The VT 35 You can ansog 2-pin sockets with protective earth (SCHUKO doses). and to determine whether
the outlet is properly connected to the electrical system TT systems (it is assumed that the electrical
system itself is fine).
You can also use the VT 35 Residual current circuit breakers (RCCB) Check with a tripping current of 10
mA to 30 mA.
Note when using the air conditioning and the storage conditions. The grid and portable device designed
for the following conditions:
- Indoor use
- In environments of pollution degree 2
- Up to 2000 m
- At temperatures of +5 ° C to +40 ° C
The device is only suitable for systems up to 230 V of Appendix II category.
CAT II: Circuits for domestic appliances or similar devices, where over-voltages medium
height may occur.
Example: flat, portable power tools, etc ...
CAT III: Circuits for high-performance machines, industrial plants, etc ..., can in which large
power surges.
Example: industrial machinery, factory equipment, etc ...
CAT IV: Circuits in which very large can power surges.
Example: network terminals, distribution centers, etc ...
Symbol (The unit is disposed properly, do not throw in the household waste)
(Directive 2002/96 / EC)
Cleaning
For cleaning disconnect and turn off the power of all ports. Clean with a damp cloth and some soapy
water, never use abrasives or solvents. Make sure that the unit is dry before re-use.
Guarantee
The unit is guaranteed in accordance with the terms and conditions against material and
manufacturing defects.
During the warranty period (1 year), the device may only be repaired by the manufacturer, who
reserves, service the unit of to replace all or part of.
The cost of returning the product to the manufacturer shall be borne by the buyer.
Unpacking – Packing
Before shipping the equipment has been tested mechanically and electronically in detail and all
precautions have been taken in order to receive the instrument in a-perfect condition. Please check
the device during unpacking for full-ness and transport damage. Notifications
s When transport damage immediately to the respective delivery service.
If you want to send the device, to use preferably the original packaging and place it in an email in
which you describe the reasons for the return as clearly as possible.
Description
N: Neutral
P: outer conductor
E: protective earth
1. Insert the plug of the Examiner VT35 in the test socket 10-16 A.
2. Check the three indicators: When all three lights is the outlet in order.
3. If one, two or all three indicators do not light, determine the fault using the table below.
4. Correct the error and perform a rescan.
Note: The transposition of neutral (N) and protective earth (E) is not recognized by the examiner VT35
Testing a fault current circuit breaker ≤ 30 mA
1. Check explained and fix the socket in the previous section optionally displayed error.
2. Set the selector switch for GFCI-tripping current to 10mA (Smallest fault current value).
3. Check the response of the RCCB by briefly pressing the test button.
If the GFCI is not triggered:
1. Increase the fault current by turning the dial to a position turn right to the next highest fault
current value.
2. Perform a new test of the RCCB.
3. Repeat steps 2b and 3b until the GFCI actually triggers and write down the set fault current
value.
4. If the GFCI does not trip even when the highest value of 30 mA, is the circuit breaker is defective
and must be replaced.