Pac8000 Modular Io Gfa1779a
Pac8000 Modular Io Gfa1779a
Intelligent Platforms
Overview
I/O Modules
I/O Modules – Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2/2 Modules
Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Discrete Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Discrete Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Pulse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
2/1 Modules
Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Discrete Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Discrete Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
Pulse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
1
3
4
www.ge-ip.com/process 3
PAC8000 Modular I/O – Overview
Redundancy options
8000 has been designed to increase avail-
ability and minimise downtime. Redundant
LAN channels and power supplies can be
specified as options to increase system avail-
ability. All Controllers can be used in redundant
configurations, as can the 8507-BI-DP BIM for
Profibus DP remote IO. Possible downtime is
further reduced by ensuring that the system
components using active circuitry can be
removed and replaced quickly and easily. Even
the field terminals can be replaced without
interrupting the operation of adjacent I/O
modules. Carriers have no active circuitry and
are unlikely to need replacement.
PAC8000 with general purpose field wiring In nodes populated only with IS I/O modules,
The PAC8000 2/2 IO module range is used a separate system power supply module
for general purpose and Zone 2 / Division provides power for the Bus Interface Module
2 applications (where the node or the field and ‘node services’. Redundancy of this
instrumentation are sited in the hazardous supply is also supported.
area). See Figure 2. PAC8000 supports a full
range of I/O module types covering inputs
and outputs for both analog and discrete
circuits. The node can be mounted on the
plant with a suitable enclosure providing
protection against the environment. Figure 3
shows a node containing all the key compo-
nents: a Bus Interface Module or Controller,
I/O modules on carriers and a pair of carrier-
extenders linked with an extension cable.
Power supplies are not shown, but arrows
indicated the location of the BFP connectors.
www.ge-ip.com/process 5
PAC8000 Modular I/O – Overview
proprietary bus system called ‘Railbus’ and sections that follow. On • A/D error on AI
• BFP failure on 2/2 AI
one BIM can control up to 64 modules. The
Input fail values
module carrier provides the transmission Off Normal
In the event of failure of an input module, the
medium for the Railbus and, by plugging reported value is forced to a predefined state – Flashing Initialization error
a module onto a carrier, connections are low, high or hold last value. This ensures that
made between the module and the bus. The the host adopts a state consistent with safe BFP = Bussed Field Power of 2/2 modules
connectors on the carrier also provide the operation of the plant.
power supply links to the module and, when MODULE ‘POWER’ LED (GREEN)
required, power for the field wiring. Power-up/initialization state
When powering-up a node it is essential On Power OK
Addressing of I/O modules for plant safety that the state of each of
Off Power failure
Modules are addressed by the BIM or the outputs is known. While the node is
Controller in terms of their position, or slot, in initializing, the I/O modules are held in the
the total chain of 64 modules not by individual power-up state (see following pages). After
module types. As a result, a module can be node initialization and before establishing Module ‘Status’ LED (yellow)
removed and replaced by another of its own external communication, the outputs are set The channel “Status” indicators have
type without the need to ‘tell’ the system of to predefined “initialization” states. This “safe- different meanings according to the module
the change. During configuration, the node state” can be defined by the user for each type and are described in the individual
is told the characteristics of each necessary output channel. module sections.
module position whether or not the module is
present at the time. Consequently, if a module Non-volatile configuration memory Important note
is removed for service replacement, the prop- The configuration information for all I/O If, when using the 8502-BI-DP Profibus
erties of the ‘slot’ are still retained. modules in a node is stored in non-volatile BIM, the node is configured over Profibus, a
memory (NVM). When a module is replaced, reduced set of configuration parameters is
IMPORTANT MODES when the node is powered up or following available. In this case, the module specifica-
a reset, the node will download the stored tions should be read in conjunction with the
Output failsafe mode configuration information to the relevant I/O Profibus BIM instruction manual INM8502
Output modules have the ability to assume a modules. Visual indicators LEDs are provided which explains the configuration options.
failsafe state. This can happen for two reasons. on each module to indicate Power, Fault and
channel Status information. These are based Alternatively, if the 8455 Configurator Soft-
1) A module can be forced in to failsafe state on the NAMUR NE44 specification for LED ware is used to configure a Profibus node, a
by issuing a specific command to it. indicators. The Power and Fault indicators are fully detailed range of module configuration
2) Modules have a configurable “timeout” common to all I/O modules and their states parameters is available.
parameter. This defines the maximum time are shown in the following tables.
period of communication inactivity. If this
GSD files are available for either of the
period is exceeded the module adopts a
above options.
failsafe state.
www.ge-ip.com/process 7
PAC8000 Modular I/O – Overview
GENERAL HART® capability always set on the ‘inner’ side of the alarm limit
The 4–20 mA AI modules provide digitized AI modules “with HART” can obtain infor- to be, typically, greater than the system noise
data and status information from 4–20 mA mation from HART instruments of protocol in the plant. If an alarm is activated, it will
current loop sensors. revision 5.0 or later. Each channel can remain until the input moves the full extent of
communicate with a single HART instrument. the deadband towards a “safer” value.
HART universal command 3 is used to gather
up to 4 dynamic variables and status from The Hi-Hi and Lo-Lo alarms support the
each HART instrument. This provides more NAMUR recommendations, i.e. if the alarm
process information to the control system limit is set less than 3.6 mA (Lo-Lo), or greater
from each device. Greater accuracy can than 21.0 mA (Hi-Hi), the alarms must be
also be achieved by eliminating A/D and D/A active for 4 seconds before the alarm is set.
errors. In addition, HART pass-through may The Deadband does not apply to NAMUR
be used for device configuration, calibration alarms. If the alarm limits are set at values
and advanced diagnostics. between the NAMUR limits, the alarms func-
tion normally.
IMPORTANT MODES
Dead zone
Output failsafe mode Each channel has a definable “dead zone”.
The AI modules have eight user-channels that This is to reduce the need for the module to
are sampled every 27 ms (2/2) or 33 ms (2/1). report every minor change in input value. If
the input value differs by the amount defined
Data format by the Dead Zone, or more, then the new
The input signal is stored as a 16-bit value is reported, otherwise it is not. This
unsigned value. In this range 0 is equivalent reduces traffic on the internal bus which
to 0mA and 65,535 is equivalent to 25mA. improves the system response time. If the
Any digital HART data is stored in its original Dead Zone value is set to zero (the default),
IEEE754 floating point format. then every input value read cycle will set a
‘New Data’ flag, and be reported.
