval when this daily tariff
schedule is effective, based on the start and the
end weekdays and, for a multi-season
schedule, on the start and the end month for
the selected season. It does not matter which
order of weekdays or months you select: the
meter recognizes the correct order.
3. For exception days like designated holidays,
select a specific day either by specifying a day
and month, or by selecting a month, a week
and a weekday within the month.
NOTE: The PM335 PRO TOU calendar provides an embedded schedule of Hebrew holidays till
2039 for Israeli customers. To enable the automatic holiday schedule, select Israel in the Country
box in the Local Settings setup (see Local Settings)
To configure your DST schedule:
1. Select DST in the “Season/Period” box.
2. Select the DST start month and day in the “Month” and “Day” boxes.
3. Select the DST end month and day in the “Till
Month” and “Till Day” boxes.
4. In the “Year” box, select a year for which these
dates will be effective.
5. Repeat steps 2-4 for all years for which you wish to provide a DST
schedule.
The PM335 PRO COM port is working in modbus master or client mode (client mode is the default)
The PM335 PRO can serve as transparent gateway when configured to be master. It enables
exchanging messages between serial connected devices and expertPower or scada via PM335
etherent connection.
The PM335 is forwarding all client messages to target devices and then return response to the
master application
Setting the working mode might be done through PAS or using the front menu
Figure 9-2: Serial port Setup Dialog Box – Modbus port mode
Configuring DNP3
Refer to the PM335 PRO DNP3 Reference guide for information on the DNP3 protocol
implementation and a list of the available data points.
DNP Options
Select Protocol Setup from the Meter Setup menu and click on the DNP Options tab.
The following table describes available options. Refer to the DNP3 Data Object Library document
available from the DNP User’s Group on the DNP3 object types.
3
The Select Before Operate command causes the meter to start a timer. The following Operate command must be sent before
the specified timeout value expires.
4
The meter requests time synchronization by bit 4 in the first octet of the internal indication word being set to 1 when the time
interval specified by the Time Sync Period elapses. The master should synchronize the time in the meter by sending the Time
and Date object to clear this bit. The meter does not send time synchronization requests if the Time Sync Period is set to 0.
Figure 9-3: Protocol Setup Dialog Box – DNP Class 0 Points Tab
Figure 9-4: Protocol Setup Dialog Box – IEC 60870-5 Options Tab
Figure 9-5: Protocol Setup Dialog Box – IEC 60870-5 Mapped Points and Events Setup Tab
3. Select an object group and parameter for points you wish to remap.
Object types and addresses are assigned automatically upon the
starting mapped address and default static type you selected for the
type of objects in the IEC 60870-5 Options Setup. When saving the
setup to the device database or sending to the meter all points are
automatically arranged in the order: measured values, single point
objects, double point objects, integrated totals.
4. If you wish to use a static point for reporting events, select a relation
and an operating threshold or a deadband to be used for detecting
events and check the Class 1 box for the point. The following options
are available:
• Delta – a new event is reported when the absolute value of the
difference between the last reported point value and its current value
exceeds the specified deadband value, or the status of a binary point
changes. Measured values with a zero deadband will not be checked
for events;
• More than (over) - a new event is reported when the point value rises
over the specified threshold, and then when it returns below the
threshold minus a predefined return hysteresis – applicable for
measured values;
• Less than (under) - a new event is reported when the point value
drops below the specified threshold, and then when it returns above
the threshold plus a predefined return hysteresis – applicable for
measured values.
Hysteresis of the return threshold for measured values is 0.05 Hz for frequency and 2% of the
operating threshold for other points.
All thresholds/deadbands for measured values should be specified in primary units.
5. Click Save as… to store your setup in the device site database, and
click Send to send the setup to the device.
Figure 9-6: Protocol Setup Dialog Box – IEC 60870-5 Class 2 Data and Counters Setup Tab
NOTES
• The configured IED name accompanies logical device names in object references.
• The device location also identifies the substation location in COMTRADE configuration files
as the station_name attribute.
• Attributes marked with the asterisk cannot be changed in the device via this setup but you
can define and store them to the device database when working offline to use for updating
a device CID file.
• The number of RCB instances defines how pre-defined RCBs are arranged in the device
for use in multi-client applications. The RCBs are automatically pre-configured in the device
in the way indicated in Section “Reporting model”. The RCB names and report IDs are set
to defaults as the number of RCB instances changes. If you intend to change the default
setting, set it first before configuring report control blocks.
3. Send your setup to the device and save it to the device database.
Figure 9-7: Protocol Setup Dialog Box – IEC 61850 IED Properties Setup Tab
Configuring Datasets
To review or configure the IEC 61850 datasets:
1. Select IEC 61850 Setup from the Meter Setup menu, and then click on the IEC 61850 Datasets
tab.
2. Select a dataset you wish to view or configure in the “Dataset Reference” box. Select “New
Dataset” to create a new dataset.
3. To delete dataset members, uncheck the appropriate “Included” boxes. Uncheck all dataset
members to delete the entire dataset.
4. To add or change dataset members, click “Edit from file”, locate the PM335_EM235.icd
template file or a CID file you generated for your device, and click Open.
A full list of the available data objects and data attributed is displayed, where included dataset
members are checked.
To create a new dataset, select a logical device where the dataset will be located and type a
dataset name in the “Dataset Name” box.
Check the “Included” boxes for items you wish to be members of the dataset and click OK.
To make easy selection of items across the list, use filters - functional constraints or/and a selected
logical device/logical node. Click “Filter checked” to see and revise a list of the selected items.
5. Send your new setup to the device and save it to the device database.
2. Select an RCB you wish to view or configure in the “RCB Reference” box.
3. Configure the RCB attributes as required for your application. The following items can be
configured:
• Report ID
• Dataset reference (can be selected from the available datasets list)
• Optional fields
• Trigger options
• Integrity period for periodic reports with the integrity trigger option selected
To change the Optional fields or Trigger options, click the arrow button at the right to the item,
check the appropriate options and click OK.
