edurev.in-Problem solving on Transformers
edurev.in-Problem solving on Transformers
edurev.in/studytube/Problem-solving-on-Transformers/e28812e7-7c8e-48fb-9317-96cadefcdf08_t
Introduction
In this lesson some typical problems on transformer are solved with emphasis on logical
steps involved. For a practical two winding transformer, the knowledge of approximate
equivalent circuit is of utmost importance in order to predict its performance. Equivalent
circuit parameters are either supplied directly or indirectly in terms of O.C and S.C test data.
The first problem enumerates in detail how to get the equivalent circuit parameters from
test data. The importance of the side (LV or HV) in which calculations are carried out is
highlighted. The second problem, in fact, is an extension of the first problem. Calculation of
regulation, efficiency and maximum efficiency are dealt with in these problems.
Next few problems highlight the basic calculation steps involved in ideal 3-phase
transformer and ideal auto transformer since the equivalent circuit of these transformers
are outside the scope of first year electrical technology course.
1. The O.C and S.C test data are given below for a single phase, 5 kVA, 200V/400V, 50Hz
transformer.
Draw the equivalent circuit of the transformer (i) referred to LV side and (ii) referred to HV
side inserting all the parameter values.
Solution
Let us represent LV side parameters with suffix 1 and HV side parameters with suffix 2.
Let us show the test data in the approximate equivalent circuit (Figure 28.1) of the
transformer as given below. Due to the fact that the HV side is open circuited, there will be
no current in the branch re1 +jx e1 . So entire power of 150W is practically dissipated in Rc l1.
The no load current I01 = 1.25 A is divided into: magnetizing component I m1 and core loss
component Icl1 as depicted in the phasor diagram figure 28.1.
1/12
Figure 28.1: O.C equivalent circuit and phasor
diagram.
= 1.25 × 0.8
∴I m1 = 1A
= 1.25 × 0.6
∴I cl1 =
0.75A
2/12
Calculation of series parameters is
rather simple and as follows.
and x e1 = a2 xe2
So the equivalent circuit referred to LV side can now be drawn showing all the parameter
values as shown below in figure 28.3.
We are now in a position to draw the equivalent circuit of the same transformer referred to
the HV side as shown in figure 28.4.
After getting the equivalent circuit, regulation, efficiency of the transformer can be
predicted under various loading conditions. Solution of the next problem shows how
equivalent circuit can be used to predict the performance,
2. For the same transformer (single phase, 5 kVA, 200V/400V, 50 Hz) of problem 1, the
equivalent circuit of which is known, calculate the following:
i. the efficiency of the transformer at 75% loading with load power factor = 0.7
Solution
∴ % efficiency, η = 91.35%
4/12
∴ x = 0.83
= 0.83 × 5kVA
iii. To calculate the regulation of the transformer at load current I 2 and load power factor
cos θ, we use the following formula in terms of HV side parameters.
iv. It is interesting to note that the difference between the reflected primary supply voltage
magnitude V1' and the secondary load terminal voltage magnitude V 2 is the numerator of
the regulation formula used above.
V1 = a V 1'
= 0.5 × 419.92
∴ V1 = 210 V
It may be recalled that one can make a 3-phase transformer by using a bank of three
numbers of identical single phase transformers or a single unit of a 3-phase transformers.
1. Three single phase ideal transformers, each of rating 5kVA, 200V/400V, 50 Hz are
available.
a) The LV sides are connected in star and HV sides are connected in delta. What line to line
3-phase voltage should be applied and what will be the corresponding HV side line to line
voltage will be? Also calculate and show the line and phase current magnitudes in both LV
& HV sides corresponding to rated condition.
b) The LV sides are connected in delta and HV sides are connected in delta. What line to
line 3-phase voltage should be applied and what will be the corresponding HV side line to
line voltage will be? Also calculate and show the line and phase current magnitudes in both
LV & HV sides corresponding to rated condition.
5/12
Solution
Here the idea is not to exceed the voltage and current rating of HV and LV coils of each
single phase transformer. Now for each transformer having rating 5 kVA, 200V/100V, 50
Hz we have:
Solution of (a)
In this case HV sides are connected in star and LV sides are connected in delta as shown
in figure 28.5. Thus line to line voltage to be applied to HV side must not exceed 200 √3 =
346.4V . This will ensure that rated voltage is applied across each of the HV coil and rated
voltage of 100 V is induced in each of the LV coil. Obviously the available line to line
voltage on the LV side will be 100 V since the coils on this side are connected in delta.
Now we are in a position to calculate the total kVA handled by the bank of 3-phase
transformer. Referring to the LV side the transformers supplies 86.6 A line current at a line
to line voltage of 100 V. Therefore, total kVA supplied is equal to Similarly total kVA drawn
from the supply is calculated as Thus we see
the total kVA becomes 3 times the individual
kVA rating of the transformers. Since the
transformers are assumed to be ideal Total kVA input = Total kVA output.