Filtering
The Analog Input modules use a first- MODULE OPERATING STATES
order software filter that provides 12 dB
attenuation at the Nyquist frequency of the Normal/Failsafe mode
algorithm. The filter supports a set of options The AI modules support failsafe mode as
that can be matched with control algorithm defined in the earlier I/O module introduc-
execution rates. tory section. When not in failsafe the module
adopts Normal mode.
Input alarms
Four configurable alarm levels are provided Channel Active/Inactive
for each channel—two high and two low (see A channel can be made active or inactive
figure below). When an input value exceeds individually. When a channel is made inactive
an alarm limit a flag is set and the BIM gets inputs will not be processed.
a new alarm status.
Alarm deadband
The Alarm Deadband prevents the alarm from
tripping on and off because of system noise.
It can be configured for each channel and is
Passthrough
Passthrough messages to HART instruments
Lo Lo Alarm limit
are always allowed. Lo Lo Alarm set
Lo Lo NAMUR Alarm set (4s delay) Lo Lo NAMUR Alarm cleared
On Sensor loop OK
www.ge-ip.com/process 9
PAC8000 Modular I/O – Overview
Alarm deadband
The alarm deadband (not shown on the
diagram) is fixed at 1%.
Power-up conditions
The module uses the following values when it Input
powers up. Value
Alarms
All alarms are made inactive by having their
values set to high or low extremes, as appro-
priate.
Dead zone
0 (i.e. all changes of A/D data are reported for Monitored
an active channel) Channel Value
Software filtering
Disabled
Lo Alarm limit
Channel type Lo Alarm set Lo Alarm cleared
Type K thermocouple or 3-wire RTD - Pt100
Visual indicators
On Sensor loop OK
www.ge-ip.com/process 11
PAC8000 Modular I/O – Overview
Channel Active/Inactive
Each channel can be made active or inactive
individually. When a channel is made inactive
the output is disabled, i.e. deenergized.
www.ge-ip.com/process 13
PAC8000 Modular I/O – Overview
NOTES:
1. This action is only available in Static mode.
2. AC modules will react differently to the on-time length and trigger time. The module can only be triggered ON during a zero crossing of the AC waveform; similarly, the module can only
switch OFF at a zero crossing point. The minimum on-time is therefore restricted to half the total period of a regular waveform.
3. Continuous pulse operation is supported only by Version 2 models of BIMs 8502 and 8505.
4. On 2/2 modules, this action is only available in Static mode.
www.ge-ip.com/process 15
PAC8000 Modular I/O – Overview
GENERAL Pulse inputs control gate input and both channel counters
These modules are designed to meet Pulse inputs can come from a range of can be started, stopped and reset by BIM
the requirements of a very wide range of sensors having different amplitudes, trigger commands. Counters can be configured to
mechanical positioning and flow applications. levels and input impedance requirements. count up (the default) or down. If the quadra-
ture calculation is enabled (see below) then
When used separately, the two input channels
Inputs types accepted are: the configured counter direction is ignored;
will accept pulse inputs to measure:
instead counter direction is determined by
• Proximity detectors (NAMUR/DIN19234)
• Frequency the quadrature value (up for forward, down
• Current inputs
• Acceleration / rate for reverse).
• Voltage inputs
• Number of pulses (i.e. counter) • Switch / electro-mechanical inputs
A counter preset value can be configured
by a BIM command which also resets the
When combined, they provide: Threshold levels for the current and voltage
counter. On reaching the preset count value
input can be set to suit the application.
• Rotational position and direction data from an event is triggered which can also be
quadrature encoding devices. In addition, passed to the channel’s digital output. This
Dynamic data
the module has two digital outputs and one state is cleared by resetting the counter or
Several values are calculated, for each
digital input to gate (start/stop) the channel assigning a new preset value.
channel, from the signal pulses received.
1 internal counter.
Quadrature (rotation direction)
Frequency
This is calculated by measuring the time
interval between pulses. An average is calcu- Rotor in
Ch 1
lated over a period (20 ms to 200 s) defined by Fig 1a) 0˚ position
the user. The time interval is measured from
the edge of one pulse to the same edge of the Ch 2
next pulse. The polarity (rising or falling edge)
can be configured.
Ch 1
as “out-of-range”.
Ch 2
Acceleration
This is calculated from the difference in Ch 1
frequency from the start to the end of the Rotation
sample period. A positive value indicates an Ch 2
increase in the rate of frequency and a nega-
0˚ 360˚
tive value is a decrease in the rate.
Counting
Each channel has a 32-bit counter that
The second channel can be used to determine
indicates the total number of input pulses
direction of rotation by comparing the phase
since the counter was reset. The counter on
of its input pulse with that of the first channel.
Channel 1 can be started and stopped by the
If the Ch 2 input is in a low state on the rising Alarm deadband Control data
edge of the Ch 1 pulse then the rotation is A deadband can be specified for the high, low The host can write data to control each
forward (Fig 1a). If the Ch 2 input is high on the and acceleration alarms. This provides hyster- channel counter. The available parameters
rising edge of the Ch 1 pulse then the rotation esis to avoid repetitive alarms in noisy signal are: start, stop, set, reset and preset value.
is backward (Fig 1b). environments.
Digital outputs
Filtering Missing pulse alarm Both digital output channels can reflect the
The module has a hardware filter which can Both channels can be configured to detect a status of the inputs by indicating:
be used to minimise the effects of contact “missing pulse”. If no input pulse is detected • Frequency or acceleration alarm
bounce. The available settings are 1, 5, 20 kHz for a defined time period an alarm is signalled • Counter preset value reached while the
and Off. in the same way as the high/low alarms. The main channel can also output:
alarm is cleared on receipt of a pulse or on • Quadrature forward or reverse signal
Alarms reconfiguration of the alarm. The time period • Scaled retransmission (a “divided by N”
High / Low alarms is restarted after each sample period in which version of the input)
High and low alarms can be configured for at least one pulse occurs.
each channel. When the input value goes
beyond an alarm limit, channel and module Line Fault Detect
flags are set, the channel LED flashes and, if Each channel can be configured to sense an
configured, the channel’s digital output state open or a short circuit condition on inputs. On
will change. detection, the actions are those for the high/
low alarms. On fault, the node can: report the
Acceleration alarms frequency value as being at the top or the
An acceleration alarm limit can also be set. bottom of the range, freeze the counter, set
If the limit is exceeded the actions taken are the acceleration to zero; depending on how
identical to those for the high/low alarms. the BIM or Controller is configured.
