Coldspell Manual Rev2
Coldspell Manual Rev2
Coldspell
Contents
1.
1.1 1.2
Introduction
Design Description
2. 3.
3.1 3.2 3.3 3.4
Specifications
Operational Details
3 4
Operating Principle
Pneumatic Section Refrigeration section Safety Schematic Diagrams
4. 5.
5.1 5.2 5.3 5.4
9 12
6.
6.1 6.2
Operation
Operator How to stop the Dryer
14
7. 8.
8.1 8.2
15 16
9. 10. 11.
Amount of Gas to be charged Repair Work Recommended spares list for 5 years
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
17 18 21
1
READ THIS MANUAL CAREFULLY BEFORE INSTALLING OR OPERATING THE EQUIPMENT These symbols warn you of any dangers and the measures to be taken to prevent them.
The most important points for the correct operation of your dryer are printed in bold type.
1. Introduction
1.1 Design Coldspell refrigeration dryer eliminates any water vapour remaining in the compressed air coming at the outlet of the compressor house. The dryers have been designed for nominal standard inlet conditions as per ISO 7183 in order to obtain a dew point under pressure of + 3oC. 1.2 Description The dryer consists of : Air to Air Heat exchanger Air to Freon Evaporator Demister Refrigerant Compressor Electronic controller Condenser Assembly Expansion Device Pressure switch* Refrigerant discharge pressure gauge* Hot gas bypass valve Auto drain valve Canopy
* Optional
Reference : Manual Version 2
2. Specifications
Operational Details Medium Inlet condition Operating pressure* Inlet temperature* Inlet humidity Ambient temperature Pressure dew point Cooling system Max. Working pressure Refrigerant compressor : Compressed Air : Free of dirt, oil, condensate and corrosive substances. : 7 Kg/cm2 : Max +45oC : Saturated at specified conditions : Max +38oC : + 3oC to 7oC : Air cooled / Water cooled : 16 Kg/cm2 : Hermetic sealed
* Optional
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
3. Operating Principle
3.1 Pneumatic section The moist compressed air (dirt, oil and water vapor) enters into the Air/Air Heat Exchanger where it is precooled by the outgoing air and thereby conserving energy. The compressed air next passes through the evaporator. It is cooled up to +3oC by the Refrigerant. At this sub-cooled temperature, the moisture present in the air is condensed and removed by the Demister. The cool saturated air passes through the Air to Air Heat Exchanger where it precools incoming air and it gets heated up. Thus this system provides clean dry air at the Outlet. Efficient Filter and Automatic Drain Valve carry out the removal of moisture at Demister. The Heat Exchangers are designed in such a way that they are self-cleaning to maintain the constant heat transfer rate. 3.2 Refrigeration section (Freon) The Evaporator remove heat from compressed air by means of cold and low pressure freon. The heat removed from the system is dissipated to the atmosphere/water by the condenser. The high pressure refrigerant flows into the expansion valves where it changes into liquid phase at low pressure. The boiling of liquid refrigerant takes place in Evaporator and cold air leaves from the Evaporator. The low pressure, low temperature refrigerant passes into the compressor and the cycle repeats. The Refrigeration Dryer senses the Refrigerant suction pressure and accordingly varies the flow of Hot Gas Bypass inside the system and maintains constant Dew point at various heat loads.
3.3 Safety
Pressurised equipments may explode if used improperly. It is therefore essential to locate any pressurised equipment, in such a way that the risks relating to incorrect use are reduced to the absolute minimum.
The person responsible for the stuff who is going to install, operate and maintain the machines described in this manual must make sure that they have read and understood these instructions. In particular we draw your attention to the safety procedures which are described in this manual and which must be scrupulously adhered to. Observing these measures will allow you to install, operate and maintain your dryer without risk. Coldspell dryers are intended for the drying of compressed air. Under no circumstances should they be used to dry other gases before Trident has performed a preliminary study and provided special instructions. 3.4 Schematic Diagrams
Model :
Coldspell 10-60
EXPANSION DEVICE DISCHARGE PRESSURE GAUGE
EVAPORATOR
REF. COMP.
ELECTRONIC CONTROLLER
CHARGING VALVE
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
Model :
EVAPORATOR
REF. COMP.
ELECTRONIC CONTROLLER
Model :
Coldspell 150-250
DISCHARGE PRESSURE GAUGE EXPANSION DEVICE
EVAPORATOR
REF. COMP.
Model :
Coldspell 300-500
DISCHARGE PRESSURE GAUGE EXPANSION DEVICE
EVAPORATOR
REF. COMP.
ELECTRONIC CONTROLLER
Model :
Coldspell 650-1000
EXPANSION DEVICE
EVAPORATOR
REF. COMP.
