Bucher Hand Terminal Ivalve-Parameter
Bucher Hand Terminal Ivalve-Parameter
Published by
Bucher Hydraulics AG
Industriestrasse 15
CH-6345 Neuheim
Phone +41 41 757 03 33
Fax +41 41 757 05 00
Email [email protected]
Internet www.bucherhydraulics.com
Classification: 430.310.
2/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve
Contents Page
2 Product description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Handterminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.2 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1 Description of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3.1 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.1 Troubleshooting / Fault diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.2 Soft-stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1.1 Scope
This manual is:
S a part of the iValve lift-control valve / iCon for parametrisation and
maintenance
S applicable to the iValve and related components such as the
Handterminal and iWIN
Reference Description
300-P-9010528 Data sheet lift control valve i250 / i500
300-I-9010542 Parametrization and maintenance iValve
300-I-9010544 Commissioning and maintenance iValve
300-S-9010437 Spare Parts iValve i250
300-S-9010548 Spare Parts iValve i500
Term Description
iValve Intelligent lift control valve
iCon Electronic control card for iValve
Handterminal Terminal (optional) for the parameterisation
of the iValve
iWIN PC-software (optional) for the parameterisation
of the iValve
iBox Sensor unit in the iValve
iTeach Program on the iCon
ParamCard Memory card
SMA Monitoring of the UCM/A3 valve
(“Self Monitoring Acknowledgement”)
4/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 2 Product description
2 Product description
2.1 Handterminal
Keys
1 Menu direction-dependent parameters
2 Menu direction-independent parameters
3 Menu iTeach / adjustments / tests
4 Menu functions / information
↑ Steps to previous parameter
↓ Steps to next parameter
+ Increases the value of the
current parameter
- Decreases the value of the
current parameter
Connection
S Connect the handterminal to the iCon using the cable provided
S Connecting cable is a standard ethernet network cable
v: 1.00 Q: 250
K1 … K8
K 1-8 1100 0000 S The left part of the second line always indicates the current speed (v)
v: 1.00 p: 25.0
in m/s.
K 1-8 1100 0000 S Pressing the ↑ or ↓ key changes the indication in the right part of the
v: 1.00 T: 31 second line:
-
K 1-8 1100 0000
S Indication of current flow Q in l/min
v: 1.00 PM: 0.49
Fast speed ∧
{ 0.629}m/s S Parameter value is being edited, indicated value not yet saved
Fast speed ∧
! 0.630 m/s S Invalid parameter value (saved value outside permissible range,
value could not be read, …), indication of default value
Status: ---
ok
Example: Display in menu mode, event log, status (menu bar 4)
Status: 48
P-card: Access S Default indication
6/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 2 Product description
2.1.2 Password
The iCons parameterd and special functions can be password-
protected. There are two password levels, level1 and level2, which can
be logged in. The passwords for the two levels consist of four digits
each.
Factory setting for level1: 0000
Factory setting for level2: 1930
Login on level1 is required to modify parameters and to execute certain
functions.
Password “0000” for level1 means: no password protection (login on
level1 always active).
Login on level2 is only required for very rarely used service functions.
If a password is set and the user is currently logged in the display will
read 1: Logout .
+ execute
If a password is set and the user is currently not logged in the display
will read 0: Login 1 .
+ execute
In this case the user must log in first before the password can be
changed: ⇒Logging in
If the two passwords entered are identical the display will read
for approx. 1 second, then change to
Carried out!
1: Change 1
+ execute
The user is logged in, parameters can be changed and functions can be
extracted (Change Function).
In order to log out and protect the Parameters against inadvertent para
meterisation: ⇒Logging out
If the two passwords entered are different, the display will read
Confirmation for approx. 1second, then change to
Confirm. wrong!
1: Change 1 .
+ execute
8/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 2 Product description
Logging in (level1)
The user is logged in, parameters can be changed and functions can be
executed.
0: Login 1 .
+ execute
Logging out
change to 0: Login 1 .
+ execute
digit in brackets tells what password level is required to modify the pa
rameter or execute the function.
10/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 2 Product description
Forgotten password
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 12/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
Control values:
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 13/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 14/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 15/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 16/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 17/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
i250/250:
44.3
i500:
44.3
65 ** P m1-curr. (PM) 0 … 10 i250/160: - P-component of PID-current
2 controller, solenoid m1 (prop.)