www.ge-ip.com/process 17
PAC8000 Modular I/O – Overview
Sequence of Events
32-Channel Sequence Of Events, non-isolated, module powered 8127-DI-SE
www.ge-ip.com/process 19
2/2 I/O Modules
RESPONSE TIME
INPUTS Other
MUX
Number of channels
A/D
• 27 ms (max.) Channel 1 of 8
• 8, single-ended
µP
www.ge-ip.com/process 21
2/2 I/O Modules
• 1–5 V inputs
Channels
(each channel)
• Open circuit and short circuit detection Channel 1 of 8
POWER SUPPLIES
24 Vdc
CONFIGURABLE PARAMETERS
Alarms
• High, high-high, low and low-low
Alarm deadband (hysteresis)
• User defined value
Input filter time constant
• User defined value
Input dead zone
• User defined value
Drive on failsafe
• Disabled / upscale / downscale
Channel status
• Active / Inactive
Isolation
MODULE SPECIFICATION Channel 1 of 4
• Any channel to Railbus – 250 V ac rms P
See also System Specification
Open circuit bleed current mV
Railbus
• ± 0.5 μA (nom.) CJ
INPUTS
Number of channels CONFIGURABLE PARAMETERS
•4
Sensor type
THCs types • User selectable FIELD TERMINALS
• B,E,J,K,N,R,S, or T to EN 60584-2, IEC584-2,
Input dead zone (hysteresis)
BS4937; W3 and W5 Recommended Compatible
• User defined value Field Wiring
Field Terminal Field Terminal
Input Type Range Overall accuracy Selectable input filtering
• Off / 2 reading average / running average 8605-FT-TC
±0.1% of span (+10 to +40°C) General purpose —
mV 0 to +120mV Drive on open circuit fault THC
±0.2% of span (–40 to +70°C)
• Disabled / upscale / downscale
< 600°C 1.5°C + BTA Class 1, Div 2
THC: B 0 to +1820°C
≥ 600°C 0.45°C + BTA
Alarms or Zone 2
8605-FT-TC
—
• High and low THC
hazardous area
E –270 to +1000°C 0.3°C + BTA Channel status
• Active / Inactive
J –210 to +1200°C 0.3°C + BTA
www.ge-ip.com/process 23
2/2 I/O Modules
Input deadzone
accommodated MUX A/D
8132-AI-UN
Input sensors
• 8 isolated, universal, input channels
2-wire RTD, 3-wire RTD, 2-wire 4-wire Channel 1 of 8
• Configurable on a channel by channel Current resistance resistance Tx Tx THC V, mV
www.ge-ip.com/process 25
2/2 I/O Modules
8607-FT-TC
8608-FT-NI
General purpose (See Note)
(No internal CJ)
(Internal CJ)
8608-FT-NI
8607-FT-TC
THC (See Note)
(Internal CJ)
(No internal CJ)
Note: For further advice on field terminals for this module and for
operation with more than one type of sensor, see Technical Support
Note: TSN113 - Getting the most from 8607 and 8608 field terminals.
0 to 25 mA 0 to 25 mA
± °C error for Tamb = 10°C to 40°C ± °C error for Tamb = -40°C to 70°C
Type Range Bottom of range 0°C Middle of range Top of range Bottom of range 0°C Middle of range Top of range
Pt100 -200°C to +850°C 0.5 0.9 1.2 2.1 0.6 1.4 2.2 4.3
jPt100 -200°C to +650°C 0.5 0.9 1.2 1.7 0.6 1.4 2.2 3.5
Pt200 -200°C to +850°C 0.5 0.8 1.2 2.0 0.6 1.2 2.2 4.2
Pt500 -200°C to +850°C 0.5 0.8 1.4 2.4 0.6 1.3 2.5 4.8
Ni120 -60°C to +250°C 0.8 0.6 0.6 0.6 1.1 0.8 1.0 1.0
Cu10 -30°C to +220°C 3.7 3.9 3.9 4.1 3.8 4.6 4.3 4.5
Ohms Ranges
±°C error for Tamb = 10°C to 40°C ±°C error for Tamb = -40°C to 70°C (for reference)
Full scale
Type Normal operating range Bottom of range Middle of range Top of range Bottom of range Middle of range Top of range
range
B 500 to 1810 6.1 2.9 2.8 10.2 5.0 5.0 0 to +1820
E -200 to 1000 1.3 0.5 0.6 2.3 0.9 1.4 -270 to 1000
J -190 to +1200 1.1 0.6 0.8 2.1 1.2 1.8 -210 to +1200
K -200 to +1372 2.0 0.8 1.3 3.4 1.5 2.6 -270 to +1372
N -190 to +1300 2.7 0.9 1.2 4.4 1.7 2.3 -270 to +1300
T -200 to +400 2.0 0.7 0.6 3.4 1.2 1.1 -270 to +400
Russian K -200 to +1300 2.0 0.8 1.3 3.4 1.2 2.6 -200 to +1300
Russian L -200 to +800 1.0 0.5 1.0 2.1 0.8 2.1 -200 to +800
www.ge-ip.com/process 27
2/2 I/O Modules
SAFETY
Channels
Channel 1 of 8
• HART variable and status reporting FM non-incendive field wiring parameters
(each channel) µP
• Valve positioners and remote • Voc = 28.7 V; Isc = 33 mA; Ca = 0.17 μF; La = 11.0 mH
P
I
4-20mA
Railbus
indicators, etc.
POWER SUPPLIES 24 Vdc
MECHANICAL
OUTPUTS 8602-FT-ST 8604-FT-FU
General purpose
Module Key Code Standard Fused
Number of channels
• A4
• 8, single-ended
Class 1, Div 2 8603-FT-FU
Module width or Zone 2
8601-FT-NI
Non-incendive
Nominal signal range (span) Non-incendive
• 42 mm hazardous area Fused
• 4 to 20 mA
Weight
Full signal range
• 200 g
• 1 to 23 mA
Open loop detection threshold
• 0.7 ± 0.25 mA
Output compliance
• 20 mA at 21.6V DC supply (into 700 Ω load)
Accuracy (over temp range)
• ± 0.25% of span
Output ripple
• < 0.02% of span
Resolution
• 12 bits
Isolation
• Any channel to Railbus – 100 V ac
CONFIGURABLE PARAMETERS
Initialisation state
• Predefined value
Drive on fail-safe
• Predefined value/last value
Channel status
• Active / Inactive
HART variable and status reporting
• Enable / Disable
• 4–20 mA Other
Channels
Channel 1 of 8
indicators, etc Railbus (12V) current
P
• 100 mA (typ.)
