EEE Ch. 4
EEE Ch. 4
ELEN 0372
Chapter (4)
Overhead Transmission Line Parameters
Introduction
The purpose of a transmission system is to transfer electric energy
from generating units at various locations to the distribution system
which ultimately supplies the load.
The electric parameters of overhead transmission lines are
resistance, inductance, capacitance, and conductance. These
parameters can be determined from the specifications for the
conductors, and from the geometric arrangements of the conductors.
where the power is in watts and I is the rms current in the conductor in
amperes.
2
1
The effective resistance is equal to the DC resistance of the
conductor only if the distribution of current throughout the
conductor is uniform.
DC resistance is given by the formula:
ℓ
R
A
where is the resistivity at 20o C.
ℓ is the length of the conductor.
A is the cross-sectional area of the conductor.
The International System of Units (SI system), ℓ is in meter, A in
square meter and in ohm-meter. The conductor resistance is
affected by three factors: frequency, spiraling and temperature.
For DC, the current distribution is uniform throughout the
conductor cross section. However, for AC, the current distribution
is nonuniform. As frequency increases, the current tends to crowd
toward the conductor surface, with smaller current density at the
conductor center.
3
2
Spiraling causes the stranded conductor length to be more than the
given conductor length. This results in a higher resistance than the
calculated value. The conductor resistance increases as temperature
increases.
The inductance and capacitance are because of magnetic and electric
fields around the conductor, respectively, as shown in figure 1.
The lines of magnetic flux form closed loops linking the circuit,
and the lines of' electric flux originate on the positive charges on
one conductor and terminate on the negative charges the other
conductor.
Variations of the current in the conductors causes a change in the
number of lines of magnetic flux linking the circuit.
Any change in the flux linking a circuit induces a voltage in the
circuit which is proportional to the rate of change of flux.
The inductance of the circuit relates the voltage induced by
changing flux to the rate of change of current.
The capacitance which exists between the conductors is defined as
the charge on the conductors per unit of potential difference
between them. The capacitance exists between conductors or
between conductors and the ground.
Conductance accounts for leakage currents flowing across
insulators and ionized pathways in the air. Since the leakage
currents are negligible compared to the current flowing in the
transmission lines, the conductance is usually neglected.
6
3
Overhead transmission lines consists of conductors, insulators and
usually shield wires. Transmission lines are suspended by towers
made of steel, wood or reinforced concrete with its own right-of-way.
4
Conductors
In the early days of the transmission of electric power, conductors
were usually made of copper, but aluminum conductors have
completely replaced copper for overhead lines because of the much
lower cost and lighter weight of an aluminum conductor compared
with a copper conductor of the same resistance.
The fact that an aluminum conductor has a larger diameter than a
copper conductor of the same resistance is also an advantage.
With a larger diameter, there is a lower electric field at the
conductor surface and less tendency to ionize the air around the
conductor “corona”.
Stranded conductors are easier to manufacture, since larger
conductor sizes can be obtained by simply adding successive layers
of strands. Stranded conductors are also easier to handle and more
flexible than solid conductors, especially in larger sizes. For
purposes of heat dissipation, overhead transmission-line conductors
are bare (no insulating cover).
9
5
Corona in Overhead Transmission Lines
Corona occurs when the surface electric field of a conductor exceeds
the dielectric strength of the surrounding air (30 kV/cm during fair
weather), producing ionization in the area close to the conductor,
with consequent corona losses, audible noise, and radio interference.
Corona is a function of conductor diameter, line configuration, and
conductor surface condition, physical state of the atmosphere. The
following are the factors upon which corona depends :
(i) Atmosphere
As corona is formed due to ionization of air surrounding the
conductors, therefore, it is affected by the physical state of
atmosphere. Corona losses under rain or snow, for instance, are much
higher than in dry weather.
12
6
In high-voltage overhead transmission lines, it is preferable to use
more than one conductor per phase (bundle conductor). Bundling
increases the effective radius of the conductor and reduces the
electric field and corona at the conductor surface. Another
important advantage of bundling is reduced line inductance.
The bundle conductor consists of two, three or four sub-conductors
as shown in figure (3).
Spacers made of steel or aluminum bars are used to maintain the
distance between bundle conductors along the line.
