Earth Tests
Earth Tests
system, which is crucial for ensuring electrical safety and proper system operation. A low
resistance indicates a good grounding system capable of dissipating fault currents effectively.
Objective
Methods of Testing
There are several methods for measuring earth resistance, with the Three-Point (Fall-of-
Potential) method being the most common. Other methods include the Two-Point Method,
Clamp Meter Method, and Four-Point Method (used for soil resistivity).
IEEE 81: Guide for measuring earth resistance and soil resistivity.
IEC 60364: Electrical installations of buildings.
BS 7430: Code of practice for earthing.
IS 3043: Indian Standard for earthing.
Equipment Required
Test Setup
1. Identify the Earth Electrode to Test:
o Locate the main grounding electrode or earth pit.
2. Drive the Test Spikes into the Ground:
o Insert two auxiliary test spikes into the soil in a straight line with the electrode
under test.
o The typical spacing is:
Electrode to Spike 1 (P): 20 m20 \, \text{m}20m (distance varies based
on the size of the grounding system).
Spike 1 (P) to Spike 2 (C): 20 m20 \, \text{m}20m (or equal spacing).
3. Connect the Tester:
o Connect the Earth Electrode to the tester’s E terminal.
o Connect the first spike to the P terminal.
o Connect the second spike to the C terminal.
Test Execution
This method is faster but less accurate and is often used for quick checks.
Procedure
1. Connect one terminal of the earth tester to the electrode under test.
2. Connect the other terminal to a nearby reference grounding system.
3. Measure the resistance, which includes both the tested electrode and the reference ground
resistance.
4. Deduct the reference resistance (if known) to estimate the actual earth resistance.
Clamp Meter Method (Contactless)
This method uses a clamp-on tester to measure earth resistance without disconnecting the
grounding system.
Procedure
Acceptance Criteria
Purpose
Equipment Required
1. High-Voltage Test Set: Capable of generating the required test voltage at the specified
frequency.
2. Voltage Divider or Measuring Device: To monitor the applied test voltage.
3. Protective Devices: To safeguard personnel and equipment (e.g., overcurrent protection
and emergency stop).
4. Grounding Rods and Connections: For safety during testing.
5. Insulation Resistance Tester (Optional): For pre-test verification.
Procedure
1. Pre-Test Preparations
1. Visual Inspection:
o Inspect the equipment or cable for visible damage, dirt, or moisture.
o Verify that connections are clean and tight.
2. Environmental Conditions:
o Ensure the test environment is dry and free of contaminants.
o Maintain temperature and humidity levels within acceptable ranges per the
equipment specification.
3. Safety Measures:
o Set up barriers and warning signs around the test area.
o Ensure proper grounding of the equipment under test and the test setup.
o Verify the functionality of emergency shutdown mechanisms.
4. Initial Measurements (Optional):
o Measure insulation resistance to check the general condition of the insulation
before applying high voltage.
2. Test Setup
3. Test Execution
1. Ramp-Up Voltage:
o Gradually increase the voltage from zero to the specified test level.
o Monitor the voltage and current continuously during this phase.
2. Hold the Test Voltage:
o Maintain the specified voltage for the required duration (e.g., 1 minute).
o Observe for any signs of insulation failure, such as:
Sudden increase in leakage current.
Audible discharge sounds.
Visible sparking or breakdown.
3. Ramp-Down Voltage:
o Gradually reduce the voltage to zero before disconnecting the test equipment.
o This prevents transient overvoltages or damage to the insulation.
4. Post-Test Procedures
1. Inspect the Equipment:
o Check for any signs of damage, discoloration, or odors that may indicate
insulation failure.
2. Document the Results:
o Record the test voltage, leakage current, duration, and any observations.
o Compare the results with acceptance criteria specified in the standards or
manufacturer's guidelines.
3. Restore Equipment:
o Disconnect all test equipment and ensure the device is properly grounded before
returning it to service.
Acceptance Criteria
The insulation must withstand the applied voltage without breakdown or excessive
leakage current.
Leakage current values should remain stable and within permissible limits (varies by
equipment type and standard).