• Open circuit detection is provided on • 150 mA (max.)
P
4-20mA
Railbus
I
each channel Bussed Field Power
24 Vdc
• 24 V dc bussed field power required • 300 mA (max.) at 24 Vdc ± 10% Bussed Field Power
Quiescent current
• 60 mA
MODULE SPECIFICATION FIELD TERMINALS
See also System Specification
MECHANICAL
Recommended Compatible
Field Wiring
Module Key Code Field Terminal Field Terminal
INPUTS
• A4
Number of channels Module width General purpose
8602-FT-ST 8604-FT-FU
• 8, single-ended Standard Fused
• 42 mm
Nominal signal range (span) Weight Class 1, Div 2 8603-FT-FU
• 4 to 20 mA • 200 g or Zone 2
8601-FT-NI
Non-incendive
Non-incendive
Full signal range hazardous area Fused
• 1 to 23 mA
Open loop detection threshold
• 0.7 ± 0.25 mA
Output compliance
• 20 mA at 21.6 V dc supply (into 700 Ω load)
Accuracy (over temp range)
• ± 0.25% of span
Resolution
• 12 bits
Isolation
• Any channel to Railbus – 100 V ac
• Between channels – None
CONFIGURABLE PARAMETERS
Initialization state
• Predefined value
Drive on fail-safe
• Predefined value / last value
Channel status
• Active / Inactive
RESPONSE TIME
Response Time
• From Railbus command to output change –
25 ms (max.)
www.ge-ip.com/process 29
2/2 I/O Modules
8109-DI-DC SAFETY
SAFE AREA OR ZONE 2/
FM non-incendive field wiring parameters DIV2 HAZARDOUS AREA
(each channel)
• 8 discrete isolated inputs • Vmax = 30 V; Imax = 100 mA; Ci = 0 μF; Li = 0 mH
• 24 V dc field voltage sources
• User definable input threshold POWER SUPPLIES
Railbus (12V) current
• Pulse counting option
P
Channel 1 of 8
• 35 mA (typ.)
• 55 mA (max.) 24V Railbus
DC
MODULE SPECIFICATION Bussed Field Power
See also System Specification • Not required
INPUTS MECHANICAL
Module Key Code FIELD TERMINALS
Number of channels
• 8 • B2
Recommended Compatible
Module width Field Wiring
OFF voltage Field Terminal Field Terminal
• < 3.2 V dc • 42 mm
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / Latch on low
Pulse counting
• Enable / Disable
RESPONSE TIME
I/O response time
• Field event to new data available on Railbus –
3 ms (max.)
POWER SUPPLIES
MODULE SPECIFICATION
See also System Specification Railbus (12V) current
• 90 mA (typ.)
• 135 mA (max.) FIELD TERMINALS
INPUTS
Bussed Field Power
Number of channels • Required Recommended Compatible
Field Wiring
Field Terminal Field Terminal
• 16
OFF voltage MECHANICAL
8617-FT-NI†
• < 3.4 V dc General purpose —
Module Key Code 16 Channel DI
ON voltage • E2
• > 11 V dc Class 1, Div 2
Module width 8617-FT-NI †
or Zone 2 —
Wetting current • 42 mm hazardous area
16 Channel DI
• 2.8 mA (nom.) @ 24 V dc
Weight
Minimum pulse width detected • 210 g † External fusing of the Field Power supply is recommended in order
to protect the field wiring.
• 5 ms
Max input freq in pulse counting mode (no-debounce)
• 100 Hz
Maximum voltage
• Input – 30 V dc
• Reverse input – -25 V dc
Isolation
• Any Channel to railbus – 250 V ac
• Channel to channel – 150 V peak
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined (User defined permits
0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / Disable
www.ge-ip.com/process 31
2/2 I/O Modules
8110-DI-DC SAFETY
SAFE AREA OR ZONE 2/
FM non-incendive field wiring parameters DIV2 HAZARDOUS AREA
(each channel)
• 8 discrete inputs • Voc = 30 V; Isc = 15.2 mA; Ca = 0.12 μF; La = 151 mH
• For dry contact switches
• 24 V dc provided on input high side POWER SUPPLIES
P
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / Disable
RESPONSE TIME
I/O response time
• Field event to new data available on Railbus –
3 ms (max.)
8121-DI-DC SAFETY
SAFE AREA OR ZONE 2/
FM non-incendive field wiring parameters DIV2 HAZARDOUS AREA
(each channel)
• 16 input channels • Voc = 30 V; Isc = 3.5 mA; Ca = 0.12 μF; La = 1000 mH
• For dry contact switches
• 24 V dc provided on input high side POWER SUPPLIES
µP
Railbus (12V) current
• Returns commoned internally Channel 1 of 16
• 90 mA (typ.)
• Pulse counting option • 135 mA (max.) Railbus
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / Disable
RESPONSE TIME
I/O response time
• Field event to new data available on Railbus –
5 ms (max.)
www.ge-ip.com/process 33
2/2 I/O Modules
Pulse width
• 1ms to 60s
MODULE SPECIFICATION SAFE AREA OR ZONE 2/
Line fault detection* DIV2 HAZARDOUS AREA
See also System Specification
• Open line & short circuit detect /disable
Other
Number of channels Channels
• 8 (independently configured as inputs or outputs) RESISTANCE MEASUREMENT ACCURACY Channel configured
MUX
as output A/D
(For normally de-energised output open and short-circuit detection)
INPUTS With forward biased test current
µP
Channel 1 of 8 Latch
ON/OFF threshold current • ±(3.4%+5.3Ω) for line resistance ≤ 220Ω
• 0.9mA (typ.) • Greater of: ±7% or ±(3.1%+27Ω) for line resistance
>220Ω, <1kΩ Railbus
O/C Voltage
• 24V dc (typ.) - depends on BFP Supply With reverse biased test current
• Greater of: ±7% or ±(3.1%+430Ω) 24V dc
Wetting current Bussed Field Power
• 1.2mA (typ.)
RESPONSE TIME
Minimum pulse width detected
• 5ms I/P Signal change to availability on Railbus FIELD TERMINALS
• 5ms (max.)