14
7
Insulators
The transmission line conductors must be properly insulated
from towers with the help of insulators to prevent any leakage current
from conductors to earth. In general, the insulators should have the
following desirable properties :
(i) High mechanical strength.
(ii) High electrical resistance of insulator material.
(iii) High dielectric strength.
(iv)The insulator material should be non-porous, free from impurities
and cracks.
The most used material for insulators of overhead line is porcelain but
glass and special composition materials are also used to a limited
extent.
There are several types of insulators but the most used are pin type,
suspension type.
15
Pin type
Suspension type
Shield Wires
Shield wires locate above the phase conductors to protect them against
lightning. They are much smaller cross section than the phase
conductors. The number and location of the shield wires are selected so
that almost all lightning strokes terminate on the shield wires rather
than on the phase conductors. Shield wires are grounded to the tower.
16
8
(a) Tension Insulators (b) Suspension insulators
17
18
9
Vibration Dampers
19
D
L1 2 10 7 ln [H/m]
r1 '
The inductance of the second conductor per-unit length is
D
L 2 2 10 7 ln [H/m]
r2 '
where r1' = 0.7788 r1.
r2' = 0.7788 r2.
D is the distance between the two conductors.
20
10
Note that the calculated inductance consists of self inductance of
the conductor and mutual inductance between the conductors.
If r1 = r2 = r, then
D
L 4 10 7 ln [H/m]
r'
21
22
11
(B) Unsymmetrical Spacing
Practical transmission line can not maintain symmetrical spacing of
conductors because of construction considerations. When the
conductors of a three-phase transmission line are not spaced
equilaterally, the problem of finding the inductance becomes more
difficult.
In order that voltage drops are equal in all conductors, the positions of
the conductors are interchanged at regular intervals along the
transmission line. Such an exchange of positions is known as
transposition. The effect of transposition is that each conductor has the
same average inductance. In a transposed system, each phase conductor
occupies the location of the other two phases for one-third of the total
line length as shown in Figure (3).
24
12
Average inductance per phase is given by:
D eq
L 2 10 7 ln H/m
r'
where Deq is the geometric mean of the three spacings of the
three-phase line.
D eq 3 D ab D ac D bc
25
13
Geometric Mean Radius (GMR)
This is the radius of a fictitious conductor assumed to have no internal
flux but with the same inductance as the actual bundled conductor.
GMR is also called self geometric mean distance, Ds. If the conductor
consists of n sub-conductors, the GMR is given by:
GMR n (d11d12 d13 ....d1n )(d 21.d 22 ....d 2 n )......(d n1.d n 2 .....d nn )
2
GMD mn' (Daa'D ab' ...Dan' )(Dba'D bb' ...D bn' ).....(Dma'D mb' .....D mn' )
28
14
Example (1):
A single-phase transmission line 35 km long consists of two solid
round conductors, each having a diameter of 0.9 cm. The conductor
spacing is 2.5 m. Calculate the total inductance of the transmission line.
Solution:
GMR for a solid conductor is
0.9
r' 0.7788 0.35 cm
2
The inductance of the transmission line is
D 250
L 4 10 7 ln 4 10 7 ln 26.3 10 7 H/m
r' 0.35
29
Example (2):
A single-phase transmission line is composed of two bundled
conductors. Conductor A consists of three 0.25 cm radius conductors,
while conductor B consists of two 0.5 cm radius conductor. Find
inductance for each bundled conductor, and inductance of the
transmission line in H/m.
Conductor B
Conductor A
30
15
Solution:
D D 9 m
aa' bb'
D D D 62 92 117 m
ab' ba' cb'
D 2 2
12 9 15 m
ca'
D 6D D D D D D 10.743 m
m aa' ab' ba' bb' ca' cb'
31
L L A L B 14.715 10 7 H/m
32
16
Example (3):
One conductor of a single-phase transmission line is composed of
three solid 0.5 cm radius wires. The return conductor is
composed of two solid 2.5 cm radius wires. Find the inductance
of the complete transmission line in mH/km.