i250/250:
2
i500:
3
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 18/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
i250/250:
3
i500:
5
68 ** Resist. m1 (PM) 1 … 100 i250/250: Ohm Ohmic coil resistance, solenoid m1
10.1 (prop.) at 20 °C
i250/160:
10.1
i500:
7.38
307 * Type s1 Max. pressure Max. pressure - Function of switching output s1
Min. pressure
Speed monitor
100 s1: pressure 0 … 100 50 bar Switching point, pressure switch s1
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 19/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
252 ** T1:delta ramp ↑ 0 … 2700 ↑ i250/160: mA iTeach: start procedure, delta start
30 current for ramp
↑ i250/250:
30
↑ i500:
30
253 ↓ 0 … 2700 ↓ i250/160:
30
↓ i250/250:
30
↓ i500:
100
258 ** T1:delta safe ↑ 0 … 1000 ↑ i250/160: mA iTeach: safety margin – difference
10 between calculated offset current
and the final ramp value that is
↑ i250/250:
actually set
10
↑ i500:
30
259 ↓ 0 … 1000 ↓ i250/160:
10
↓ i250/250:
10
↓ i500:
10
254 T1:t target ↑ 0.1 … 60 ↑ 0.3 s iTeach: target start time
255 ↓ 0.1 … 60 ↓ 0.3
256 * T1:max.corr. ↑ 1 … 500 ↑ 100 mA iTeach: max. correction of offset
257 ↓ 1 … 500 ↓ 100 current by iTeach
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 20/40
Lift Control Valve iValve 3 Operation
____________________________________________________________________________
________________________________________________________________________________________________
300-I-9010543-EN-01/09.2015 21/40
3 Operation Lift Control Valve iValve
Demand values UP
Demand values DN
K8 speed v
80 %
Acceleration v
{ 0.501}m
Acceleration v
0.500 m Acceleration v
{ 0.499}m
Fast speed v
0.500 m/s
Demand values
Contr. values
Start Optim. ∧
time
P PM travel ∧
{1.501}
P PM travel ∧
1.500
P PM travel ∧
{1.499}
I PM travel ∧
6.000
Contr. values UP
Contr. values DN
Start Optim v
time
P PM travel v
P PM travel v { 0.801}
0.800
P PM travel v
{ 0.799}
I PM travel v
4.000
22/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 3 Operation
* Start speed ∧
Acceleration ∧
Fast speed ∧
Deceleration ∧
Slow speed ∧
Soft stop ∧
Relevelling ∧ * Start speed v
Soft st. Rlvl ∧ Acceleration v
* Insp. accel. ∧ Fast speed v
Insp. speed ∧ Deceleration v
* Insp. decel. ∧ Slow speed v
* K6 accel. ∧ Soft stop v
K6 speed ∧ Relevelling v
* K6 decel. ∧ Soft st. Rlvl v
* K7 accel. ∧ * Insp. accel. v
K7 speed ∧ Insp. speed v
* K7 decel. ∧ * Insp. decel. v
* K8 accel. ∧ * K6 accel. v
K8 speed ∧ K6 speed v
* K8 decel. ∧ * K6 decel. v
* Emerg. decel. ∧ * K7 accel. v
* Trigger speed ∧ K7 speed v
** Trigger volume ∧ * K7 decel. v
**TSA: p red ∧ * K8 accel. v
** Grad. Vm(p) ∧ K8 speed v
** TSA: T red. ∧ * K8 decel. v
** Grad. Vm(T) ∧ * Emerg. decel. v
* Trigger speed v
Demand values UP
** TSA: p red. v
Demand values DOWN
** Grad. Vm(p) v
** TSA: T red. v
** Grad. Vm(T) v
* I PM start ∧
* I PM start r. ∧
P PM travel ∧
I PM travel ∧
D PM travel ∧
* Pulsation PWM ∧
* I PM start v
Start Optim ∧
* I PM start r. v
* PID gain (v) ∧
P PM travel v
* FF Gain accel. ∧
I PM travel v
* FF Gain speed ∧
D PM travel v
* FF Gain decel. ∧
* Pulsation PWM v
** FF Ramp i sta. ∧
Start Optim v
** FF Ramp T. ∧
* PID gain (v) v
** FF Ramp i end. ∧
* FF Gain accel. v
* FF Gain speed v
* FF Gain decel. v
**Min curr.PM. v
**Max. Delta PM. v
** FF unlock i. v
** FF unlock T v
** FF Ramp i sta. v
** FF Ramp T. v
** FF Ramp i end. v
** FF A3 % open. v
** FF A3 T . v
** FF A3 % hold. v
Contr. values UP
Contr. values DOWN
24/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 3 Operation
All
+execute
ITeach Para UP
iTeach Para. DOWN
T3: corr. Max. v
{ 0.35 }
T1: start time v
T1: start time v { ON }
Pipe rup.test
+ execute
26/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 3 Operation
T1:start time ∧
**T1:p0 ∧
**T1:i(p) ∧
**T1:grad. i/p) ∧
**T1:delta ramp ∧
**T1:delta safe ∧
T1:start time v
T1: target ∧
**T1:p0 v
*T1:max. korr. ∧
**T1:i(p) v
T3:slow travel ∧
**T1:grad. i/p) ∧
T3: t target ∧
**T1:delta ramp ∧
*T3 max. corr. ∧
**T1:delta safe v
T1: target v
*T1:max. korr. v
T3:slow travel v
T3: t target v
*T3 max. corr. v
iTeach Para. UP
iTeach Para. DN
Deleting
+ select
Load parameters
+ select
Save parameters
+ select
Passwort
+select
Functions
Information
Even log
+ select
**
**
Version data
+ display
Operating data
+ display
Process values
+ display
**
SMA frequency
+ display
** Digital inputs
+ display
** Digital outputs
+ display
** EEPROM
+ select
28/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 3 Operation
Parameterisation
Display of curves
30/40 300-I-9010543-EN-01/02.2015
Lift Control Valve iValve 4 Repair
4 Repair
32/40 300-I-9010543-EN-01/02.2015
flashing
Event Description / Comment Possible causes Analysis / Remedy
LED
Hints
(Emergency stop) (as long as
Error relay
supply fails).
