2180903 Pspd Lab Manual
2180903 Pspd Lab Manual
2180903 Pspd Lab Manual
NAME:
ENROLLMENT NO:
BATCH NO:
YEAR:
CERTIFICATE
Date of Submission:-
1.
9
Laboratory Experiment – 1
Requirement:
You have to install a Lab VIEW Run time Engine on your computer to run the exe file in order to
perform the experiment.
Objective of Experiment:
This experiment gives the vision by which we can see the voltage wave travelling toward the
load, voltage reflected wave from the load end and the voltage standing wave, by which we can
understand the concept behind the transmission of analog signal in the lossless transmission line.
In a transmission-line operating at high frequency, due to impedance mismatch between the
source, transmission-line, and load there is a loss of energy transfer from source to load. The
effects due to mismatch of the load and characteristic impedance can be studied here in frequency
domain. This can be done by sending a wave on the line with its load mismatched and watching
the reflected wave along with voltage standing wave over transmission line. By varying various
parameters of transmission line their effects can be visualized accordingly.
Theory:
Transmission line: It is a device designed to guide the electrical energy from one point to
another. It is used, for example, to transfer the RF energy from source to antenna. For efficient
point-to-point transmission of power and information the source energy must be directed or
guided. Transmission line that consists of two or more conductors may support transverse
electromagnetic (TEM) waves, characterized by the lack of longitudinal field components. The
TEM mode of guided waves is one in which E and H are perpendicular to each other and both are
Transverse to the direction of propagation along the guiding line. TEM waves have uniquely
defined voltage, current, and characteristic impedance.
The three most common types of guiding structures that support TEM waves are:
Coaxial transmission line: This type of transmission line consists of an inner conductor and
outer conductor separated by a dielectric medium. This structure has the important advantage of
confining the electric and magnetic fields entirely within the dielectric region. No stray fields are
usually generated inside a coaxial transmission line, and little external interference is coupled into
the line.
In this experiment at the generator terminal we have AC voltage source, and transmission line is
( ) (1)
( ) (2)
Where,
(3)
Standing wave ratio (SWR): Standing wave ratio (SWR) is defined as the ratio of the maximum
to the minimum voltages along a finite, terminated transmission-line.
Procedure: Please download the files shown on the left to perform the actual experiment. The
exe file is the Lab VIEW file that will run on Lab VIEW Run time Engine
Step 1: Set the incident voltage ( ) in volts and frequency (f) of incident wave in GHz.
Step 2: Set the number of cycles, number of points in distance scale and location of point
(in meter) at which voltage has to be measured w.r.t. time.
Step 3: Enter the values of properties of transmission-line i.e. length of transmission line (l) in
meter, characteristic impedance of transmission line ( ) in Ohm and relative dielectric constant
(epsilon) of transmission line.
Step 4: Enter the value of load resistance ( ) in Ohm.
Step 5: In the output you will see three plots first one showing the incident voltage travelling
along transmission line, second plot shows the reflected voltage wave travelling along
transmission line and the third plot shows the voltage standing wave along the transmission line.
Step 6: Run the VI to see the results. In case, you wish to see the result for different values then
Click STOP and repeat steps 1 – 5 before running the program again.
Task:
1. By specifying source and load values and giving the properties of transmission line, observe
the travelling wave, reflected voltage wave and standing wave ratio.
2. Observe the waves in case of matched and mismatched impedance.
3. Observe the waves for short circuited and open circuited transmission line by specifying ―0‖
value to load reactance and for load resistance specify the value ―0‖ for short circuited and ―inf‖
for open circuited transmission line.
Summary: This experiment gives a vision to see the high frequency voltage wave travelling
in the transmission-line. This experiment helps in building concept of waves travelling in
transmission line, reflected waves from the load end and the standing wave generated in case of
impedance mismatch.
Laboratory Experiment – 2
Aim of Experiment: Visit of substation and draw its lay out plan
Objective: To see firsthand apparatus that we will be studying in this course and learn about their
role in operation and protection of power systems.
Report:
Write a few sentences about each apparatus you saw, include its photograph if you were allowed
to take it (of course with permission and always reference the source), and state its role, as you
understand it at this stage in your study, in operation and protection of power systems. State the
approximate physical size and the electric ratings in terms of voltage, current, power, kVA etc.
These apparatus may include transmission line towers and their structure, transmission line
conductors, their size and bundling, transformers, circuit breakers, surge arresters, relays, line
traps for line-carrier communication, microwave towers, bus bars and their arrangement,
substation grounding, battery backup as uninterruptible power supplies and so on.
Laboratory Experiment – 3
Tasks
1. Consider a 345-kV transmission line consists of three-conductor-flat towers shown in Figure. This
transmission system consists of a single-conductor per phase, which is a Bluebird ACSR conductor
with a diameter of 1.762 inches. The PSCAD/EMTDC file for this 345-kV single-conductor line is
Line Parameters .psc , which is located in this folder. Double click on it to open it and execute it to
calculate line constants. Compare the results with those given in Example
3. A 200 km long 345-kV line has the parameters given in the Table below. Neglect the resistance.
Measure the reactive power at both ends under the following two levels of loading if both ends are
held at the voltages of 1 per unit: (a) 1.5 times SIL, and (b) 0.75 times SIL. The PSCAD/EMTDC file
for modeling this transmission line is Transmission Line. psc , which is located in this folder.
Double click on it to open it and execute it.
Table
Task 1:
1) Take T-Line i.e. transmission line from toolbar.
