Mod 5 Ele
Mod 5 Ele
A network of wires drawn connecting the meter board to the various energy
consuming loads (lamps, fans, motors etc) through control and protective devices for
efficient distribution of power is known as electrical wiring.
Electrical wiring done in residential and commercial buildings to provide power for
lights, fans, pumps and other domestic appliances is known as domestic wiring. There
are several wiring systems in practice. They can be classified into:
Distribution system - This system is more organized in the sense that the main circuit
is drawn to several distribution centers and connected to the distribution boards.
Branches are tapped from these distribution boards. This system of wiring has an
aesthetic appeal, as they are without joints and also makes the location of the fault
point easier. All the points are maintained almost at the same potential. Each circuit is
provided with an independent fuse. Provides flexibility for repair and maintenance.
This system is widely preferred for indoor wiring though expensive.
Types of Wiring:
Cleat wiring
CTS wiring or TRS wiring or batten wiring
Metal sheathed wiring or lead sheathed wiring
Casing and capping
Conduit wiring
1. Cleat wiring:
In this type of wiring, insulated conductors (usually VIR, Vulcanized Indian Rubber)
are supported on porcelain or wooden cleats.
The cleats have two halves one base and the other cap.
The cables are placed in the grooves provided in the base and then the cap is placed.
Both are fixed securely on the walls by 40mm long screws.
The cleats are easy to erect and are fixed 4.5 – 15 cms apart.
This wiring is suitable for temporary installations where cost is the main criteria but
not the appearance.
Advantages:
1. Easy installation
2. Materials can be retrieved for reuse
3. Flexibility provided for inspection, modifications and expansion.
4. Relatively economical
5. Skilled manpower not required.
Disadvantages:
In this wiring system, wires sheathed in tough rubber are used which are quite
flexible.
They are clipped on wooden battens with brass clips (link or joint) and fixed on to the
walls or ceilings by flat head screws.
These cables are moisture and chemical proof.
They are suitable for damp climate but not suitable for outdoor use in sunlight.
TRS wiring is suitable for lighting in low voltage installations
Advantages:
The wiring is similar to that of CTS but the conductors (two or three) are individually
insulated and covered with a common outer lead-aluminum alloy sheath.
The sheath protects the cable against dampness, atmospheric extremities and
mechanical damages.
The sheath is earthed at every junction to provide a path to ground for the leakage
current.
They are fixed by means of metal clips on wooden battens. The wiring system is very
expensive. It is suitable for low voltage installations.
1. The clips used to fix the cables on battens should not react with the sheath.
2. Lead sheath should be properly earthed to prevent shocks due to leakage currents.
3. Cables should not be run in damp places and in areas where chemicals (may react
with the lead) are used.
Advantages:
Disadvantages:
Advantages:
1. Highly inflammable.
2. Usage of unseasoned wood gets damaged by termites.
3. Skilled workmanship required.
5. Conduit wiring:
In this system PVC (polyvinyl chloride) or VIR cables are run through metallic or
PVC pipes providing good protection against mechanical injury and fire due to short
circuit.
They are either embedded inside the walls or supported over the walls, and are
known as concealed wiring or surface conduit wiring (open conduit) respectively.
The conduits are buried inside the walls on wooden gutties and the wires are drawn
through them with fish (steel) wires.
The system is best suited for public buildings, industries and workshops.
Advantages:
Disadvantages:
Switches S1 and S2 are two-way switches with a pair of terminals 1&2, and 3&4
respectively.
When the switch S1 is in position1 and switch S2 is in position 4, the circuit does not
form a closed loop and there is no path for the current to flow and hence the lamp will
be OFF.
a) Straight connection
b) Cross connection
When S1 is changed to position 2 the circuit gets completed and hence the lamp glows
or is ON. Now if S 2 is changed to position 3 with S 1 at position 2 the circuit continuity
is broken and the lamp is off. Thus the lamp can be controlled from two different
points.
1 3 ON
1 4 OFF
2 3 OFF
2 4 ON
o Fuses
o Relays
o Miniature circuit breakers (MCB)
o Earth leakage circuit breakers (ELCB)
FUSE
Fuse element connected between two terminals i.e. connected in series with the
circuit to be protected as shown in the figure 5.6(a).
The working principle of a fuse is based on the “Heating effect of Current” i.e.