complete standstill).
012: CV: Failure Communication with valve failed 1 Y iCon and iBox (check plugs,
defective / interrupted error cable)
300-I-9010543-EN-00/09.2015
Flow signal Qf (unscaled) too high (measured raw EMC disturbance, measurement error, flow meas Check electrical earthing /
022: Flow Qf high 1 Y i
value > 6MHz) measurement faulty error grounding
Flow signal Qf (unscaled) too low (measured raw EMC disturbance, measurement error, flow meas Check electrical earthing /
023: Flow Qf low 1 Y i
value < 2MHz) measurement faulty error grounding
Flow Qf (scaled) too low (lowest permissible value: Measurement error and/or incorrect scaling, meas Check scaling (possibly contact
Events are in error- / event list with mnemonic "e" listed.
error
4 Maintenance
switch it!
091: SIU DN speed too high (travelling DOWN), threshold for distance too short, ball valve closed, pipe rupture 2 error N
valve / adjust it correctly (by
triggering an SIU can be parametrised valve closes at a too low speed, load pressure
authorised personnel only!)
too low (particularly during commissioning)
iii= if repeated or lasting: replace ParamCard 2= de-activated (switched OFF) when ok and no
The following events cause the iCon to stop the travel immediately (error relay is activated, solenoids are de-energised until
________________________________________________________________________________________________
33/40
flashing
Event Description / Comment Possible causes Analysis / Remedy
LED
Hints
(Emergency stop) (as long as
Error relay
supply fails).
096: I m0 (A3) drop Current in m0 (A3) solenoid drops out Safety relay opened before end of travel 2 - N Check contactor drop-out delay
Lift Control Valve iValve
complete standstill).
300-I-9010543-EN-00/09.2015
command timing (No new
Adjustment of 0-point (for flow measurement) not Load pressure too low (installation incorrectly meas command before end of SMA
108: Error 0-point correct. Adjustment is carried out automatically at dimensioned), wrong command timing, RSVQ 2 Y i
error procedure). After replacement of
start of travel! piston replaced
RSVQ-piston (and only in this
case!!): adjust 0-point
iii= if repeated or lasting: replace ParamCard 2= de-activated (switched OFF) when ok and no
The following events cause the iCon to stop the travel immediately (error relay is activated, solenoids are de-energised until
________________________________________________________________________________________________
34/40
flashing
Event Description / Comment Possible causes Analysis / Remedy
LED
Hints
(Drive disable) (as long as
Error relay
valid for K5?
error present)
300-I-9010543-EN-00/09.2015
024: Valve: Version iCon does not recognise the existing valve version Valve version not readable, or unknown 1 Y be lit permanently) iv
Temperature signal (unscaled) too high (measured EMC disturbance, measurement error, meas
028: Temperature high 1 Y Check electrical earthing/grounding i
raw value > 1023) temperature measurement faulty error
Events are in error- / event list with mnemonic "d" listed.
Temperature signal (unscaled) too low (measured EMC disturbance, measurement error, meas
029: Temperature low 1 Y Check electrical earthing/grounding i
raw value < 1) temperature measurement faulty error
4.1.3 Events which cause a Drive disable
iii= if repeated or lasting: replace ParamCard 2= de-activated (switched OFF) when ok and no commands,
after 500ms at the earliest
iv= also recorded at update of iCon firmware
Software V1.010
________________________________________________________________________________________________
35/40
flashing
Event Description / Comment Possible causes Analysis 7 Remedy
LED
Hints
(Drive disable) (as long as
Error relay
valid for K5?