ELECTRONIC CONTROLLER
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
WATER OUT
REF. COMP.
CHARGING VALVE
4. Wiring Diagrams
Model :
Coldspell 10 to 100
L E COMPRESSOR K1
S C R
OLP
J4 1 2 3
J5-2
CONDENSOR FAN
JUNCTION BOX N N N
Model :
Coldspell 150
1
SW 16A
A2
L2 T2
J4 L N E 1 2 3 J5-3 J3-3 J1-1 J1-2 DRAIN VALVE 24V DC CONTROL CARD J2-2 J2-1 TEMPERATURE SENSOR
L1
C1 A1
J5-2
K1
AC
T1 2
J3-2
COMPRESSOR
CONDENSOR FAN
N COMPRESSOR
N
N
OLP
3 1
POTENTIAL RELAY
K1 : Hot gas Bypass Valve C1 : Contactor Coil A1, A2 AC : Auxiliary Contactor PS : Pressure Switch
TOP
230V, 50Hz 1Phase Supply L
4 5 2 1
Starting Capacitor
JUNCTION BOX
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
1
SW 16A
3 L2 T2 4
L N E J4 1 2 3
A2 1 PS 4
J5-2 J3-2
L1
C1 A1
K1
AC
T1 2
J5-3
N N
COMPRESSOR
CONDENSOR FAN
COMPRESSOR
K1 : Hot gas Bypass Valve C1 : Contactor Coil A1, A2 AC : Auxiliary Contactor PS : Pressure Switch
N L Starting Capacitor
Model :
Coldspell 300
L L E
A2
1
SW 16A
3 L2 T2 4 1
C1 A1
J5-2 J4 L N E 1 TEMPERATURE 2 3 J5-3 J1-1 J1-2 DRAIN VALVE 24V DC CONTROL CARD SENSOR
L1
AC
T1 2
PS
4
N N
COMPRESSOR
CONDENSOR FAN
COMPRESSOR
N L Starting Capacitor
10
Model :
L3 N
L3
1 L1
SW 16A
3 L2
5 L3 PS 1 4
J5-2 J4 L N E 1 2 3 J5-3 J1-1 J1-2 DRAIN VALVE 24V DC CONTROL CARD J2-2 J2-1 TEMPERATURE SENSOR
AC T1 2 T2 4 T3 6
L1 L1 L2 L3 N
L2
L3
L3
COMPRESSOR
CONDENSOR FAN N
Model :
L3 N
L3 N
L3
1 L1
SW 23A
3 L2
5 L3
21
N/O
A2 1 PS C1 A1 4
J5-2 J4 L N E 1 2 3 J5-3 J1-1 J1-2 DRAIN VALVE 24V DC CONTROL CARD J2-2 J2-1 TEMPERATURE SENSOR
AC T1 2 T2 4 T3
N/O
6 22
L1 L1 L2 L3 N
L2
L3
L3
L3
COMPRESSOR
CONDENSOR FAN - 1
CONDENSOR FAN - 2 N
COMPRESSOR * HEATER
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
11
5. Installation
Various risks (crushing, explosion, projection, noise,): The installation operations described in this chapter should be performed only by personnel qualified in the installation of electro-pneumatic systems. Follow the procedure described below with care in order to prevent exposing personnel to danger.
5.1 Storage If your dryer is about to be stored during a long time before installation and use, take care to the following instructions: If possible, let the dryer in its original packing (In particular products fitted with marine packing with plastic film and dessicant) Check that air inlet and outlet are correctly blocked in order to protect the system from foreign materials Check that the machine is correctly protected from atmospheric dust or water. Check that the store is frost protected Make sure to archive correctly the attached documents. 5.2 Installation and site connections
Series-Coldspell
Refrigeration Dryer
TRIDENT
1. Install the dryer in a closed clean, dry room protected from frost. Access to the room should be restricted to personnel not qualified in unit maintenance and operation. The room must be adequately ventilated. The dryer must not be directly exposed to sources of heat. The temperature of the room must not exceed 43oC.
12
2. Make sure that the dryer is not near any equipment which does not comply with the electromagnetic compatibility directives and which may degrade dryer operation. There must be a minimum distance of 1 m between the dryer and any other equipment, which uses electricity. Yellow lines demarcating the area are preferred. 3. Ensure that the dryer is installed in vertical position and kept level. 4. Fix the anchor points if it's necessary. 5. Install a system of by-pass valves between the dryer inlet and outlet so as to be able to service the installation without having to interrupt the compressed air supply from the network. The upstream and downstream valves must be closed during installation. 6. Connect the compressed air for processing to the dryer inlet with rust-free pipes. 7. Connect a drain pipe to the Drain valve part connection (1/2''F) 8. Connect the processed compressed air to the dryer output with rust-free pipes. 9. Check that all the connectors are airtight and that the fixings are tight. 5.3 Electrical Connections Connect the electrical power cable to the supply as specified in this manual, ensure the supply is well grounded.