NOTE
Configure your new and customized datasets and update them in the device, or save to the device
database if you work offline, before configuring reports; otherwise you may get an incomplete
dataset list.
4. Send your new setup to the device and save it to the device database.
2. In the Subscription Number box, select the subscription you wish to configure.
3. Click the “Open SCL File” button and open an ICD or CID file for the publishing device you
wish to subscribe to. PAS shows you a list of all datasets linked to GOOSE publisher control
blocks that are found in the ICD/CID file. Check the Subscribe box for the dataset you wish to
subscribe to.
4. The publisher attributes and a list of dataset members for the selected dataset are displayed as
shown in the picture below. PAS also indicates a basic IEC 61850 data element type and a
physical MMS type for dataset members. Check the Subscribe boxes for elements you want to
subscribe to, and then click OK.
You are allowed to select no more than 16 elements. Elements with incompatible data types are not
allowed for selection.
The publisher attributes of the selected dataset and the selected data elements are copied to the
current subscription.
Select compatible input variables to which dataset elements will be mapped in the device. See the
table below for allowable mapping options depending on the basic variable type.
Basic Data Type MMS Data Type Compatible Input Variables
BitString32 Bstring32 ExtInd, ExtiVal
Dbpos Bstring8 ExtInd, ExtiVal
Enum INT8 ExtInd, ExtiVal
INT32 INT32 ExtInd, ExtiVal
INT32U INT32U ExtInd, ExtiVal
INT16 INT16 ExtInd, ExtiVal
INT16U INT16U ExtInd, ExtiVal
INT8 INT8 ExtInd, ExtiVal
INT8U INT8U ExtInd, ExtiVal
BOOLEAN BOOLEAN ExtInd, ExtiVal
FLOAT32 FLOAT32 ExtfVal
NOTES:
• Mapping integer data to a BOOLEAN ExtInd variable results in copying a
least-significant bit of the dataset member only.
• Mapping double-point data of type Dbpos to a BOOLEAN ExtInd variable
causes a high-order bit of the dataset member to be copied to the following
BOOLEAN ExtInd variable.
5. Check the application ID, configuration revision and destination MAC address to meet the
GOOSE publisher attributes.
6. Select Yes in the Subscription Enabled box to activate the subscription.
7. Repeat the setup for other subscriptions you wish to configure, and then send your setup to the
device and save to the device database. Notice that dataset member names are not stored in
the device and will not be displayed when reading the setup from the device unless you saved
the setup in the device database on your PC.
Enter the password and click OK. If your authorization was successful, you are not prompted for the
password again until you close the dialog window.
This window indicates the present GPRS communication status (see Setting Up GPRS Network in
Chapter 5) and connection statistics of the TCP clients (see Setting Up eXpertPower Client and
Setting Up TCP Notification Client in Chapter 5).
To clear the communication counters, click on Clear.
You can also clear the communications counters via the PAS Reset dialog (see Resetting
Accumulators, Maximum Values and Files).
≡/
ꭞ
Note:
The EM235 display menus is identical to the PM335 display menus
Reset Counters
Access Reset Setup menu, Select Counters and clear the desired counters as described below
using UP/DOWN navigation buttons and OK/ENTER button.
≡/
Note:
The EM235 display menus is identical to the PM335 display menus
Reset Logs
Access Reset Setup menu, Select Logs and clear the desired logs as described below using
UP/DOWN navigation buttons and OK/ENTER button.
≡/
Note:
The EM235 display menus is identical to the PM335 display menus
Using PAS
PAS allows you to clear energy accumulators, maximum demands, Min/Max log registers, counters
and log files in your device. To open the Reset dialog, select a device site from the list box on the
toolbar, check the On-line button on the toolbar, and then select Reset from the Monitor
menu.
To reset the desired accumulation registers or to clear a file, click on the corresponding button. If a
target has more than one component, you are allowed to select components to reset. Check the
corresponding boxes, and then click OK.
This section describes operations on the meter you can perform from the front display or via PAS.
To access device control options from PAS, you should have your meter online.
Some data sets are preset for your convenience and others are empty. You can freely modify data
sets.
Polling Devices
To run data polling, check the On-line button on the PAS toolbar, and then click on either the
Poll button or Continuous Poll button on the local toolbar. Click on the Stop button to
stop continuous polling,
You can open as many data monitor windows as you wish, either for different sites, or for the same
site using different data sets.
An open data monitor window is linked to the current site and does not change if you select another
site in the site list.
You can view acquired data in a tabular form or in a graphical form as a data trend.
The following picture shows a typical data monitor window.
Polling Options
To change the polling options, click on the Data Monitor window with the right mouse button and
select Options.
If you check “Do not stop on errors”, polling is resumed automatically when a communication error
occurs, otherwise polling stops until you restart it manually.
graph, click on the button on the local toolbar, and then select the desired date and time range.
Selecting Channels
To select data channels for your trend, click on the trend window with the right mouse button, select
“Channels”, check the channels you want displayed, and then click OK.
Delta Measurements
To measure the distance between two trend points, click on the Delta button on the toolbar,
click with the left mouse button on the first point, and then click on the second point. The first
reference point is frozen until you close and reopen Delta, while the second point can be placed
anywhere within the trend line. You can measure a delta in both directions. To disable Delta, click
on the Delta button again.
Using a Zoom
You can use a horizontal and a vertical zoom to change size of your graph. Use the buttons
on you local toolbar representing green arrowheads to zoom in or out of the trend graph.
Every click on these buttons gives you a 100-percent horizontal zoom. Two buttons
representing a magnifying glass give you a proportional zoom in both directions.
Printing Data
To print retrieved data, click the button on the PAS toolbar, select a printer, and then click OK.
To check the report, as it will look when printed, select Print Preview from the File menu.