Whenever a short circuit, over current or mismatched load connection occurs,
then the thin wire inside the fuse melts because of the heat generated by the
heavy current flowing through it. Therefore, it disconnects the power supply
from the connected system as shown in the figure 5.6(b).
In normal operation of the circuit, fuse wire is just a very low resistance
component and does not affect the normal operation of the system connected to
the power supply.
The material used for fuse wires must have the following characteristics
Advantages of fuse
1)It is simplest and cheapest protecting device.
2)It requires no maintenance.
3)The Operation of fuse is automatic
4)The minimum operating time during abnormal condition.
5)With the help of fuse heavy currents can be interrupted without noise, smoke,
gas and flame.
Disadvantages of fuse
1)Fuse is required to be replaced or rewired after its operation.
2)The replacement or rewiring of fuse takes a lot of time.
3)The current-time characteristics cannot be always corelated with that of the
Dept of EEE, EWCE
Basic Electrical Engineering
protected
equipment’s.
4)It is not possible to provide secondary protection to fuses.
When the excessive current flows take place through MCB due to abnormal
conditions, the bimetallic strip gets heated and it deflects by bending.
The latch causes the MCB to turn off by stopping the flow of the current in the
circuit.
This process helps to safeguard the appliances or devices from the hazards
happening due to overload or overcurrent.
The plunger hits the trip lever, it causes the automatic release of the latch
mechanism by opening the circuit breaker contacts.
The trip unit is the key part of the MCB – Miniature Circuit Breaker on which
the unit operates.
Advantages of MCB
Applications of MCB
MCB is the key component for the safety and efficient functioning of the electric
machines and is used in most of the electrical appliances that are used for
industrial applications.
In domestic usage appliances like lights, heaters, and fans require MCB to
constantly check and protect the connection.
The first aid can save the life and reduce severity of the accidents.
Electrical Safety Rules Following are few of the safety rules must be observed
while dealing with electricity.
• All the electrical supply lines shall be sufficient in power and size and of
sufficient mechanical strength for the work.
• All electric supply lines, wires, fittings and apparatus at a consumer's premises
should be in a safe condition and in all respects fit for supplying energy.
• The underground cable must be properly insulated and protected under all the
ordinary operating conditions.
• A suitable earthed terminal should be provided by supplier on the consumer's
premises.
• The bare conductors, if any are ensured that they are inaccessible.
• Proper precaution is taken about earthing of electrical equipment before
handled by the person.
No person shall work on any live electric supply line or apparatus and no
person shall assist such person.
Flexible cables shall not be used for portable or transportable motors,
generators, transformers, rectifiers, electric drills, welding sets etc. unless
they are heavily insulated and adequately protected from mechanical
injury.
When a.c. and d.c. circuits are installed on the same supports they shall be
so arranged and protected that they shall not come into contact with each
other when live.
First aid boxes must be provided and maintained at generating stations
and substations.
Fire buckets filled with clean dry sand and ready for immediate use for
extinguishing fires.
Instructions in English, Hindi and any local languages for the restoration
of person suffering from electric shock must be affixed in generating
station and substation at a suitable place.
Each installation is periodically inspected and tested.
The neutral conductor of a three phase four wire system shall be earthed
by not less than two separate and distinct connections with the earth both
at generating station and at substation.
Earthing
Earthing : The connection of electrical machinery to the general mass of earth,
with a conducting material of very low resistance is called earthing or grounding.
The earthing of electrical equipment bring the equipment to zero potential and
avoid the shock to the operator, under any fault conditions.
NOTE: In modern three phase four wire supply system uses grounded neutral.
Necessity of Earthing:
The current I gets an alternative path through the body of the person to earth
from the insulation resistance.
The resistance of body and earth are not very high and hence current increases to
such a high value that the person receives a fatal shock.
Hence when the machine is not earthed, there is always a danger of the shock,
under certain fault conditions.
So body of the person carries very low current which is not sufficient to cause
any shock.
Methods of Earthing
This ensures very low resistance path from appliance to the earth.
i) Plate earthing ii) Pipe earthing iii) Earthing through water main iv)
Horizontal strip earthing v) Rod earthing
Plate Earthing:
The size or dimension of the plate used in plate earthing is 60cm(H) x 60cm(W) x
3.18mm(D) for copper plate and 60cm(H) x 60cm(W) x 6.3mm(D) for the
galvanized iron plate.
