Modbus IP Manual BTU100L
Modbus IP Manual BTU100L
MODBUS IP MANUAL
FOR
BTU-100L
BTU Meter
CONTENTS
NOTES -
If value received at 164 address is = 20000 means either i/p A or i/p B or i/p C is open.
If value received at 165 address is = 20000 means either i/p A or i/p B or i/p C is open.
If value received at 164 address is = 20001 means i/p A is below by approx. 1% (3.84mA).
If value received at 165 address is = 20001 means i/p A is below by approx. 1% (3.84mA)
If value received at 164 address is = 20002 means i/p A is above by approx. 7.5% (21.2mA).
If value received at 165 address is = 20002 means i/p A is above by approx. 7.5% (21.2mA)
If value received at 164 address is = 20003 means error1 [TEMP DIFF NEGATIVE].
If value received at 165 address is = 20003 means error1 [TEMP DIFF NEGATIVE].
If value received at 164 address is = 20004 means error2 [TEMP DIFF EXCEDDED 20 DEGREES].
If value received at 165 address is = 20004 means error2 [TEMP DIFF EXCEDDED 20 DEGREES].
If value received at 168 address is = 20000 means i/p A is open.
If value received at 168 address is = 20001 means i/p A is below by approx. 1% (3.84mA)
If value received at 168 address is = 20002 means i/p A is above by approx. 7.5% (21.2mA)
If value received at 176 address is = 20000 means i/p B is open or above by approx 7.5%.
If value received at 177 address is = 20000 means i/p C is open or above by approx 7.5%.
If value received at 178 address is = 20000 means either i/p B or i/p C is open.
1.1 How to calculate Power from values received at address 30165 & 30166?
Power = (( value received at 30165 x 65536 ) + value received at 30166)
1.2 How to calculate Energy from values received at address 30167 & 30168?
Energy = (( value received at 30167 x 65536 ) + value received at 30168)
1.3 How to calculate Total Flow from values received at address 30170 & 30171?
Total Flow = (( value received at 30170 x 65536 ) + value received at 30171)
1.4 Internal Communication Error interpretation from the value received at address
30187
If value received at this address is 0, the internal communication between the MODBUS
RTU to MODBUS TCP/IP convertor is OK.
If the value received at this address is 1 and rest all values returned are zero then there is
a problem with the internal communication. Contact factory.
Table 1.1 :- Multiplying Factor Interpretation for Flow rate from the Value received
at MODBUS address 30170
Sr. No. Value Returned Multiplying Factor For Flow rate
1 0 1
2 1 10
3 2 100
4 3 1000
Table 1.2 :- D.P. Position Interpretation for Flow Rate from the Value received at
MODBUS address 30173
Sr. No. Value Returned D. P. Position
1 0 0000.
2 1 000.0
3 2 00.00
4 3 0.000
Table 1.3:- D.P. Position Interpretation for Total Flow from the Value received at
MODBUS address 30174
Sr. No. Value Returned D. P. Position
1 0 000000.
2 1 00000.0
3 2 0000.00
Table 1.5 :- Engineering Unit Interpretation for Flow Rate from the Value received at
MODBUS address 30183
Sr. No. Value Returned Engineering Unit
1 0 m3 / hr
2 1 LPM
3 2 LPS
4 3 USGPM
Table 1.6 :- Engineering Unit Interpretation for Total Flow from the Value received at
MODBUS address 30184
Sr. No. Value Returned Engineering Unit
1 0 m3
2 1 LITRE
3 2 X10LTR
4 3 X100LTR
5 4 KILOLTR
6 5 GALLON
7 6 X10GAL
8 7 X100GAL
Table 1.7 :- Engineering Unit Interpretation for Power from the Value received at
MODBUS address 30185
Sr. No. Value Returned Engineering Unit
1 0 KW
2 1 MBTU/HR
3 2 TR
Table 1.8 :- Engineering Unit Interpretation for Temperature from the Value
received at MODBUS address 30186
Sr. No. Value Returned Engineering Unit
1 0 ºC
2 1 ºF
Enter ‘Admin’ as login id and ‘Manas123’ as password to login, the following page
Opens
The current settings are shown in the box just below the respective setting and the
user can modify the parameters as per desired.Set the RTC date time, MODBUS ID,