Max input frequency in pulse counting mode
(no debounce) Railbus command to O/P change Recommended Compatible
Field Wiring
Field Terminal Field Terminal
• 30Hz • 1ms (max.)
Isolation (any channel to Railbus) 8604-FT-FU
POWER SUPPLIES 8610-FT-NA
• 250V ac General purpose Standard
Non-arcing
Fused
Railbus (12V) current
OUTPUTS • 50mA (typ.), 70mA (max.) 8611-FT-FU
Non-arching
Maximum Output Current per Channel Bussed Field Power Fused
• 2A • All channels configured as inputs – 50mA (max)
• Any channels configured as output – 50mA + o/p
Maximum Output Current per Module
load currents
• Continuous – 6A
• Non-continuous (<10 seconds) – 8A
MECHANICAL
INPUT CONFIGURABLE PARAMETERS • Module key code – B6
• Module width – 42mm
Filter time interval • Weight – 210g
• 0 to 8s (in 1ms steps)
Earth Leakage Detection Channel
• ON / OFF
* Normally de-energised channels only
General The counter “wraps around” from 65 535 to For normally de-energized outputs, if a single
The 8129-IO-DC Discrete Input/ Output zero without indication. switch fails short circuit, the other switch can
Module provides the interface to 8 channels, energise the load. If either fails open circuit,
which may be configured in any combination Transitions are counted even if the channel is the load cannot be energized.
of discrete inputs and outputs. configured to “latching”.
Switches are tested by pulsing them ON or
Combined inputs and outputs Earth leakage detection OFF for a maximum of 5 ms – the load must
Each of the 8 channels of the 8129-IO-DC Where earth leakage fault detection is not respond to this length of pulse. This test
Discrete Input/Output Module may be config- required, a single channel of an 8129-IO-DC can be disabled if required.
ured, on a channel-by-channel basis, as module must be configured to monitor earth
either an input or an output. leakage and wired to the appropriate termi- Short circuit protection
nals of an 8751-CA-NS Controller Carrier. Channels that are configured as outputs and
When configured as an input, the channel which are short-circuited are protected by
is suitable for use with dry contacts – with Input latching over-temperature thermal detection. If an
power supplied from the Module. Inputs can be configured to “latch” a partic- output channel is short-circuited it will briefly
ular (filtered) input transition and maintain conduct an over specification current, but
When configured as an output, the channel is the output in the latched state until the latch this will be identified by the thermal detection
capable of switching up to 2.0A (maximum of is cleared. “Normal Polarity” will latch a tran- and the relevant channel made inactive.
6.0A continuous per module). Output channels sition from 0 to 1 as 1, “Inverse Polarity” will
are used with solenoids, valves and alarms. latch a transition 1 to 0 as 0. The operation is Pulsed output
described in figure 1. Output channels can be configured to give
Diagnostics a pulsed output – of either single static,
Comprehensive diagnostic tests are Normally energized and normally single dynamic, continuous or continuous
performed on the module and each of its de-energized outputs dynamic form.
channels, including tests for stuck ON and Individual output channels can be either
stuck OFF output switches. normally energized or de-energized. Each The single static pulse is ON for a predeter-
output channel comprises 2 switches that mined time. It then remains OFF until a new
Live maintenance operate in series with the load – one on the pulse instruction is received.
The field wiring connections to the 8129-IO-DC supply line, the other on the return
Discrete I/O Module are classified as non- The single dynamic pulse is ON for a period
sparking and can only be worked on in a For normally energized outputs, if a single that may be changed by the application, then
Class 1, Division 2 or Zone 2 hazardous area switch fails short circuit, the other switch can remains OFF until a new instruction to write
once the Bussed Field Power connection has still de-energise the load. If either fails open is received.
been isolated. circuit, the load will be immediately de-ener-
gized by the fault.
Note: the Bussed Field Power connection
must also be isolated before removing or
replacing the module. Time
Input configuration 1
Input channels are used to interface to volt
Filtered Input State
free contacts. Line fault detection can be
turned OFF or can detect open circuits or 0
both open and short.
Input filtering 1
A change in the input state is recorded only Recorded State
if the states observed at the start and end of (normal polarity)
the filter time interval are the same. If they 0
are different the previous state is maintained.
(This reduces the chance of noise being incor-
rectly interpreted as a change of input value).
1
The filter time interval can be configured
Recorded State
between 0 and 8s, in 1ms intervals. (inverse polarity)
0
Input transition counting
A counter can record the number of filtered
transitions of a particular type. Depending Latch Enable Reset Latch Reset Latch
on the polarity setting, the counter will either
count transitions from 0 to 1, or from 1 to 0.
Figure 1 Recording of input states
www.ge-ip.com/process 35
2/2 I/O Modules
In continuous pulse mode a series of pulses Short circuit line fault detection can be
of defined ON period are sent, with a defined enabled with forward or reverse biased test
OFF period between. Series currents. With forward biased test currents,
3.3kΩ End of line
10kΩ
the threshold at which a short circuit fault
Continuous dynamic pulse mode allows the is reported is configurable up to 1kΩ. With
application to continually vary the ON and reverse biased test currents, the threshold is
OFF times of the pulse train. fixed at 1.95kΩ.
Figure 3 LFD resistor values
For all types of Pulsed Output, the ON time Module operating states
of the pulse may be between 0 and 60s in The nominal resistance thresholds employed Input “Failsafe” mode
1ms intervals. are shown in the table below. The module supports failsafe mode as defined
in the earlier I/O module introductory section.
For the continuous pulse mode, the OFF Resistance Value
period can be set between 0 and 60s, in Open circuit > 30kΩ Output “Failsafe” mode
1ms intervals. Open circuit > 6.5kΩ The module supports failsafe mode as
Closed circuit < 6.5kΩ defined in the earlier I/O module introductory
Pre-configured output patterns Short circuit < 1.95kΩ section, with the following two additions:
A number of different, pre-defined output 1) Channel using “Configured failsafe values”
patterns are available, which can be used to Output channel line fault detection In this mode, the module will force the
indicate the occurrence of different events, Line fault detection (LFD) for open and/or outputs to predefined levels— defined on a
using the same alarm hardware. The patterns short circuit line faults can optionally be per channel basis.
comply with the requirements of NFPA 72 enabled for normally de-energized outputs.
and are shown in Figure 2. (Normally energized loads would be de-ener- On entering “failsafe”:
gized by either open or short circuit line
Input channel line fault detection faults, of these only short circuit faults will be a) If channel is in Static mode of operation:
Line fault detection (LFD) for open and short detected and reported by the IO Module). Pulse mode is disabled and the channel
circuit line faults will normally be enabled for is configured as a latched output and is
safety related input channels. Series resistors An open circuit fault will be reported for line driven to its failsafe value.
are required for short circuit detection and resistances above 30kΩ. b) If channel is in Dynamic mode of operation:
end of line resistors for open circuit detection, If in single pulse (momentary) mode, the
as shown in figure 3. configuration is not cleared, but the output
is driven to its failsafe value.