! !
Risk of electrical shock: When connecting the machine, cut off the power at the connecting point.
Various risks (explosion, projection, noise, ...): Do not pressurise until the installation procedure has been completed.
For water-cooled condenser, ensure that the Water pump is switched on. Switch ON the system with the ON/OFF switch provided in the front panel of the canopy.
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
13
6. Operation
6.1 Operator Only a minimum level of experience in handling compressed air is necessary to operate a Coldspell refrigeration dryer and he should be familiar in the following terminologies : Pressure in Kg/cm2 Flow in cfm Dew points in oC Components of a fluid network: compressor, valves, drains, taps, pressure gauges, filters, tanks,... 6.2 How to stop the dryer
Various risks (projection, explosion, noise,...) : Whenever working on the dryer, it I esessential to disconnect it from the network. Follow the procedure below :
1. Open the by-pass valve 2. Close the upstream valve 3. Close the downstream valve 4. Switch off the Dryer 5. Vent the air inside the dryer
14
7. Maintenance
Various risks (projection, noise, ...) : This operation should be performed by professionals of Refrigeration.
Trident make Refrigeration dryers are robust, reliable machines. To ensure uninterrupted, problem-free operation, regularly perform the inspections below. Type of inspection Discharge pressure in refrigerant line Drain valve Air Cooled condenser surface cleaning Water cooled condenser cleaning using dilute HCL Y Y/R Inlet temperature Dew point temperature
D W - Weekly
D H/R M - monthly
D -
D -
R - As required
* Note : For water cooled condenser Clean the condenser by recirculating dilute HCL if discharge pressure exceeds the value specified in Table 7.1.
Table 7.1
Freon R22 R134a Discharge pressure in psig 300 180
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
15
8. Condenser cleaning
8.1 Air Cooled Stop the dryer Open the side doors, so that all dust removed while cleaning can be vent out of dryer through the side doors Using compressed air and an air gun clean the dust accumulated on the condenser fins from outside the dryer. Ensure that there is no dust inside the dryer and reassemble the doors. 8.2 Water Cooled Stop the dryer Stop the water supply and close the inlet and outlet valves of the water supply Open the door covering the condenser. Drain the water completely. Pass dilute HCL solution in the tube side at pressure for more than 1 hour Reassemble all and start the dryer.
16
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
17
18
Trouble 5 High Discharge pressure R22 Gas : Above 280 PSI incase of water cooled.
Root cause Water cooled model, water supply or cooling tower not proper Water cooled model, scale formation in the condenser tubes Refrigeration line block, after the condenser or Expansion device block Condenser dirty
Clean or blow off condenser dust Close hot gas by pass valve Charge gas to maintain the suction and discharge pressure Replace the compressor Arrest the leak & charge the gas Clean condenser dust Charge gas Purge gas to maintain the suction and discharge pressure Clean the block Close the hot gas by pass valve Clean the after cooler Correct the flow rate
19
6 Compressor thermal overload relay trip or compressor getting off and not getting on
Less return gas in the suction line Less return gas in the suction line Winding open Gas leak in the system Condenser dirty
7 Compressor head is hot and less return gas in the suction line
Expansion device block Hot gas bypass valve opened more Inlet temperature high Inlet flow rate high
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
20
This Document may be modified without notice reproduction, even partial, forbidden without written Authentication
21
WARRANTY
Products of Trident Pneumatics Pvt Ltd are guaranteed to be free from defects in materials and workmanship when installed and operated in accordance with the instructions outlined in the Instruction Manual. Trident Pneumatics Pvt. Ltd.'s obligation under this warranty shall be limited to repair or replacement (at the discretion of Trident) of defective goods returned to Trident's plant within one (1) year from the date of commissioning. Product Model Serial No. : : : :
___________________________
5/232, K.N.G Pudur Road, Somayampalayam, Coimbatore 641 108. Ph : 0422 2400492, 2401373 Fax : 0422 2401376 e-mail : [email protected] Website : www.tridentpneumatics.com
vii) Set pressure viii) Drain valve settings Date of completion : Date of completion :
Commissioning :
5/232, K.N.G. Pudur Road, Somaiyampalayam P.O., Coimbatore - 641 108, India. Ph : +91-422-2400492 Fax : +91-422-2401376 e-mail : [email protected] Website : www.tridentpneumatics.com