Solution:
Geometric mean distance:
33
34
17
Example (4):
Three-phase 60 Hz transmission line has a flat horizontal
configuration. Each sub-conductor of the bundled conductor has
GMR = 1.42 cm. Find the inductive reactance in /km per phase
for d = 45 cm
Figure (4)
Solution:
D s 4 1.42 45 1.42 45 8 cm
35
36
18
Example (5):
Calculate the inductive reactance in /km per phase of a bundled
60 Hz three-phase transmission line having three subconductors per
bundled conductor. Each sub-conductor has GMR =1.18 cm with
45 cm between subconductors. The spacing between bundled
conductor centers is 9, 9, and 18 m.
D12 = 9 m D23 = 9 m
D13 = 18 m
Solution:
GMR for a bundled conductor is
37
38
19
Capacitance of Overhead Transmission Line
The conductors of overhead transmission-lines are charged, and
there is a potential difference between the conductors and between
the conductors and the ground. Therefore, there is capacitance
between the conductors and between the conductors and the
ground. The basic equation for calculation of the capacitance is the
definition of the capacitance as the ratio of the charge and the
potential difference between the charged conductors. For
transmission lines, the capacitance per unit length is required
q
C
V
F / m
where q is the charge per unit length in C/m.
V is the potential difference between the conductors or a
conductor and ground.
39
20
If the transmission line is supplied by a transformer having a
grounded center tap, the potential difference between each
conductor and ground is half the potential difference between the
two conductors. Therefore, it is convenient to define a capacitance
between each conductor and a neutral. The capacitance from
conductor a to point n is Can and is the same as the capacitance
from conductor b to n, Cbn.
41
If C an C bn
2
C an C
Then C ab an
2C an 2
C an C bn 2C ab
2 o
Can [ F / m]
D
ln
r
42
21
(2) Capacitance of Balanced Three Phase Line (Solid Conductor)
(A) Symmetrical Spacing
The capacitance per phase to neutral for symmetrical spacing three-
phase lines is
2 o
Can [ F / m]
D
ln
r
43
22
(1) Capacitance of a Single-phase Two-wire Line (Bundled Conductor)
2πεo πε o
C an [F/m] C ab [F/m]
D D
ln m ln m
Ds Ds
(2) Capacitance of Balanced Three Phase Line (Bundled Conductor)
(A) Symmetrical Spacing
Capacitance of transmission lines per phase to neutral is given by:
2 πε o
Can [F/m]
D
ln m
Ds
(B) Unsymmetrical Spacing
Capacitance of transmission lines per phase to neutral is given by:
2πεo
C an [F/m]
D
ln eq
Ds
45
Example (6):
A three-phase overhead transmission line has its conductors arranged
at the corners of an equilateral triangle of 2 m side. The diameter of
each conductor is 1.25 cm. Calculate the capacitance per phase to
neutral in μF/km.
Solution:
The conductor radius is
1.25
r 0.625 cm
2
The capacitance per phase to neutral is
2πεo 2π 8.854 10 12
C an 9.644 10 12 [F/m]
D 200
ln ln
r 0.625
9.644 10 3 [ F / km]
46
23
Example (7):
A three-phase 50 Hz, 66 kV overhead transmission line has a
horizontal arrangement as shown in Figure (3). The conductor
diameter is 1.25 cm. If the line length is 100 km, calculate:
(a) The capacitance per phase to neutral.
(b) The charging current per phase.
Assuming complete transposition of the line.
Figure (3)
Solution:
The conductor radius is
1.25
r 0.625 cm
2
D eq 3 D ab D bc D ca 3 2 2.5 4.5 2.82 m 282 cm
47
48
24
Example (8):
Three-phase 60 Hz transmission line has a flat horizontal
configuration. Each sub-conductor of the bundled conductor has a
radius of 2 cm. Find the capacitive reactance in .km per phase
for d = 45 cm
Figure (4)
Solution:
D s 4 2 45 2 45 9.487 cm
49
50
25
Example (9):
Calculate the capacitance per phase to neutral in μF/km of a
bundled 60 Hz three-phase transmission line having three
subconductors per bundled conductor. Each sub-conductor has a
radius of 1.5 cm with 45 cm between subconductors. The spacing
between bundled conductor centers is 9, 9, and 18 m.
D12 = 9 m D23 = 9 m
D13 = 18 m
Solution:
GMR for a bundled conductor is
51
D eq 3 9 9 18 11.34 m 1134 cm
52
26