On leaving failsafe:
(a) Fire Alarm Channel will adopt the mode defined
below for a channel going from inactive
to active state
0.5 0.5
sec sec
1.5
sec 2) Channel using “Hold last value”
If the module goes into failsafe during a
(b) Supervisory single pulse, it is allowed to complete the
pulse before adopting the failsafe state. A
latched (discrete) output will remain at its
current value.
0.5 0.5 2.0
sec sec sec
Visual indicators
(c) Trouble For the operation of the Power and Fault
LED’s see IO Module Overview.
• 42 mm Channel 1 of 8
Weight 115V
L
Railbus
INPUTS
FIELD TERMINALS
Number of channels
• 8 Recommended Compatible
Field Wiring
OFF voltage Field Terminal Field Terminal
• < 34 V ac
ON voltage 8602-FT-ST 8604-FT-FU
General purpose
Standard† Fused
• > 84 V ac
Wetting current Class 1, Div 2 8611-FT-FU
8601-FT-NA
• 2 mA (nom.) @ 115 V ac or Zone 2 Non-arching
Non-arching†
hazardous area Fused
Maximum input voltage
• 130 V ac
† External fusing of the Field Power supply is recommended in order
Frequency to protect the field wiring.
• 50 / 60 Hz
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / Disable
RESPONSE TIME
I/O response time
• Field event to new data available on Railbus –
33 ms (max.)
POWER SUPPLIES
Railbus (12V) current
• 40 mA (typ.)
• 60 mA (max.)
www.ge-ip.com/process 37
2/2 I/O Modules
8112-DI-AC Frequency
• 50 / 60 Hz SAFE AREA OR ZONE 2/
DIV2 HAZARDOUS AREA
• 8 discrete inputs MECHANICAL
• For dry contact switches. Module Key Code
• E1
• 115 V ac provided on input high side P
MODULE SPECIFICATION
See also System Specification
FIELD TERMINALS
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / Disable
RESPONSE TIME
I/O response time
• Field event to new data available on Railbus –
33 ms (max.)
POWER SUPPLIES
Railbus (12V) current
• 40 mA (typ.)
• 60 mA (max.)
Bussed Field Power
• 115 V ac ±10%
• 42 mm Channel 1 of 8
Weight 230V
L
Railbus
AC
MODULE SPECIFICATION • 170 g N
INPUTS
FIELD TERMINALS
Number of channels
• 8 Recommended Compatible
Field Wiring
OFF voltage Field Terminal Field Terminal
• < 68 V ac
ON voltage 8602-FT-ST 8604-FT-FU
General purpose
Standard† Fused
• > 168 V ac
Wetting current Class 1, Div 2 8611-FT-FU
8610-FT-NI
• 1 mA (nom.) @ 230 V ac or Zone 2 Non-arching
Non-arching†
hazardous area Fused
Maximum input voltage
• 265 V ac
† External fusing of the Field Power supply is recommended in order
Frequency to protect the field wiring.
• 50 / 60 Hz
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / Disable
RESPONSE TIME
I/O response time
• Field event to new data available on Railbus –
33 ms (max.)
POWER SUPPLIES
Railbus (12V) current
• 40 mA (typ.)
• 60 mA (max.)
www.ge-ip.com/process 39
2/2 I/O Modules
8114-DI-AC Frequency
• 50 / 60 Hz SAFE AREA OR ZONE 2/
DIV2 HAZARDOUS AREA
• 8 discrete inputs MECHANICAL
• For dry contact switches. Module Key Code
• E2
• 230 V ac provided on input high side P
MODULE SPECIFICATION
See also System Specification
FIELD TERMINALS
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 2ms steps)
Latch inputs
• Enable / Disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / Disable
RESPONSE TIME
I/O response time
• Field event to new data available on Railbus –
33 ms (max.)
POWER SUPPLIES
Railbus (12V) current
• 40 mA (typ.)
• 60 mA (max.)
Bussed Field Power
• 207 to 265 V ac
• Not required N
MODULE SPECIFICATION
See also System Specification MECHANICAL
Module Key Code
INPUTS • E3, non-arcing FIELD TERMINALS
CONFIGURABLE PARAMETERS
Latch inputs
• Enable / disable
Latch polarity
• Latch on high / latch on low
Pulse counting
• Enable / disable
ELECTRICAL ISOLATION
Channel to railbus
• 275V ac (max)
Between blocks (1-4, 5-8, 9-12, 13-16)
• 275V ac (max)
Channel to Channel and Ch+ to Ch- within one block
Ch. 1-4, 5-8, 9-12, 13-16
• 130V ac (max)
www.ge-ip.com/process 41
2/2 I/O Modules
Channel 1 of 8
• Discrete or pulsed outputs MECHANICAL +
–
Railbus
• 42 mm
MODULE SPECIFICATION
Weight
See also System Specification
• 200 g FIELD TERMINALS
• Continuous* – 1 A
• For < 100 ms – 4 A
• For < 20 ms – 6 A
CONFIGURABLE PARAMETERS
Output initialisation state
• Predefined value
Fail-safe
• Predefined value / last value
Output
• Discrete, momentary or continuous pulse‡
Pulse width
• 2 ms to 130 s
RESPONSE TIME
Response time
• From Railbus command to output change –
1 ms (max.)
††
The total instantaneous switched current should not exceed the
following:
10 A for < 100 ms
18 A for < 20 ms
* Limited to 6 A per module
‡ Consult GE for availability
www.ge-ip.com/process 43
2/2 I/O Modules
Channel 1 of 8
Railbus (12V) current
• Discrete or pulsed outputs
• 75 mA (typ.) L
MECHANICAL
MODULE SPECIFICATION Module Key Code FIELD TERMINALS
See also System Specification • F1
Recommended Compatible
Module width Field Wiring
Field Terminal Field Terminal
OUTPUTS • 42 mm
Number of channels Weight 8604-FT-FU 8602-FS-ST
General purpose
• 8 • 220 g Fused Standard†
CONFIGURABLE PARAMETERS
Output initialisation state
• Predefined value
Fail-safe
• Predefined value / last value
Output
• Discrete, momentary or continuous pulse‡
Pulse width
• 2 ms to 130 s † Stated figures are for operation with unfused field terminal. When
operating with 2 A fused field terminal part no. 8604-FT-FU,
maximum switched current is 5 A inrush for <10 ms pulse width at
0.1% duty cycle and <108 operations
* Limited to 3 A per module.
