EM2M Instruction-Manual

The document provides safety precautions, specifications, wiring guidelines, and installation instructions for the EM2M-1P-C-100A device. It emphasizes the importance of following safety notifications, correct voltage supply, and proper wiring to prevent electric shock and equipment damage. Additionally, it includes configuration settings, communication protocols, and a detailed description of pulse output and measurement accuracy.

Uploaded by

Rohit Rangari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
279 views3 pages

EM2M Instruction-Manual

The document provides safety precautions, specifications, wiring guidelines, and installation instructions for the EM2M-1P-C-100A device. It emphasizes the importance of following safety notifications, correct voltage supply, and proper wiring to prevent electric shock and equipment damage. Additionally, it includes configuration settings, communication protocols, and a detailed description of pulse output and measurement accuracy.

Uploaded by

Rohit Rangari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

selec EM2M-1P-C-100A SAFETY PRECAUTIONS

PRODUCT PROFILE All safety related notifications, symbols and instructions that appear in this
operating manual or on the equipment must be strictly followed to ensure the
OP639-V03

safety of the operating person as well as the instrument.


If the equipment is not used in a manner specified by the manufacturer it might
impair the protection provided by the equipment.
Do not use the equipment if there is any mechanical damage.
Ensure that the equipment is supplied with correct voltage.

CAUTION :
1. Read complete instructions prior to installation and operation of the unit.
2. Risk of electric shock.
3. The equipment in its installed state must not come in close proximity to any
heating sources, oils, steam, caustic vapors or other unwanted process by
products.

WIRING GUIDELINES
SPECIFICATIONS
WARNING :
Display : 1 Row of 7 Digits
LCD Display with backlight 1. To prevent the risk of electric shock, power supply to the equipment
LCD indications : - Communication in Progress must be kept OFF while doing the wiring Arrangement.
:
MD - Maximum Demand of Power 2. Wiring shall be done strictly according to the terminal layout. Confirm
: IP - Import Energy that all connections are correct.
: EP - Export Energy 3. Use lugged terminals.
LED Indication : INT - Integration of Energy 4. To reduce electromagnetic interference use of wires with adequate
Wiring Input : 1Ø - 2W rating and twists of the same in equal size shall be made with shortest
: 176-276V AC (Self Powered) connections.
Rated Input Voltage
: 45 to 65 Hz 5. Layout of connecting cables shall be away from any internal EMI
Frequency Range
: Ib : 10A, Imin : 0.5A, Imax : 100A source.
Rated Input Current 6. Cable used for connection to power source, must have a cross section
Display Update Time : 1 sec for all parameters
: Auto / Manual (Programmable) of 25mm2 (13 to 11AWG ; 750C(min)). These wires shall have current
Display Scrolling carrying capacity of 100A.
Power Consumption : Less than 8VA 7. Copper cable should be used (Stranded or Single core cable).
Environmental Conditions : Indoor use 8. Before attempting work on device, ensure absence of voltages using
: Altitude up to 2000 meters appropriate voltage detection device.
: Pollution degree II
Temperature : Operating : -100C to 550C INSTALLATION GUIDELINES
: Storage : -200C to 750C
CAUTION :
Humidity : Up to 85% (non - condensing)
: DIN Rail 1. This equipment, being buit-in type, normally becomes a part of main
Mounting
: 150gms control panel and in such case the terminals do not remain accessible to
Weight the user end after installation and internal wiring.
Output : Pulse Output
2. Conductors must not come in contact with the internal circuitry of the
: Voltage Range : External 24V DC Max
equipment or else it may lead to a safety hazard that may in turn endanger
: Current Capacity : 100mA Max life or cause electrical shock to the operator.
Communication : RS485 MODBUS RTU 3. The equipment shall not be installed in environmental condition other than
Tightening Torque : 1.5 Nm to 2 Nm those mentioned in this manual.
4. Connector screw must be tightened after installation.
ORDER CODE INFORMATION
CONFIGURATION
Product Outputs Certification
There are 2 dedicated keys(Scroll & Enter) to enter into configuration
EM2M-1P-C-100A RS485 (Modbus RTU) & Pulse O/P Menu / change settings.
The settings should be done by a professional, after going through this user
manual and after having understood the application situation.
SERIAL COMMUNICATION
Interface standard and protocol RS485 AND MODBUS RTU For the configuration setting mode :
Communication address 1 to 255 Press the (Scroll & Enter) keys for 3 sec to enter or exit from the Configuration
menu.
Transmission mode Half duplex
In online mode, press Scroll key to move on to next page.
Data types Float and Integer In configuration mode, press Enter key to change the parameters value / page
Transmission distance 500 Meter maximum and Scroll key to enable the editing and save the changes in configuration.
Transmission speed Press the Enter key to check Serial no..
9600 &19200 (in bps)
Press the Enter key for 3 sec for communication Lock.
Parity None, Odd, Even
Stop bits 1 or 2 NOTE : Above 70A current pulse duration should be set to 0.05sec.

