Minimum Electrical Clearance
Minimum Electrical Clearance
Minimum Electrical Clearance
INDOOR
11 76.2 127.0
15 101.6 165.1
22 139.7 241.3
33 222.25 355.6
OUTDOOR
11 177.8 228.6
22 279.4 330.2
33 381 431.8
66 685.8 787.4
Mi i W ki Cl
Minimum Working Clearance:
OUTDOOR SWITCHYARD
11 2750 2500
33 3700 2800
66 4000 3000
Voltage in KV To ground in mm
132 6.10
220 7.00
400 8.84
800 12.40
Clearance(Mt)
Vertical Distance
Extra High Voltage 3.7 Meter + Add 0.3 meter for every additional 33KV
Extra High Voltage 2.0 Meter + Add 0.3 meter for every additional 33KV
Conductor
Conductor
Above 33KV Line 5.8 Meter + Add 0.3 meter for every additional 33KV
For Flat roof, Open Balcony, Verandah Roof and lean to Roof