‡ Consult GE for availability
Load
Module width
• 42 mm
MODULE SPECIFICATION
See also System Specification Weight
• 200 g FIELD TERMINALS
CONFIGURABLE PARAMETERS
Output initialisation state
• Predefined value
Fail-safe
• Predefined value / last value
Output
• Discrete, momentary or continuous pulse‡
Pulse width
• 2 ms to 130 s
RESPONSE TIME
Response time
• From Railbus command to output change –
3 ms (max.)
www.ge-ip.com/process 45
2/2 I/O Modules
• 75 mA (typ.)
• Discrete or pulsed outputs • 125 mA (max.) 20 to
L
265V Railbus
• 1A per channel switched Bussed Field Power
AC
N
Load
• Not required
CONFIGURABLE PARAMETERS
Output initialisation state
• Predefined value
Fail-safe
• Predefined value / last value
Output
• Discrete, momentary or continuous pulse‡
Pulse width
• 2 ms to 130 s
CONFIGURABLE PARAMETERS
Channel Status*
• Active / Inactive
Output initialization state
• Predefined value
Fail-safe
• Predefined value / last value
Output
• Discrete, momentary or continuous pulse
Pulse width
• 500ms to 60s
www.ge-ip.com/process 47
2/2 I/O Modules
pulse detection 4 10
MODULE SPECIFICATION
See also System Specification
Terminal Description
DYNAMIC DATA (READ ONLY) POWER - Green LED
1 Current input OFF ON FLASHING
PROCESS VALUES
2 Voltage input
Frequency Power failure Power OK Not Applicable
3 NAMUR input Channel #1
• 16 bit unsigned
4 Common
Count FAULT - Red LED
5 Power supply +ve
• 32 bit signed OFF ON FLASHING
6 Power supply + ve
Acceleration In running state Fault
Awaiting module
7 Current input training
• 16 bit signed
8 Voltage input Channel #2
STATUS VALUES 9 NAMUR input PULSE INPUT CHANNEL - Yellow LED
Frequency/acceleration alarms 10 Common OFF ON FLASHING
• High / Low Channel active and Channel active but in
11 NAMUR gate/control input Channel inactive
• Missing pulse detect operating normally alarm condition
12 Common
Line fault detect Channel #1
13 Output +ve DIGITAL OUTPUT CHANNEL - Yellow LED
• Open / Short circuit
14 Output -ve OFF ON FLASHING
Quadrature direction 15 Output +ve Channel active and
• 1 =clockwise, 2 =anti-clockwise Channel #2 Channel inactive
operating normally
Not applicable
16 Output -ve
www.ge-ip.com/process 49
2/2 I/O Modules
• 250 V ac 9kΩ
Channel
1 of 32
• 8 kHz Railbus
www.ge-ip.com/process 51
2/2 I/O Modules
126-channel Addressable
Smoke and Heat Detector Module
24V dc, non-isolated, module-powered
– XP95 detectors
y 7 8 z 9 10
– Discovery detectors (normal mode)
– Intrinsic safe Apollo instruments (via
protocol converter and isolator) INPUT MECHANICAL
– Zone & Switch monitors & IO Number of channels Module Keyode
– Mini Switch Interfaces • 126 • C2
Isolation (channel to Railbus) Module Width
– Sounders & beacons • 250V ac • 42mm
• Detector alarm state notification Weight
RESPONSE TIME • 185g
• Detector fault notification
Poll time (per device - not in alarm state)
• Channel fault detection • 45ms, typical
FIELD TERMINALS
• 24V dc bussed field power required Poll time (per device - in alarm state)
• 135ms, typical Field Wiring
Recommended Compatible
Field Terminal Field Terminal
MODULE SPECIFICATION Total poll time (126 devices - no alarms)
See also System Specification • 5.7s, typical 8611-FT-FU
8610-FT-NA
Minimum Poll time General purpose Non-arcing
Non-arcing
Fused
• 600ms
Class 1, Div 2 8611-FT-FU
8610-FT-NA
POWER SUPPLIES or Zone 2 Non-arcing
Non-arcing
hazardous area Fused
Railbus (12V) current
• <100 mA
Bussed field power
• 1500mA (max) at 24V dc (max)
Supply to field
• 900mA (450mA from each loop end)1
1
Consideration must be given to operation in case of a loop breakage.
www.ge-ip.com/process 53
2/1 I/O Modules
• HART variable and status reporting Analog signal change to availability on Railbus Railbus
CONFIGURABLE PARAMETERS
Alarms
• High, high-high, low, low-low
Alarm deadband (hysteresis)
• User defined value
Input filter time constant
• User defined value
Input dead zone
• User defined value
www.ge-ip.com/process 55
2/1 I/O Modules
CONFIGURABLE PARAMETERS
MODULE SPECIFICATION Sensor type
See also System Specification • User selectable FIELD TERMINALS
Alarms
INPUTS • High and low Field Wiring Type Recommended Field Terminal
Number of channels Input dead zone
• 8 • User defined value Intrinsically safe
8626-FT-IS
RTD inputs Selectable input filtering standard
• (2-, 3- or 4-wire) • Off / 2 reading average / running average
• Pt100, Pt500 to BS EN60751: 1996 Drive on open circuit fault
• Ni120 to DIN 43 760: 1985 • Disabled / upscale / downscale MECHANICAL
• jPt100 to JIS C1604: 1981
Channel status Module Key Code
• User definable linearisation table, NOTE 1
• Active / Inactive • C3
Offset (2-wire RTD mode) Module width
RTD INPUT
• User defined value • 42 mm
Input type Range Weight
Pt100, Pt500 -200 to +850° C RESPONSE TIME • 245 g
jPt100 -200 to +650° C Signal change to availability on Railbus
Ni120 -60 to +250° C • 600 ms (max.)
www.ge-ip.com/process 57
2/1 I/O Modules
– 1 s per channel P
4-20mA
SAFETY
MODULE SPECIFICATION Location of module
See also System Specification Field wiring protection FIELD TERMINALS
• [EEx ia] IIC
OUTPUTS Safety description (each channel) Field Wiring Type Recommended Field Terminal
• Vo = 24.6 V, Io = 93 mA, Po = 0.57 W
Number of channels
• 8 FM entity parameters
Intrinsically safe
• Voc ≤ 24.6 V dc, Isc ≤ 93 mA 8621-FT-IS
Nominal signal range (span) standard
• Ca ≤ 0.42 μF, La ≤ 4.2 mH
• 4 to 20 mA
Full signal range Intrinsically safe
POWER SUPPLIES loop disconnect
8622-FT-IS
• 1 to 22 mA
IS Railbus (12V) current
Voltage to load
• All channels @ 22 mA into 650 Ω load) – 630 mA
• 13 V min. @ 20 mA
Power dissipation within module
Load resistance
• 4.1 W (max.)