RESOLUTION LUG DESCRIPTION


7.2
Energy 0.01k
4.3
ACCURACY

Measurement Accuracy
15

Voltage ±0.5% of Full scale


Current ±0.5% of Nominal
7

Power Factor ±0.01 of Full scale


33

Frequency ±0.1% of Full scale


Active Power 1.00 % of Full scale
Reactive Power 1.00 % of Full scale
11

Apparent Power 1.00 % of Full scale


Active Energy Class 1
Reactive Energy Class 2
Apparent Energy Class 1
11.1 7.5
Demand Active Power 1.00 % of Full scale
Demand Reactive Power 1.00 % of Full scale LUG TYPE : 25mm2 Copper flat pin type lug
Demand Apparent Power 1.00 % of Full scale
(NOTE : to be Wired with LUG only)

Doc. name : OP INST EM2M-1P-C-100A OP639-V03(Page 1 of 3)


Config. Factory FRONT PANEL DESCRIPTION
Function Range or Selection
page Setting
FOR EM2M-1P-C-100A
1 Password 0000 to 9998 1000
Key Online Page Description
2 Change Password No / Yes No Press
2.1 New Password 0000 to 9998 0001 1st screen Displays Total Active Energy
2nd screen Displays Import Active Energy
3 Demand Interval Method Sliding / Fixed Sliding
3rd screen Displays Export Active Energy
4 Demand Interval Duration 1 to 30 15 Displays Total Reactive Energy
4th screen
5 Demand Interval Length 1 to 30 1 5th screen Displays Import Reactive Energy
kWh - Total/IP/EP 6th screen Displays Export Reactive Energy
6 POP Total VArh
kVArh -Total/IP/EP 7th screen Displays Apparent Energy
7 Pulse Weight 1/10/100/1000 1000 8th screen Displays Active Power
Press
8 Pulse Duration 0.05 to 2 sec 0.1 9th screen Displays Reactive Power
10th screen Displays Apparent Power
9 Slave Id 1 to 255 1
11th screen Displays Voltage L-N
10 Baud Rate 9600, 19200 bps 9600 bps
12th screen Displays Current
11 Parity None, Odd, Even None 13th screen Displays Power Factor
12 Stop Bit 1 or 2 1 14th screen Displays Frequency
13 Backlight 0 to 7200 0 15th screen Displays Max Demand Active Power
Factory Default 16th screen Displays Max Demand Reactive Power
14 No / Yes No
17th screen Displays Max Demand Apparent Power
15 Reset No / Yes No
15.1 Password 0001 to 9999 1001 MODBUS REGISTER ADDRESSES LIST
15.2 Reset kWh No / Yes No Readable / Writable Parameters : [Data Structure : Integer]
15.3 Reset kVArh No / Yes No Hex Length
Address Parameter Range (Register)
15.4 Reset kVAh No / Yes No Address
15.5 Reset Max Demand No / Yes No Min value Max value
40000 0x00 Password 0 9998 1
For resetting energy parameters user will be prompted for password. If correct
password is entered, the user will be able to reset parameters. This password 40001 0x01 Slave ID 1 255 1
will be greater than the configuration password by 1. Value Meaning

AUTOMATIC / MANUAL Demand Interval 0 Sliding 1


40004 0x04
Long press scroll key to toggle between Automatic/Manual mode. Method
1 Fixed 1