Copying Data
To copy the entire data table or a part of a table into the Clipboard or into another application such
as Microsoft Excel or Word:
1. Click on the Data Monitor window with the right
mouse button and choose Select All, or click on
the upper-left corner of the data table (where
the “No.” label is displayed).
2. Click on the Data Monitor window with the right
mouse button again and choose Copy or click
on the Copy button on the PAS toolbar.
3. Run an application to where you want to copy
data, position cursor at the correct place, and
then click on the Paste button on the
application's toolbar, or select Paste from the
Edit menu.
If you want only a part of data to be copied, select with the mouse while holding the left mouse
button the rows or columns in the table you want to copy, and then click on the Copy button on
the PAS toolbar.
PAS retrieves harmonic spectrum for V1-V3 and I1-I3 channels. Harmonics can be displayed as a
spectrum chart for a selected channel or in a table. PAS can also synthesize waveforms based on
the harmonic spectrum to let you view a shape of the voltage and current waveforms in your
network.
Click on the button to view a spectrum chart for the selected channel. To change a channel,
click on the window with the right mouse button, select Channels..., check the channel you want
displayed, and then click OK. PAS provides voltage, current, active power and reactive power
spectrum charts.
PAS can give you indication on whether harmonic levels in the sampled waveforms exceed
compliance limits defined by the power quality standards or local regulations.
To review or change harmonic limits:
Click on the spectrum window with the
right mouse button and select Limits….
2 Select a known harmonics standard, or
select Custom and specify your own
harmonic limits.
3 Check the Enabled box to visualize
harmonic faults on the spectrum graph
and in harmonic tables.
Harmonics that exceed selected compliance levels are colored in red on the graph and in the
tables.
6. If you wish to retrieve data starting with a known date, check the
“From” box and select the start date for retrieving data.
7. If you wish to retrieve data recorded before a known date, check
the “To” box and select the last date for retrieving data.
8. Click OK.
Copying Data
To copy the entire data table or graph, or part of the data, into the Clipboard or into another
application such as Microsoft Excel or Word:
1. Click on the data window with the right mouse
button and choose Select All, or, if your current
view represents a table, click on the upper-left
corner of the table (where the “No.” label is
commonly displayed).
2. Click with the right mouse button on the window
again and choose Copy, or click on the Copy
button on the PAS toolbar.
3. Run the application to which you want to copy
data, position the cursor at the correct place,
and then click the Paste button on the
application's toolbar or select Paste from the
Edit menu.
Printing Reports
To print a data report to a printer, click on the print button on the toolbar, select a printer and
click OK. If you want to check how your document appears on the printed page, select Print
Preview from the File menu.
Customizing Views
Date Order
To change the way PAS displays the date, select Options from the Tools menu, click on the
Preferences tab, select the preferred date order, and then click OK.
Timestamp
The timestamp is normally recorded and displayed on the screen at a 1-ms resolution. If you have
an application that does not support this format, you may instruct PAS to drop the milliseconds. To
change the way PAS records and displays the timestamp, select Options from the Tools menu,
click on the Preferences tab, select the preferred timestamp format, and then click OK.
Viewing Options
Customizing Views
Changing Date Order
To change the way PAS displays the date:
Select Options from the Tools menu and
click on the Preferences tab.
Select the preferred date order.
Click OK.
Copying a Table
To copy the entire table, or its part, into the Clipboard or into another application such as Microsoft
Excel or Word:
Click on the data window with the right
mouse button and choose Select All, or
click on the upper-left corner of the table
(where the “No.” label is commonly
displayed).
Click with the right mouse button on the
window again and choose Copy, or click
on the Copy button on the PAS
toolbar.
Run the application to which you want to
copy data, position the cursor at the
correct place.
Click the Paste button on the
application's toolbar or select Paste from
the Edit menu.
When copying, table columns are separated by a tab character.
Printing a Table
To check how your document appears on a printed page, select Print Preview from the File menu.
To print a table to a printer, click on the print button on the toolbar, select a printer and click
OK.
To change the marker position, click on the button, or click on the window with the right mouse
button and select Set Marker, and then click on the point where you want to put the marker.
You can also drag both markers with the mouse, or use the right and left arrow keys on your
keyboard to change the marker position. Click on the graph pane to allow the keyboard to get your
input before using the keyboard.
Delta Measurements
To measure the distance between two waveform or trend points, click on the Delta button , then
click on the first point, and then click on the second point.
The first reference point is still frozen until you uncheck and check the Delta button again, while the
second point can be placed anywhere within the graph line by clicking on the graph to the left or
right from the reference point.
To disable delta measurements, click on the Delta button once again.
Using a Zoom
You can use a horizontal and, for waveforms, also a vertical, zoom to change size of your graph.
Use the buttons on your local toolbar to zoom in and zoom out. One click gives
you a 100-percent horizontal or 50-percent vertical zoom. Two buttons representing
magnifying glasses give you a proportional zoom in both directions.
Copying a Graph
To copy a graph, or its part, into the Clipboard or into another application such as Microsoft Excel or
Word:
Click on the graph window with the right
mouse button and choose Copy All, or
Copy Waveform. Some windows may
have additional options.
Position the cursor at the place where
you whish to copy the graph.
Printing a Graph
To check how the graph appears on a printed page, select Print Preview from the File menu.
To print a graph to a printer, click on the Print button on the PAS toolbar, select a printer and
click OK.
To change the default sorting order based on the date and time, click on the Sort button , or
click on the report window with the right mouse button and select “Sort...”, check the desired sort
order, and then click OK.
Linking to Waveforms and Data Records
If you programmed a setpoints to log setpoints operations to the Event log and the setpoints can
trigger the Waveform or Data recorder, PAS automatically establishes links between the event and
other database records where it finds a relationship with the event. Waveforms recorded at the time
of the event are always linked to this event, even if the waveform was triggered by another source.
The event ID for which PAS finds related data is blue colored. Click on the colored event ID to
check a list of the event links. Click on a list item to move to the related waveform or data log
record.