• 0 to 650 Ω max.
Accuracy (@ 25 °C) MECHANICAL
• ± 20 μA
Module Key Code
Temperature stability
• A4
• (-40°C to + 70 °C) – ± 0.006% of span per °C
Module width
Resolution
• 42 mm
• 12 bits
Weight
Open circuit detection threshold
• 265 g
• > 685 Ω (typ.)
(also detects loads greater than driveable range)
Isolation
• Any channel to Railbus – 60 V ac
• Between channels) – None
CONFIGURABLE PARAMETERS
Output initialisation state
• Predefined value
Drive on “fail-safe”
• Upscale / downscale / last value
Channel status
• Active / Inactive
* Time to reach 90% level for 4-20 mA step into 650 Ω load
8204-AO-IS SAFETY
HAZARDOUS AREA SAFE AREA OR ZONE 2/
Field wiring protection ZONE 0/DIV1 DIV2 HAZARDOUS AREA
• [EEx ia] IIC
• 8 single-ended ouput channels
Safety description
• Intrinsically safe • Vo = 24.6 V, Io = 93 mA, Po = 0.57 W
• Conventional 4–20 mA #
POWER SUPPLIES
• Open-circuit field wiring detection Channel 1 of 8
OUTPUTS MECHANICAL
FIELD TERMINALS
Number of channels Module Key Code
• 8 • A4
Field Wiring Type Recommended Field Terminal
Nominal signal range (span) Module width
• -4 to 20 mA • 42 mm
Full signal range Weight Intrinsically safe
8621-FT-IS
standard
• 1 to 22 mA • 245 g
Voltage to load
Intrinsically safe
• 13 V min. @ 20 mA 8622-FT-IS
loop disconnect
Load resistance
• 450 Ω max.
Accuracy (@ 25 °C)
• ± 20 μA
Temperature stability
• (-40°C to +70 °C) – ± 0.006% of span per °C
Resolution
• 12 bits
Open circuit detection threshold
• 0.7 mA ± 0.2 mA
Isolation
• Any channel to Railbus – 60 V ac
• Between channels – None
CONFIGURABLE PARAMETERS
Output initialisation state
• Predefined value
Drive on “fail-safe”
• Upscale / downscale / last value
Channel status
• Active / Inactive
www.ge-ip.com/process 59
2/1 I/O Modules
SAFETY
MODULE SPECIFICATION
See also System Specification Field wiring protection
• [EEx ia] IIC FIELD TERMINALS
INPUTS Safety Description (each channel)
• Uo = 10.5 V, Io = 14 mA, Po = 0.04 W Field Wiring Type Recommended Field Terminal
Number of channels
FM Entity parameters
• 16
• VOC ≤ 10.5 V dc, ISC ≤ 14 mA Intrinsically safe,
OFF current • Ca ≤ 2.67 μF, La ≤ 176 mH 16-channel
8623-FT-IS
• <1.2 mA
Isolation
ON current • Any channel to Railbus) – 60 V ac Intrinsically safe,
• >2.1 mA (channels arranged in two groups of eight, with returns commoned 8-channel loop 8624-FT-IS
within each group) disconnect
Switching hysteresis
• 200 μA (nom.)
POWER SUPPLIES
Applicable specifications
• NAMUR, DIN19234 IS Railbus (12V) current
• (16-channel mode) – 350 mA (max.)
Voltage applied to sensor
• (8-channel mode) – 285 mA (max.)
• 7.0 to 9.0 V from 1 kΩ ±10%
Output (wetting) current MECHANICAL
• @ 100Ω line impedance
• >6 mA Module Key Code
• B1
Line fault detection
• Short circuit Module width
• <100 Ω • 42 mm
• Open circuit Weight
• >90 kΩ • 170 g
Maximum input frequency in pulse counting mode
• 20 Hz
Minimum pulse width detected
• 45 ms
CONFIGURABLE PARAMETERS
Selectable input filter
• Fast, slow or user defined
(User defined permits 0 to 512 ms values in 3ms steps)
Latch inputs
• Enable / Disable
• 25 V MECHANICAL
Current limit per channel 10 20 30 40 50
Module Key Code
• 45 mA (min.) Output current (mA)
• B5
Output supply ripple
Module width
• <0.5% of output (pk. to pk.)
• 42 mm FIELD TERMINALS
Line fault detection
Weight
• Short circuit – <15 Ω
• 220 g Field Wiring Type Recommended Field Terminal
• Open circuit – >13 kΩ
Isolation
• Any channel to Railbus – 60 V ac Intrinsically safe
8621-FT-IS
standard
• Between channels – None
www.ge-ip.com/process 61
2/1 I/O Modules
output channels
Input Sensors
• 2- and 3-wire pulse transmitter format 5 6
4-20mA 4-20mA 4-20mA
MODULE SPECIFICATION
See also System Specification
www.ge-ip.com/process 63
2/1 I/O Modules
LED INDICATORS
www.ge-ip.com/process 65
About GE Intelligent Platforms
GE Intelligent Platforms provides industrial software, control systems and embedded computing platforms
to optimize our customers’ assets and equipment. Our goal is to help our customers grow the profitability
of their businesses through high-performance solutions facilitated by the Industrial Internet. We work
across industries, including manufacturing, water, oil & gas, mining, power, defense and aerospace. A
division of GE, we are headquartered in Charlottesville, VA. www.ge-ip.com
www.ge-ip.com
©2014 General Electric Company. All Rights Reserved. *Trademark of GE Intelligent Platforms, Inc.,