MODBUS REGISTER ADDRESSES LIST Min Value Max Value


40005 0x05 Demand Interval
Readable parameters for Communication [Length (Register) : 2; Data Structure : Float (Swapped)] 1 30 1
Length
Address Hex Address Parameter Demand Interval
40006 0x06 1 30 1
30000 0x00 Total Active Energy Duration
30002 0x02 Import Active Energy Value Meaning
30004 0x04 Export Active Energy 0 Total Wh 1
30006 0x06 Total Reactive Energy
1 Total VArh 1
30008 0x08 Import Reactive Energy
Export Reactive Energy 2 IP Wh 1
30010 0x0A 40007 0x07 POP
30012 0x0C Apparent Energy 3 EP Wh 1
30014 0x0E Active Power 4 IP VArh 1
30016 0x10 Reactive Power 5 EP VArh 1
30018 0x12 Apparent Power 0 1 1
30020 0x14 Voltage L-N
1 10 1
30022 0x16 Current
40008 0x08 Pulse Weight 2 100 1
30024 0x18 Power Factor
30026 0x1A Frequency 3 1000 1
30028 0x1C Max Demand Active Power Min Value Max Value
30030 0x1E Max Demand Reactive Power 40009 0x09 Pulse Duration 0.05 2.00 1
30032 0x20 Max Demand Apparent Power Meaning
Value
Energy rollover counter addresses : Energy rollover counter will increment 0 9600 1
40010 0x0A Baud Rate
when energy is roll over from 99999.99 to 0. 1 19200 1
[Data Structure: Integer]
0 None 1
30149 0x95 Total kWh
40011 0x0B Parity 1 Odd 1
30150 0x96 Import kWh
30151 0x97 Export kWh 2 Even 1
30152 0x98 Total kVArh 0 1 1
40012 0x0C Stop bit
30153 0x99 Import kVArh 1 2 1
30154 0x9A Export kVArh Min value Max Value
30155 0x9B kVAh 40013 0x0D Backlight OFF 0 7200 1
Value Meaning
PULSE OUTPUT DESCRIPTION
40014 0x0E Factory Default 1 Set to Factory 1
Pulse Output Type Description Pulse width Default
Fixed 40040 0x28 Reset kWh 1 Reset Active
POP1 Per kWh 0.05 to 2 sec 1
1000 Pulses Energy
Configurable 40041 0x29 Reset kVArh 1 Reset Reactive
Per kWh - Total/IP/EP 1
POP2 1/10/100/1000 0.05 to 2 sec Energy
Per kVArh - Total/IP/EP
Pulses
40042 0x2A Reset kVAh 1 Reset Apparent
1
Energy
40043 0x2B Reset Max 1 Reset Demand
1
Demand Power

Doc. name : OP INST EM2M-1P-C-100A OP639-V03(Page 2 of 3)


TYPICAL WIRING DIAGRAM MECHANICAL DIMENSIONS

1 PHASE 2 WIRE

35mm 47mm
+

456789
RS485

1 2 3
L - IN

- -
L - OUT PULSE 2 2
+

-
N 1
PULSE 1
+
selec
selec EM2M
EM2M

50Hz
1000))AA50Hz
EN50470-1/3
CONNECTION DIAGRAM FOR COMMUNICATION

-5((10
-10
90mm 45mm 90mm

2230
23 ,25
0VV 00..5
11 22

Master

RS485
Converter Suggested
terminating resistor
(120 ohm, ¼ watt)

selec
selec EM2M
EM2M selec EM2M
EM2M
0Hz
500Hz
A550Hz
Hz

5H
.5-10(100)A50 z
0)))AA
EN50470-1/3

EN50470-1/3

0,25-5(100)A
5-5(110000
VV 0.5-10(10
00,..52-10(

30V 0
2230V
223
23
2 00V
30

11 222 1 2
1 1 2

Contact sales for PC based monitoring


software to communicate with the meters.

(Specifications are subject to change, since development is a


continuous process.)
Selec Controls Pvt. Ltd.
Factory Address : EL-27/1, Electronic Zone, TTC Industrial
Area, MIDC, Mahape, Navi Mumbai - 400 710, India.
Website : www.selec.com
For Sales & Support,
Tel. No. : +91-22-41418468 / 452
Mob. No. : +91-9136977315, Email : [email protected]
For Service,
Tel. No. : +91-7498077172 / +91-7400069545
Email : [email protected]

Doc. name : OP INST EM2M-1P-C-100A OP639-V03(Page 3 of 3)