To filter events, click on the Filter button , or click on the report window with the right mouse
button and select “Filter...”, check the categories of events you want to display, and then click OK.
To change the default event sorting order, click on the Sort button , or click on the report window
with the right mouse button and select “Sort...”, check the desired sort order, and then click OK.
To change the time range for your graph, click on the Time Range button on the local toolbar,
and then select the desired date and time range.
Selecting Channels
To select desired data channels for your trend, click on the trend window with the right mouse
button, select “Channels”, check the channels you want displayed, and then click OK.
Using a Zoom
You can use a horizontal and a vertical zoom to change size of your graph. Use the
buttons on you local toolbar representing green arrowheads to zoom in and zoom out. One click
gives you a 100-percent horizontal zoom. Two buttons representing magnifying glasses
give you a proportional zoom in both directions.
Delta Measurements
To measure the distance between two trend points, click on the Delta button , then click on the
first point, and then click on the second point. The first reference point is still frozen until you close
and reopen Delta, while the second point can be placed anywhere within the trend line. You can
measure a delta in both directions. To disable delta measurements, click on the Delta button once
again.
Viewing Waveforms
Waveform data can be displayed in five different views. When you open a new file, PAS shows you
a waveform graph showing non-overlapped waveforms. Each waveform window has a local toolbar
from where you can open another window to examine the waveform in a different view.
You can open all five views together to analyze different properties of the waveform like a wave
shape, waveform disturbance, unbalance, or spectrum. When you move to another waveform
record, all views are updated simultaneously to reflect the changes.
To view overlapped waveforms, click on the button on the local toolbar; to view non-
overlapped waveforms, click on the button.
Waveform data is recorded in series that may contain many cycles of the sampled waveform. A
waveform window displays up to 128 waveform cycles. If the waveform contains more cycles, the
scroll bar appears under the waveform pane allowing you to scroll through the entire waveform.
To view a cycle-by-cycle frequency plot of the sampled voltage waveforms, click on the button.
The order of the highest displayed harmonic component is equal to the half sampling rate at which
the waveforms are sampled minus one. If the waveform was sampled at a rate of 256 samples per
cycle, 63 harmonics are available. With 32 samples per cycle, only 15 harmonics are calculated,
while others will be zeros.
PAS can give you indication on whether harmonic levels in the sampled waveforms exceed
compliance limits defined by the power quality standards or local regulations.
To review or change harmonic limits:
1. Click on the spectrum window with the right
mouse button and select “Limits…”.
2. Select a harmonics standard, or select
“Custom” and specify your own harmonic limits.
3. Check the Enabled box to visualize harmonic
faults on the spectrum graph and in harmonic
tables.
Harmonics that exceed selected compliance levels are colored in red on the graph and in the
tables.
To change a phase, click on the window with the right mouse button, select “Options...”, check the
phase you want displayed, and then click OK.
Waveform Options
Scrolling through Waveforms
The status bar at the bottom of the window shows you how many records the log file contains. Use
green arrowheads on the window toolbar to scroll through records.
To select the channels you want to view on the screen, click on the waveform window with the right
mouse button, select “Channels...”, check the channels you want displayed, and then click OK.
Checkboxes for channels that are not present in the waveform are dimmed.
To change the reference channel, click on the waveform window with the right mouse button, select
“Options...”, click on the “Phasor” tab, check the channel you want to make a reference channel,
and then click “OK”.
If you leave the Triangle box checked, PAS connects the ends of the voltage and current vectors
showing you three-phase voltage and current triangles. This is useful when analyzing voltage and
current unbalances.
Phasor diagrams are calculated over one waveform cycle pointed to by the left marker line. As you
move the marker, the phasor diagrams are updated reflecting the new marker position.
To change the marker position, click on the button, or click on the waveform window with the
right mouse button and select Set Marker, and then click on the point where you want to put the
marker. You can drag both markers with the mouse, or use the right and left arrow keys on your
keyboard to change the marker position. Click on the waveform pane to allow the keyboard to get
your input before using the keyboard.
Using a Zoom
You can use a horizontal and a vertical zoom to change size of your waveforms. Use the buttons
on you local toolbar representing green arrowheads to zoom in or out of the
waveform graph. Every click on these buttons gives you a 100-percent horizontal or 50-percent
vertical zoom. Two buttons give you a proportional zoom in both directions.
When in the overlapped waveform view, you can zoom in on a selected waveform region. Click on
the waveform window with the right mouse button, click 'Zoom', point onto one of the corners of the
region you want to zoom in, press and hold the left mouse button, then point to another corner of
the selected region and release the mouse button.
Delta Measurements
To measure the distance between two waveform points, click on the Delta button , then click on
one point, and then click on the second point. The first reference point is still frozen until you close
and reopen Delta, while the second point can be placed anywhere within the waveform line. You
can measure a delta in both directions. To disable the Delta, click on the Delta button once again.
NOTE
When reading multi-section profile data, only the first section is available for reading online.
See Chapter 9 Viewing Files for information on using different log views.
Exporting Files
Exporting Files in COMTRADE and PQDIF Formats
The COMTRADE and PQDIF file converters allow you to convert saved real-time waveforms into
COMTRADE or PQDIF file format, and data log tables – into PQDIF format.
Manual Converting
To manually convert your waveforms or a data log into COMTRADE or PQDIF format:
Click on the Export button on the PAS toolbar.
2. Select the database and a data log table you want to export, and
then click Open.
3. Select a folder where you want to store your exported files, type a
file name that identifies your files, select a file output format, and
then click on the Save button.
4. The PQDIF files are commonly recorded in compressed format. If
you do not want your files to be compressed, uncheck the
Compress box before saving the file.
In COMTRADE format, each waveform event is recorded into a separate file.
PQDIF file names are followed by a timestamp of the first event recorded to the file, and may look
like follows:
PM130 PRO dl14_20190404T174843.pqd.