Place the earthing plate vertically at a depth of below 3 meter from the ground
level.
Use a 12.7 mm diameter pipe to lay the earthing conductors through it.
Use a 190mm diameter pipe to connect the funnel and earthing plate.
Fill the coal, sand, and salt around the earthing plate in alternate layers in the earth
pit. After that fill the earth pit with black soil.
Salt soaks the alkali of the ground and the Coal makes the soil to hold the
moisture. So, using these Salt and Coal helps to increase the overall conductivity
and efficiency of the earthing system.
Funnel arrangement is provided to pour the water periodically to the earthing to
increase the conductivity.
Pipe Earthing:
ELECTRICITY BILL
In electrical engineering, the power rating of equipment is the highest power input
allowed to flow through particular equipment.
The power rating of an electric appliance is the electrical energy consumed per
second by the appliance when connected across the voltage of the mains.
Example: A bulb having rating of 60 W, 220 V, indicates that the bulb will
consume 60 J of energy per second when connected across the mains supply of
voltage 220 V.
For example: A 1000 watt electric iron running for one hour will consume (1000
watt X 1 hour) 1000 watt hour or 1 kilowatt hour (kWh) of electricity.
Similarly to calculate the monthly power consumption multiply the daily power
consumption by 30 days and for annual power consumption multiply the daily
power consumption by 365 days.
If we use 1000 Watts or 1 Kilowatt of power for 1 hour then you consume 1 unit or
1 Kilowatt-Hour (kWh) of electricity.
The tariff rates are decided based upon the different types of consumers such as:-
1. Residential 2. Commercial 3. Industrial
Let the initial reading of energy meter at the beginning of month = x kWh
Final reading of energy meter at the end of month = y kWh
Then, total kWh consumed for that month = (y-x)
But 1 Unit = 1 kWh
Therefore, Total Units of electrical energy consumed = (y-x) Units
The rate of electricity is given in terms of per unit cost.
If the cost of per Unit electrical energy is ₹R, then the total amount charged for the
consumption of electrical energy is given by the multiplication of ₹R and number
of Units consumed.
Therefore, the total electricity bill for one month = ₹ (y-x)R
Two-part tariff –
When the rate of electrical energy is charged on the basis of maximum demand of
the consumer and the units consumed it is called two-part tariff.
In this type, the total charge to be made from the consumer is split into two
components.
One is for the annual fixed charge (whether consumer uses the electricity or not,
the charges have to pay, these charges are based upon the total connected load) and
the other is the amount to be paid for the actual consumption of power.
The fixed charges depend upon the number of units consumed by the customer.
Thus the consumer is charged at a certain amount per kW of maximum demand + a
certain amount per kWh of energy consumed.
For Example: Mumbai Reliance energy has following tariff: First 100 units: Rs
2.96/unit & Next 200 units (from 101 to 300): Rs 5.56/unit Next 200 units (from
301 to 500): Rs 9.16/unit Any units after that (above 500): Rs 10.61/unit. So taking
the above case, if the consumption is less than 100 units, we just pay Rs 2.96 per
unit. But if the consumption increases beyond 500 units, every unit above 500 is
charged There is always error in assessing the maximum demand of the consumer.
at Rs 10.61 per unit. So if we have consumed 540 units in a month, the bill will be
calculated as:
First 100 units @ Rs 2.96 = Rs 296
Next 200 units @ Rs 5.56 = Rs 1112
Next 200 units @ Rs 9.16 = Rs 1832
Final 40 units @ Rs 10.61= Rs 424.4
So we pay higher amounts per unit as our consumption increases. The motive
behind such structure is to motivate people to consume less electricity
Solution: Maximum Demand = 200kW , Load Factor= 40% Tariff Rate = Rs.200
per kW of maximum demand + 10 paise per kWh
Energy consumed per annum(kWh)=(200 X 0.4 X 24(hours)X365(days))=700.80
X 103 kWh
Annual fixed charge=Rs.200 per kW of maximum demand
Annual fixed charge=200 X200= Rs .40,000
Running charge = 10 paise per kWh
Running charge=0.1X700.80x103 =Rs. 70,800
Total charge of tariff = Fixed charge + Running charge = 40,000+70,800= Rs.
Dept of EEE, EWCE
Basic Electrical Engineering
1,10,800.