SABP-P-127
SABP-P-127
SABP-P-127
SABP-P-127
Guideline for Designing High Voltage Direct Current (HVDC)
Systems
Document Responsibility: UPS, DC Systems, and Power Electronics Standards
Committee
Contents
1 SCOPE ......................................................................................................................................................... 5
3 REFERENCES ................................................................................................................................................ 5
4 SYSTEMS DESCRIPTIONS.............................................................................................................................. 5
16 AUDIBLE NOISE...................................................................................................................................... 15
Summary of Changes
Paragraph Number
Change Type
Current Revision (Addition, Modification, Deletion, Technical Change(s)
Previous Revision New)
N/A (29 July 2021)
New SABP - -
1 Scope
This best practice provides a guideline for designing, installation and application
of voltage source converter (VSC) based, high-voltage direct current (HVDC)
power transmission systems for offshore applications.
3 References
All referenced specifications, standards, codes, drawings, and similar material
are considered part of this Best Practice to the extent specified applying latest
revisions unless stated otherwise.
4 Systems Descriptions
A HVDC power transmission system should consist of, but is not limited to, AC
side transformers, converter reactors, converter stations, DC cables, DC
grounding electrodes, AC filters, DC filters, cooling systems, communication
systems, control systems, and protection systems. Al terminologies related to
HVDC and are provided in IEC 60633 and IEC 62747.
Switching between the metallic return mode and metallic pole return mode
should be performed without power interruption.
5.3 Power Transmission Requirements
The power transmission requirements should be achieved with all redundant
equipment out of service and redundant insulated-gate bipolar transistor (IGBT)
switches bypassed.
The power transmission requirements should be met for the frequency range
specified in Table 1 throughout the entire range of ambient temperatures and at
all AC bus voltages as specified in SAES-P-100.
Any limitation on steady state or short-time power flow which may be necessary
due to abnormal AC system conditions should be implemented within the
control system.
57 ≤ fn ≤ 63 ꝏ
fn < 57 or fn > 63 20
The HVDC control system shall be stable under all operating conditions and
should not excite oscillations, such as sub-synchronous oscillations, between
the HVDC and AC system.
The controller should optimize the recovery of the DC system following faults
with the objective of obtaining the fastest practical power transfer recovery with
the minimum energy loss to the receiving AC system while at the same time
maintaining the stability of the AC systems.
• The HVDC system should be running in its normal control mode with all
control parameters at their nominal values prior to the application of the
power order step.
When a pole blocks while communications are not in-service, 90% of the
required DC power transfer to the other pole shoud be achieved within 100
milliseconds of the rectifier blocking.
• Bipolar operation at 25%, 50%, 75% and 100% of rated power transfer in
the normal power transfer mode
• Dedicated metallic return operation at 25%, 50%, 75% and 100% of rated
power transfer in the normal power transfer mode
• Pole metallic return operation at 25%, 50%, 75% and 100% of rated power
transfer in the normal power transfer mode
The HVDC system should recover to 90% of the pre-fault power transfer level
consistently within 150 milliseconds from the instant of fault clearing without any
subsequent oscillations.
The post-fault power order should be equal to the pre-fault power order unless
AC/DC systems dictate otherwise.
The control equipment should be provided with the facility to adjust the delay
between fault clearance and the start of recovery and the rate of recovery.
The selectable range of settings should be discussed during the engineering
studies.
The total time to restore the power to 90% of the pre-fault power from the end of
the deionization period shall not exceed 100 milliseconds.
Faults should be applied at the line ends and at the line midpoint for each line
segment between the converter stations. The demonstration should include the
influence of the function provided to transfer power from the faulted pole to the
other pole.
The clearing and recovery of DC line pole fault should be demonstrated for the
following system configurations with a pre-fault power transfer set at 100% for
the specific modes:
• Bipolar
• Dedicated metallic return in parallel with one pole used as metallic return
to transmit power to the extent possible under the above reduced voltage
conditions.
9 Controlled Shutdown
Each pole should be able to be shut down in a controlled manner by the
automatic reduction in the power order. The shutdown sequence and timing
should not negatively impact the AC systems.
The performance study should include but not be limited to the following types
of studies:
• Performance during pole start-up and shut-down sequences during two and
multi-terminal operation.
The HVDC system control should be designed such that the specified
performance is met with the communication system in service and for a
maximum communication system delay. The studies should also address
performance when the communication system is out of service.
The reactive power controls should, to the extent possible, minimize operation
of the on-load tap-changers for the converter transformers.
12 Insulation Coordination
Insulation coordination studies should be carried out to establish the required
insulation level for supplied equipment and determine the clearances between
energized parts and between energized parts and ground.
13 Limitation of Overvoltage
Blocking of the converter valves to protect them and other DC side equipment
from sustained over-voltages appearing on the AC system should not be
permitted. The converter station equipment should be adequately rated to allow
The use of converter valve group controls to limit temporary (dynamic) over-
voltages shall be permitted providing that the valves and other converter
equipment are adequately rated and that such action does not restrict the
power transfer capability of the HVDC system during or after the event.
• Lightning surges due to both direct strikes and back flashover on the DC line
or any of the AC lines connected to the converter stations
• Lightning surges due to direct strikes within the converter stations in the
event of shielding failures
• FWWL which is at least 1.25 times the front of wave protective level.
Oil Insulated Equipment: For all equipment with oil insulation and with arresters
connected within 5 meters of the terminals, the LIWL shall be an IEC standard
value. This value should not, for the internal insulation, be less than:
• The FWWL should not be less than 1.20 times the front of wave protective
level.
The converter terminal shall neither damage nor cause malfunction of the DC
control and protection system or the communication system.
• VHF, UHF & microwave radio systems 100 MHz to 8,500 MHz
• 100 microvolts/meter under fair weather conditions at any point outside the
station fence, and 500 meters from the nearest bus connecting the valve to
the converter transformers within the station
• 30 meters from the conductors of any outgoing AC line, HVDC line, and
electrode line
This RIL criterion should be achieved at all frequencies within the range of 150
kHz to 1,000 MHz.
16 Audible Noise
The audible noise should comply with Saudi Aramco Engineering Standard
SAES-A-105. The audible noise shall be limited for the overall station and the
various areas of the converter station buildings to the levels indicated in Table 2
for all operating conditions.
Noise reports should note the date, time and weather condition for each time a
set of measurements are taken at the site.
Document History
18 December 2016 New Saudi Aramco Engineering Standard developed as HVDC technology was
presented as a solution for offshore power supply reliability. Justifications
include:
1- Problems with powering offshore platforms with long AC cables.
2- HVDC provides a mitigation solution for power delivery reliability and voltage
regulation problems.
3- HVDC provides redundancy and scalability through its modular design.
4- The HVDC technology is recommended for immediate use to power Zuluf
platform and provide backup to Safaniya and Marjan fields.
29 July 2021 Conversion of the Saudi Aramco Engineering Standard SAES-P-127 to be a Saudi
Aramco's Best Practice (SABP-P127).