Automatic Converting
PAS allows you to automatically convert data logs into PQDIF format at the time you upload data
from your devices via the Upload Scheduler.
To automatically convert your data log tables into PQDIF format:
Open the Upload Scheduler.
Highlight a desired device site with the
left mouse button, and then click on the
Export button.
Check the Enabled box for a data log or a
waveform log table you want to
automatically convert at the upload time.
Highlight the Record to… row for the
selected table and click on the Browse
button.
Select a folder where you want to store
converted files, type in the converted file’s
name, select a desired output file format,
and then click on Save.
Repeat the same for all tables you wish to
be converted.
Click OK.
Archiving Files
Microsoft Access databases tend to grow fast. Databases above 0.5 Gigabytes can drastically slow
down file operations.
To avoid enormous growing files, you can either periodically change the target database, or use the
Upload Scheduler’s file archiver to automatically move older data to archives.
The Upload Scheduler archives files upon a weekly, monthly or yearly schedule. When archiving
data, a new database is created to where older data from your present database with the expired
archiving date is moved.
An archive file keeps the original database name to which the date of the oldest database record is
added, so you can easily identify your archives and work with them as you work with a regular
database.
To provide a schedule for archiving files:
When defining a schedule for uploading
files from your meter, click on Configure
or double click on the site row.
Click Auto Archive.
Construction
Dimensions see Figure 2-1
Weight: 0.70 kg (1.54 lb.)
Materials
Case enclosure: plastic PC/ABS blend
Front panel: plastic PC
PCB: FR4 (UL94-V0)
Terminals: PBT (UL94-V0)
Connectors-Plug-in type: Polyamide PA6.6 (UL94-V0)
Packaging case: Carton and Stratocell® (Polyethylene Foam) brackets
Labels: Polyester film (UL94-V0)
Input Ratings
Voltage input rating L-N (L-L) Measurement CAT III
Operating range: 5 VAC (L-N)/ 8VAC (L-L) to 690 VAC (L-N)/ 1000 VAC (L-L)¹
Input impedance: 4000 kΩ
Burden for 400V: < 0.04 VA
Burden for 120V: < 0.01VA
Over-voltage withstands: 1000 VAC continuous, 2000 VAC for 1 second
Isolation: 4000VAC @ 1mn
Wire size: up to 10 AWG (> 4.5 mm2)
¹_UL Listing covers the nominal Voltage Input up to 277V L-N (480V L-L)
Built-in option
Solid State relay option
1 relays rated at 50mA/250 V AC/DC, 1 contact (SPST Form A, Resistive load)
Galvanic isolation: 4000VAC @ 1mn
Operate time: 1 ms max.
Release time: 0.25 ms max.
Update time: 1 cycle
Connector type: removable, 2 pins.
Wire size: 14 AWG (up to 1.5 mm2)
Built-in (optional)
2 digital inputs
Dry Contacts, internally wetted @ 24VDC
Galvanic isolation: 4000VAC @ 1mn
Internal power supply: 24VDC
Scan time: 1 ms
Connector type: removable, 5 pins.
Wire size: 14 AWG (up to 1.5 mm2)
Communication Ports
COM1
RS-485 optically isolated port
Isolation: 4000VAC @ 1mn
Baud rate: up to 115.2 kbps.
Supported protocols: MODBUS RTU, DNP3, SATEC ASCII, IEC 60870-5-101
Connector type: removable, 3 pins.
Wire size: up to 14 AWG (up to 1.5 mm2).
COM4
Infra Red COM port
Isolation: 4000VAC @ 1mn
Baud rate: up to 38.4 kbps.
Supported protocols: MODBUS RTU, IEC 62056-21 (future)
Front Panel access with magnetic head
Real-time Clock
Standard Meter Clock (PM335 PRO regular version)
Battery backup clock
Accuracy: typical error 15 seconds per month/ < 5 minutes/year @ 25°C
Typical clock retention time: 24 months
Display
PM335
3.5" LCD TFT color Display, 320 x 480 dots resolution
Tri-color LED load bar graph (40-110%)
Diagnostics indication LED
kWh/kvarh Pulse LED
Keypad: 5 push buttons
EM235
1.77” LCD TFT color Display, 120 x 160 dots resolution
Diagnostics indication LED
kWh/kvarh Pulse LED
Keypad: 4 push buttons
Standards Compliance
Accuracy:
Meets IEC62053-22:2003, class 0.2S
Meets IEC 62053-24:2020, class 0.5S
Meets ANSI C12.20 –2015, class 10 0.2%
Electromagnetic Immunity:
Comply with IEC 61000-6-2:
IEC 61000-4-2 level 3: Electrostatic Discharge
IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
IEC 61000-4-4 level 3: Electric Fast Transient
IEC 61000-4-5 level 3: Surge
IEC 61000-4-6 level 3: Conducted Radio Frequency
IEC 61000-4-8: Power Frequency Magnetic Field
Meets ANSI/IEEE C37.90.1: Fast Transient SWC
Electromagnetic Emission:
Complies with IEC 61000-6-4: Radiated/Conducted class B
Complies with IEC CISPR 22: Radiated/Conducted class B
Safety/Construction:
Meets IEC/UL 61010-1, 3rd ed.