6/12
Solution of (b)
Since LV coils are connected in star allowed line current to be delivered is 50 A. So total
kVA output is √3 ×173.2 × 50 VA = 15 kVA . In each HV coil current has to be 25 A and the
corresponding supply line current is √3 ×25= 43.3 A . Total input kVA is √3 × 200 × 43.3 VA
= 15 kVA . Distribution of phase and line currents in LV and HV sides are shown in figure
28.6.
2. Three identical single phase transformers each of rating 5 kVA, 200V/100V, 50Hz are
connected in delta-delta. Calculate what line to line voltage to be applied to the HV side?
Also find out corresponding LV side line to line voltage. Find out the kVA rating of the bank
such that none of the transformers get over loaded.
Solution
Solution: The relevant connection for open delta is shown in figure 28.8
7/12
Figure 28.8: Connection of transformers
for open delta.
A careful look at the circuit in fig 28.8 shows that both HV and LV coils are in series with
the lines. Thus if we want the transformers not to be over loaded, line currents on the LV
side must be 50 A which automatically fixes the HV side line current to be 25 A.
Let us use to calculate the kVA handled by the bank of two single phase
transformers i.e;
Solution
First note that it is not a bank of single phase transformers. In fact it is a single unit of 3-
phase transformer with the name plate rating as 500 kVA, 6000 V/400 V, 50Hz, delta-star
connected 3-phase transformer. 500 kVA represents the total kVA and voltages specified
are always line to line. Similarly unless otherwise specified, kW rating of a 3-phase load is
the total kW absorbed by the load. The connection diagram is shown in figure 28.9.
8/12
Figure 28.9: Connection diagram
with 3-phase load.
Load kVA =
300/0.8 = 375 kVA = input kVA
I 2L = 541.3 A
∴I 1L = 36.1 A
Recall that an auto transformer essentially is essentially a single winding transformer with
a portion of the winding common to both supply and the load side. In contrast to a two
winding transformer it can not provide isolation between HV and LV side. Here VA is
transferred from one side to the other not only by magnetic coupling but also by electrical
conduction. Autotransformer becomes cheaper than a similarly rated two winding
transformer when the voltage transformation ratio is close to unity. A single phase two
winding transformer can be suitably connected to perform like an auto transformer.
1. A 5kVA, 200 V/ 100 V, 50 Hz, single phase ideal two winding transformer is to used to
step up a voltage of 200 V to 300 V by connecting it like an auto transformer. Show
the connection diagram to achieve this. Calculate the maximum kVA that can be
handled by the autotransformer (without over loading any of the HV and LV coil).
How much of this kVA is transferred magnetically and how much is transferred by
9/12
electrical conduction.
Solution
Two connect a two winding transformer as an auto transformer, it is essential to know the
dot markings on the two coils. The coils are to be now series connected appropriately so
as to identify clearly between which two terminals to give supply and between which two to
connect the load. Since the input voltage here is 200 V, supply must be connected across
the HV terminals. The induced voltage in the LV side in turn gets fixed to 100 V. But we
require 300 V as output, so LV coil is to be connected in additive series with the HV coil.
This is what has been shown in figure 28.10.
Since the load is in series with LV coil, so load current is same as the current flowing
through the LV coil. Thus a maximum of 50 A can be drawn by the load otherwise
overloading of the coils take place.
∵ transformer is ideal
Now the question is now much current is flowing in the HV coil and in which direction?
However, this is quite easy since supply and load currents are already known along with
their directions as shown in figure 28.10. Applying KCl at the junction P, we get:
The direction of I HV is obviously from top to bottom. No matter whether a two winding
transformer is used as a two winding transformer or as an autotransformer, mmf must be
balanced in the coils. If current comes out through the dot terminal in the LV coil, current
must flow in through the dot of the HV coil.
10/12
It is important to note that as a two winding transformer, kVA handling capacity is 5 kVA,
the rating of the transformer. However, the same transformer when connected as auto
transformer, kVA handling capacity becomes 15 kVA without overloading any of the coils.
= 15 – 5 = 10 kVA
2. An autotransformer has a coil with total number of turns NCD = 200 between terminals C
and D. It has got one tapping at A such that NAC = 100 and another tapping at B such that
NBA = 50.
Calculate currents in various parts of the circuit and show their directions when 400 V
supply is connected across AC and two resistive loads of 60Ω & 40Ω are connected across
BC and DC respectively.
Solution
Let us first draw the circuit diagram (shown in figure 28.11) as per data given in the
problem. First let us calculate the voltages applied across the loads remembering the fact
that voltage per turn in a transformer remains constant.
= 200 × 4 = 800V
So, current through 40Ω = 800/40 = 20A
= 150 × 4 = 600 V
11/12
Figure 28.11: Circuit arrangement.
Now we know all the load currents and the current drawn from the supply. Current
calculations in different parts of the transformer winding becomes pretty simple-one has to
apply KCL at the tap points B and A.
It is suggested to repeat the problem if 40Ω resistor is replaced by an impedance (30 + j40)
Ω other things remaining unchanged.
12/12