error present)
ParamCard not (correctly) plugged in, card Check ParamCard (LED "card" must be
048: P-Card: Access Error when accessing ParamCard (I2C-access) 1 Y iii
Lift Control Valve iValve
300-I-9010543-EN-00/09.2015
error
Pressure (scaled) too low (lowest permissible Measurement error and/or incorrect scaling, meas Check scaling (possibly contact the
081: Pressure low 1 Y i
value: minus 1 bar) possible result from event 027 error factory)
Temperature (scaled) too high (highest permissible Measurement error and/or incorrect scaling, meas Check scaling (possibly contact the
082: Temperature high 1 Y i
value: plus 100 °C) possible result from event 028 error factory)
Temperature (scaled) too low (lowest permissible Measurement error and/or incorrect scaling, meas Check scaling (possibly contact the
4 Maintenance
e.g. parametrised slow speed higher than 1.54 x Set parameters to correct values (e.g.
145: Para: coherence Parameters not coherent fast speed, scaling for flow measurement not 1 error Y load factory settings), possibly contact
___________________________________________________________________________
iii= if repeated or lasting: replace ParamCard 2= de-activated (switched OFF) when ok and no commands,
after 500ms at the earliest
iv= also recorded at update of iCon firmware
________________________________________________________________________________________________
36/40
flashing
Event Description / Comment Possible causes Analysis / Remedy
LED
Hints
(SMA-signal not issued) (as long as
Error relay
valid for K5?
error present)
300-I-9010543-EN-00/09.2015
Self-monitoring acknowledge error (monitored
See document SMA-Signal_300-D-SMA-Signal- See document SMA-Signal_300-D-SMA-
135: SMA2 error while travelling down). No SMA signal is issued - - Y
en.pdf Signal-en.pdf
after the travel that caused the SMA2 error
lock the elevator when SMA-signal is not issued).
4.1.4 Events related to SMA-Signal
________________________________________________________________________________________________
37/40
flashing
Event Description / Comment Possible causes Analysis / Remedy
LED
Hints
(only information, no (as long as
Error relay
valid for K5?
effect) error present)
24 V voltage too high (above 26.4 V. Threshold Using battery supply in case of emergency
067: PS 24V high - pwr Y Check 24 V power supply
Lift Control Valve iValve
can also be higher than 26.4 V) lowering, power supply wrongly adjusted
24 V voltage too low (below 21.6 V. Threshold can 24 V power supply overloaded / wrongly sized / Check 24 V power supply (also check
068: PS 24V low - pwr Y
also be lower than 21.6 V) wrongly adjusted during travel)
300-I-9010543-EN-00/09.2015
Current in m0 (A3) solenoid too high while not Measurement error, incorrect wiring, short-circuit,
092: I m0 (A3) high - m0 Y Check wiring of A3 solenoid (m0) ii
actuated current from external source
Current in m0 (A3) solenoid too low while not Measurement error, incorrect wiring, current from
093: I m0 (A3) low - m0 Y Check wiring of A3 solenoid (m0) ii
actuated external source
Current in m0 (A3) solenoid too high while Wrong solenoid connected, incorrect wiring,
094: I m0 (A3) high - m0 Y Check wiring of A3 solenoid (m0)
actuated short-circuit
(m0)
Current in m1 (PM) solenoid too high while not Measurement error, incorrect wiring, short-circuit,
097: I m1 (PM) high - m1 Y Check wiring of UP/DOWN solenoid (m1) ii
actuated current from external source
4.1.5 Events without Effect (only as information)
Current in m1 (PM) solenoid too low while not Measurement error, incorrect wiring, current from
098: I m1 (PM) low - m1 Y Check wiring of UP/DOWN solenoid (m1) ii
actuated external source
4 Maintenance
________________________________________________________________________________________________
38/40
flashing
Event Description / Comment Possible causes Analysis / remedy
LED
Hints
(only information, no (as long as
Error relay
valid for K5?
effect) error present)
Lift Control Valve iValve
300-I-9010543-EN-00/09.2015
104: R m1 (PM) low Coil resistance of m1 (PM) solenoid too low Incorrect wiring, short-circuit - m1 Y Check wiring of UP/DOWN solenoid (m1)
Events are in error- / event list with mnemonic "i" listed.
4 Maintenance
Following events have no impact, neither on error relay nor on error- / event list.
___________________________________________________________________________
________________________________________________________________________________________________
39/40
4 Repair Lift Control Valve iValve
4.2 Soft-stop
The iCon factory setting for the soft-stop distance is 0mm.
If a different soft-stop distance is required or set the parameter “Soft-
stop” shall be adjusted accordingly (0mm=Softstop=Off).
See Chapter 3.2
In this case the soft-stop switches shall be positioned with the corre
spondent distance away from the landing. Furthermore it must be made
sure, that the contactors drop out with sufficient delay, so that the soft
stop distance can be travelled.
40/40 300-I-9010543-EN-01/02.2015