AC and Impulse Insulation:
Meets IEC 62052-11:
4000 VAC during 1 minute
6KV/500Ω @ 1.2/50 μs impulse
Degree of Protection: IP51
UL Listing covers the base unit, the optional modules are not a part of UL listing
Real-time Clock
Accuracy: typical error 1 minute per month @ 25°C
Typical clock retention time: 2 years
Standards Compliance
Accuracy:
Meet IEC62053-22, class 1
Electromagnetic Immunity:
Comply with IEC 61000-6-2:
IEC 61000-4-2 level 3: Electrostatic Discharge
IEC 61000-4-3 level 3: Radiated Electromagnetic RF Fields
IEC 61000-4-4 level 3: Electric Fast Transient
IEC 61000-4-5 level 4: Surge
IEC 61000-4-6 level 3: Conducted Radio Frequency
IEC 61000-4-8: Power Frequency Magnetic Field
Electromagnetic Emission:
Comply with IEC 61000-6-4: Radiated/Conducted class A
Comply with IEC CISPR 22: Radiated/Conducted class A
Safety/Construction: Meets UL/IEC 61010
9E6x0_Exx04_50Hz/60Hz
9EHA6x0_Exx04_50Hz/60Hz
Measurement Specifications
Table 22: Measurement Specifications Parameters
Designation Description
NONE None (stub, read as zero)
DIGITAL INPUTS Digital Inputs
DI1:16 Digital Inputs Status DI1:DI12
RELAYS Relays
RO1:16 Relay Status RO1:RO4
COUNTERS Pulse Counters
COUNTER 1 Counter #1
COUNTER 2 Counter #2
COUNTER 3 Counter #3
COUNTER 4 Counter #4
RT PHASE 1-Cycle Phase Values
V1 V1/V12 Voltage 1
V2 V2/V23 Voltage 1
V3 V3/V31 Voltage 1
I1 I1 Current
I2 I2 Current
I3 I3 Current
kW L1 kW L1
kW L2 kW L2
kW L3 kW L3
kvar L1 kvar L1
kvar L2 kvar L2
kvar L3 kvar L3
kVA L1 kVA L1
kVA L2 kVA L2
kVA L3 kVA L3
PF L1 Power factor L1
PF L2 Power factor L2
PF L3 Power factor L3
V1 THD V1/V12 Voltage THD 1
V2 THD V2/V23 Voltage THD 1
V3 THD V3/V31 Voltage THD 1
I1 THD I1 Current THD
I2 THD I2 Current THD
I3 THD I3 Current THD
I1 KF I1 K-Factor
I2 KF I2 K-Factor
I3 KF I3 K-Factor
I1 TDD I1 Current TDD
I2 TDD I2 Current TDD
I3 TDD I3 Current TDD
V12 V12 Voltage
V23 V23 Voltage
Designation Description
V31 V31 Voltage
RT TOTAL 1-Cycle Total Values
kW Total kW
kvar Total kvar
kVA Total kVA
PF Total PF
PF LAG Total PF lag
PF LEAD Total PF lead
kW IMP Total kW import
kW EXP Total kW export
kvar IMP Total kvar import
kvar EXP Total kvar export
V AVG 3-phase average L-N/L-L voltage
V LL AVG 3-phase average L-L voltage
I AVG 3-phase average current
RT AUX 1-Cycle Auxiliary Values
In In (neutral) Current
FREQ Frequency
V UNB% Voltage unbalance 2
I UNB% Current unbalance 2
AVR PHASE 1-Second Phase Values
V1 V1/V12 Voltage
V2 V2/V23 Voltage
V3 V3/V31 Voltage
I1 I1 Current
I2 I2 Current
I3 I3 Current
kW L1 kW L1
kW L2 kW L2
kW L3 kW L3
kvar L1 kvar L1
kvar L2 kvar L2
kvar L3 kvar L3
kVA L1 kVA L1
kVA L2 kVA L2
kVA L3 kVA L3
PF L1 Power factor L1
PF L2 Power factor L2
PF L3 Power factor L3
V1 THD V1/V12 Voltage THD 1
V2 THD V2/V23 Voltage THD 1
V3 THD V3/V31 Voltage THD 1
I1 THD I1 Current THD
I2 THD I2 Current THD
I3 THD I3 Current THD
I1 KF I1 K-Factor
I2 KF I2 K-Factor
I3 KF I3 K-Factor
I1 TDD I1 Current TDD
I2 TDD I2 Current TDD
I3 TDD I3 Current TDD
V12 V12 Voltage
Designation Description
V23 V23 Voltage
V31 V31 Voltage
AVR TOTAL 1-Second Total Values
kW Total kW
kvar Total kvar
kVA Total kVA
PF Total PF
PF LAG Total PF lag
PF LEAD Total PF lead
kW IMP Total kW import
kW EXP Total kW export
kvar IMP Total kvar import
kvar EXP Total kvar export
V AVG 3-phase average L-N/L-L voltage 1
V LL AVG 3-phase average L-L voltage
I AVG 3-phase average current
AVR AUX 1-Second Auxiliary Values
In In (neutral) Current
FREQ Frequency
V UNB% Voltage unbalance 2
I UNB% Current unbalance 2
PHASORS Phasors
V1 Mag V1/V12 Voltage magnitude 1
V2 Mag V2/V23 Voltage magnitude 1
V3 Mag V3/V31 Voltage magnitude 1
I1 Mag I1 Current magnitude
I2 Mag I2 Current magnitude
I3 Mag I3 Current magnitude
V1 Ang V1/V12 Voltage angle 1
V2 Ang V2/V23 Voltage angle 1
V3 Ang V3/V31 Voltage angle 1
I1 Ang I1 Current angle
I2 Ang I2 Current angle
I3 Ang I3 Current angle
DEMANDS Present Demands (Power Demands E, EH)
V1 DMD V1/V12 Volt demand 1
V2 DMD V2/V23 Volt demand 1
V3 DMD V3/V31 Volt demand 1
I1 DMD I1 Ampere demand
I2 DMD I2 Ampere demand
I3 DMD I3 Ampere demand
kW IMP BD kW import block demand
kvar IMP BD kvar import block demand
kVA BD kVA block demand
kW IMP SD kW import sliding window demand
kvar IMP SD kvar import sliding window demand
kVA SD kVA sliding window demand
kW IMP ACD kW import accumulated demand
kvar IMP ACD kvar import accumulated demand
kVA ACD kVA accumulated demand
kW IMP PRD kW import predicted sliding window demand
Designation Description
kvar IMP PRD kvar import predicted sliding window demand
kVA PRD kVA predicted sliding window demand
PF IMP@kVA DMD PF (import) at Maximum kVA sliding window demand
kW EXP BD kW export block demand
kvar EXP BD kvar export block demand
kW EXP SD kW export sliding window demand
kvar EXP SD kvar export sliding window demand
kW EXP ACD kW export accumulated demand
kvar EXP ACD kvar export accumulated demand
kW EXP PRD kW export predicted sliding window demand
kvar EXP PRD kvar export predicted sliding window demand
In DMD In (neutral) current demand
SUMM ACC DMD Billing Summary (Total) Accumulated Demands E, EH
REG1 ACD Register #1 accumulated demand
REG2 ACD Register #2 accumulated demand
REG3 ACD Register #3 accumulated demand
REG4 ACD Register #4 accumulated demand
SUMM BLK DMD Billing Summary (Total) Block Demands E, EH
REG1 BD Register #1 block demand
REG2 BD Register #2 block demand
REG3 BD Register #3 block demand
REG4 BD Register #4 block demand
SUMM SW DMD Billing Summary (Total) Sliding Demands E, EH
REG1 SD Register #1 sliding demand
REG2 SD Register #2 sliding demand
REG3 SD Register #3 sliding demand
REG4 SD Register #4 sliding demand
ENERGY Total Energy E, EH
kWh IMPORT kWh import
kWh EXPORT kWh export
kvarh IMPORT kvarh import
kvarh EXPORT kvarh export
kVAh TOTAL kVAh total
SUMMARY REGS Billing Summary (Total) Energy Registers E, EH
SUM REG1 Summary energy register #1
SUM REG2 Summary energy register #2
SUM REG3 Summary energy register #3
SUM REG4 Summary energy register #4
PHASE ENERGY Phase Energy E, EH
kWh IMP L1 kWh import L1
kWh IMP L2 kWh import L2
kWh IMP L3 kWh import L3
kvarh IMP L1 kvarh import L1
kvarh IMP L2 kvarh import L2
kvarh IMP L3 kvarh import L3
kVAh L1 kVAh total L1
kVAh L2 kVAh total L2
kVAh L3 kVAh total L3
%HD V1 V1/V12 Harmonic Distortions EH 1
V1 %HD01 H01 Harmonic distortion
V1 %HD02 H02 Harmonic distortion
… ...
Designation Description
V1 %HD40 H40 Harmonic distortion
%HD V2 V2/V23 Harmonic Distortions EH 1
V2 %HD01 H01 Harmonic distortion
V2 %HD02 H02 Harmonic distortion
… ...
V2 %HD40 H40 Harmonic distortion
%HD V3 V3/V31 Harmonic Distortions EH 1
V3 %HD01 H01 Harmonic distortion
V3 %HD02 H02 Harmonic distortion
… ...
V3 %HD40 H40 Harmonic distortion
%HD I1 I1 Harmonic Distortions EH
I1 %HD01 H01 Harmonic distortion
I1 %HD02 H02 Harmonic distortion
… ...
I1 %HD40 H40 Harmonic distortion
%HD I2 I2 Harmonic Distortions EH
I2 %HD01 H01 Harmonic distortion
I2 %HD02 H02 Harmonic distortion
… ...
I2 %HD40 H40 Harmonic distortion
%HD I3 I3 Harmonic Distortions EH
I3 %HD01 H01 Harmonic distortion
I3 %HD02 H02 Harmonic distortion
… ...
I3 %HD40 H40 Harmonic distortion
ANG V1 V1/V12 Harmonic Angles EH 1
V1 H01 ANG H01 Harmonic angle
V1 H02 ANG H02 Harmonic angle
… ...
V1 H40 ANG H40 Harmonic angle
ANG V2 V2/V23 Harmonic Angles EH 1
V2 H01 ANG H01 Harmonic angle
V2 H02 ANG H02 Harmonic angle
… ...
V2 H40 ANG H40 Harmonic angle
ANG V3 V3/V31 Harmonic Angles EH 1
V3 H01 ANG H01 Harmonic angle
V3 H02 ANG H02 Harmonic angle
… ...
V3 H40 ANG H40 Harmonic angle
ANG I1 I1 Harmonic Angles EH
I1 H01 ANG H01 Harmonic angle
I1 H02 ANG H02 Harmonic angle
… ...
I1 H40 ANG H40 Harmonic angle
ANG I2 I2 Harmonic Angles EH
I2 H01 ANG H01 Harmonic angle
I2 H02 ANG H02 Harmonic angle
… ...
I2 H40 ANG H40 Harmonic angle
ANG I3 I3 Harmonic Angles EH
Designation Description
I3 H01 ANG H01 Harmonic angle
I3 H02 ANG H02 Harmonic angle
… ...
I3 H40 ANG H40 Harmonic angle
H1 PHASE Fundamental (H01) Phase Values
V1 H01 V1/V12 Voltage 1
V2 H01 V2/V23 Voltage 1
V3 H01 V3/V31 Voltage 1
I1 H01 I1 Current
I2 H01 I2 Current
I3 H01 I3 Current
kW L1 H01 kW L1
kW L2 H01 kW L2
kW L3 H01 kW L3
kvar L1 H01 kvar L1
kvar L2 H01 kvar L2
kvar L3 H01 kvar L3
kVA L1 H01 kVA L1
kVA L2 H01 kVA L2
kVA L3 H01 kVA L3
PF L1 H01 Power factor L1
PF L2 H01 Power factor L2
PF L3 H01 Power factor L3
HRM TOT POW Fundamental and Harmonic Total Power Values
kW H01 Total fundamental kW
kvar H01 Total fundamental kvar
kVA H01 Total fundamental kVA
PF H01 Total fundamental PF
MIN PHASE Minimum 1-Cycle Phase Values
V1 MIN V1/V12 Voltage 1
V2 MIN V2/V23 Voltage 1
V3 MIN V3/V31 Voltage 1
I1 MIN I1 Current
I2 MIN I2 Current
I3 MIN I3 Current
MIN TOTAL Minimum 1-Cycle Total Values
kW MIN Total kW
kvar MIN Total kvar
kVA MIN Total kVA
PF MIN Total PF
MIN AUX Minimum 1-Cycle Auxiliary Values
In MIN In Current
FREQ MIN Frequency
MAX PHASE Maximum 1-Cycle Phase Values
V1 MAX V1/V12 Voltage 1
V2 MAX V2/V23 Voltage 1
V3 MAX V3/V31 Voltage 1
I1 MAX I1 Current
I2 MAX I2 Current
I3 MAX I3 Current
MAX TOTAL Maximum 1-Cycle Total Values
Designation Description
kW MAX Total kW
kvar MAX Total kvar
kVA MAX Total kVA
PF MAX Total PF
MAX AUX Maximum 1-Cycle Auxiliary Values
In MAX In Current
FREQ MAX Frequency
MAX DMD Maximum Demands (Power Demands E, EH)
V1 DMD MAX V1/V12 Maximum volt demand 1
V2 DMD MAX V2/V23 Maximum volt demand 1
V3 DMD MAX V3/V31 Maximum volt demand 1
I1 DMD MAX I1 Maximum ampere demand
I2 DMD MAX I2 Maximum ampere demand
I3 DMD MAX I3 Maximum ampere demand
kW IMP SD MAX Maximum kW import sliding window demand
kW EXP SD MAX Maximum kvar import sliding window demand
kvar IMP SD MAX Maximum kW export sliding window demand
kvar EXP SD MAX Maximum kvar export sliding window demand
kVA SD MAX Maximum kVA sliding window demand
In DMD MAX In (neutral) current maximum demand
MAX SUMMARY DMD Billing Summary (Total) Maximum Demands E, EH
REG1 MD Summary register #1 maximum demand
REG2 MD Summary register #2 maximum demand
REG3 MD Summary register #3 maximum demand
REG4 MD Summary register #4 maximum demand
AO RAW Raw Analog Outputs (A/D Units)
AO1 Analog output AO1
AO2 Analog output AO2
AO3 Analog output AO3
AO4 Analog output AO4
TOU PRMS TOU Parameters E, EH
ACTIVE TARIFF Active TOU tariff
ACTIVE PROFILE Active TOU profile
TOU REG1 Billing TOU Energy Register #1 E, EH
REG1 TRF1 Tariff #1 register
REG1 TRF2 Tariff #2 register
… …
REG1 TRF8 Tariff #8 register
TOU REG2 Billing TOU Energy Register #2 E, EH
REG2 TRF1 Tariff #1 register
REG2 TRF2 Tariff #2 register
… …
REG2 TRF8 Tariff #8 register
TOU REG3 Billing TOU Energy Register #3 E, EH
REG3 TRF1 Tariff #1 register
REG3 TRF2 Tariff #2 register
… …
REG3 TRF8 Tariff #8 register
TOU REG4 Billing TOU Energy Register #4 E, EH
REG4 TRF1 Tariff #1 register
REG4 TRF2 Tariff #2 register
… …
Designation Description
REG4 TRF8 Tariff #8 register
TOU MAX DMD REG1 Billing TOU Maximum Demand Register #1 E, EH
REG1 TRF1 MD Tariff #1 maximum demand
REG1 TRF2 MD Tariff #2 maximum demand
… …
REG1 TRF8 MD Tariff #8 maximum demand
TOU MAX DMD REG2 Billing TOU Maximum Demand Register #2 E, EH
REG2 TRF1 MD Tariff #1 maximum demand
REG2 TRF2 MD Tariff #2 maximum demand
… …
REG2 TRF8 MD Tariff #8 maximum demand
TOU MAX DMD REG3 Billing TOU Maximum Demand Register #3 E, EH
REG3 TRF1 MD Tariff #1 maximum demand
REG3 TRF2 MD Tariff #2 maximum demand
… …
REG3 TRF8 MD Tariff #8 maximum demand
TOU MAX DMD REG4 Billing TOU Maximum Demand Register #4 E, EH
REG4 TRF1 MD Tariff #1 maximum demand
REG4 TRF2 MD Tariff #2 maximum demand
… …
REG4 TRF8 MD Tariff #8 maximum demand
1 In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be line-to neutral; for any other wiring
mode, they will be line-to-line voltages.
2 The value is calculated as a relation of the maximum deviation of phase values from a 3-phase
average value to a 3-phase average.
NOTE
Designations of some enginering demands and billing energy and demand registers are shown
using a short name notation available in PAS V1.4. By default, PAS uses long names compatible
with older versions of PAS. You can select a desired notation from the Tools/Options/Preferences
tab.
PAS does not allow to store data in files using different data names. If you have a file uploaded with
a previous version of PAS using long data names, either continue using long data names, or store
data in a new file.
See table below for a list of parameters with short and long names.
Short Data Name Long Data Name Description
kW IMP ACD kW IMP ACC DMD Accumulated demand
kW IMP PRD kW IMP PRD DMD Predicted sliding window demand
PF IMP@kVA MD PF IMP@kVA MXDMD PF (import) at maximum kVA demand
REG1 ACD SUM REG1 ACC DMD Billing summary (total) register accumulated demand
REG1 BD SUM REG1 BLK DMD Billing summary (total) register block demand
REG1 SD SUM REG1 SW DMD Billing summary (total) register sliding demand
REG1 SUM REG1 Billing summary (total) energy register
REG1 MD SUM REG1 DMD MAX Billing summary (total) register maximum demand
REG1 TRF1 TOU REG1 TRF1 Billing tariff energy register
REG1 TRF1 MD DMD1 TRF1 MAX Billing tariff register maximum demand
TRF1 SEASON TRF1 Generic billing tariff energy register
TRF1 MD SEASON TRF1 Generic billing tariff register maximum demand