2) Double click on T-Line, in the configuration parameters dialog select Termination style as Direct
connection
3) Set other parameters as per requirement
4) Click on edit to edit tower and conductor data
5) Select and delete ‗frequency dependent model‘block. Right click on blank area and select
Bergeron model
6) Again right click on blank area to select type of tower. There are 12 tower types to choose from
7) Double click on Tower structure to edit the data as below
Component Properties
Line constants 3 conductor Tower Data: Here you can edit Height of conductors, Horizontal
flat tower Spacing between conductors etc. Also you can specify no. of ground
wires and transposed lines or untransposed lines.
Aim of Experiment: Survey of rural electrification and draw single line diagram.
Report :
Allow activities to occur after daylight hours, including education. In impoverished and
undeveloped areas, small amounts of electricity can free large amounts of human time and
labor. In the poorest areas, people carry water and fuel by hand, their food storage may be
limited, and their activity is limited to daylight hours.
Reduce isolation through telecoms
Improve safety with the implementation of street lighting, lit road signs.
Improve healthcare by electrifying remote rural clinics.
Reduces the need for candles and kerosene lamps with their inherent fire safety risks and
improves indoor air quality.
Improve productivity, through the use of electricity for irrigation, crop processing, and other
activities.
304 million Indians (24 percent of the population) are still without electricity. [17] India has
20% of the world's population but 40% of the world's population without electricity.[18]Rural
areas in India are electrified non-uniformly, with richer states being able to provide a
majority of the villages with power while poorer states still struggling to do so. The Rural
Electrification Corporation Limited was formed to specifically address the issue of
providing electricity in all the villages across the country. Poverty, lack of resources, lack
of political will, poor planning, and electricity theft are some of the major causes which
has left many villages in India without electricity, while urban areas have enjoyed growth
in electricity consumption and capacity. The central government is increasingly trying to
improve the dire conditions by investing heavily in bio-gas, solar as well as wind
energy.Programs such as The JNN solar mission, Pradhan Mantri Gram Vidyut yojna to
fasten the pace of electrification and diversify the procedure.The work is also on-going for
reducing wastage, providing better equipments and improving the overall infrastructure
for electrical transmissions in villages. Currently, more than 95% of villages in India have
been electrified with a further goal of providing complete electrification by 2020. Northern
and North-Eastern states in India are lagging behind the national average bringing the
numbers down, primarily due to inefficient state governments and lack of economic
resources; these states are currently the focus of many NGOs as well as state programs.
It is estimated that 1-2 GW of solar power will be required for the 1 lakh un-electrified
villages in the country, not to mention the solar power requirements of un-electrified
households of electrified villages.[19] A breakdown is provided below on the number of
states and UTs (Union Territories) that have been electrified :
Rural State/UT (Electrification rate, Unelectrified villages)
electrification rate
99.00-99.99% Himachal Pradesh (99.81%, 34), Uttar Pradesh (99.77%, 224), Uttarakhand (99.52%,
76), Rajasthan (99.26%, 332), Madhya Pradesh (99.51%, 258), Karnataka
(99.86%,39), West Bengal (99.96%, 14)
95.00-98.99% Jammu & Kashmir (98.31%, 107), Tripura (98.03%, 17), Bihar (97.46%, 993),
Chhattisgarh (96.55%, 675), Odisha (95.33%, 2210)
90.00-94.99% Jharkhand (93.98%, 1775), Assam (92.31%, 1950), Manipur (91.55%, 201), Mizoram
(94.03%, 42), Nagaland (94.14%, 82)
Theory:
Introduction:
Earth behaves as an Electrical conductor but its characteristics is that its conductivity is
variable and unpredictable. The resistance of an earth connection varies with earth’s
composition, chemical contents, moisture, temperature, season of the year, depth and
diameter of rod and other reasons. The resistance offered to AC and DC also differs
considerably. Theoretically, it is possible to calculate the resistance of any system of
earthing electrodes. However as there are too many variables such as temperatures,
season, moisture contents etc., it is usually measured in practice rather than calculated.
OBJECT OF EARTHING
The object of earthing system is to provide a surface under and around a station, which
shall be at a uniform potential (nearly zero or absolute earth potential). This Earth
surface should be as nearly as possible to the system. This is in order to ensure that, all
parts of apparatus other than live parts and attending personnel shall be at earth
potential at all times. Due to this there exists no potential difference, which could cause
shock or injury to a person, when short circuit or any other type of abnormalities takes
place
Pipe Earthing
Pipe earthing is the best form of earthing and is very cheap in cost. In this method of
earthing, a galvanized and perforated pipe of approved length and diameter is placed up
right in a permanently wet soil.
The size of the pipe depends upon the current to be carried and the type of the soil.
Usually the pipe used for this purpose is of diameter 38 mm and 2.5 meters in length for
ordinary soil or of greater length in case of dry and rocky soil. The depth at which the
pipe must be buried depends upon the moisture of the ground. The pipe is placed at a
depth of 3.75 meters (minimum). The pipe is provided with a tapered casing at the lower
end in order to facilitate the driving. The pipe at the bottom is surrounded by broken
pieces of coke to increase the effective area of the earth and to the earth and to
decrease the earth resistance respectively. Another pipe of 19 mm diameter and
minimum length 1.25 meter is connected at the top to G I pipe through reducing socket.
In our country in summer the moisture in the soil decrease which cause increase in earth
resistance. So a cement concrete work, is done in order to keep the water arrangement
accessible, and in summer to have an effective earth, 3 or 4 buckets of water are put
through the funnel connected to 19 mm diameter pipe, which is further connected to G I
pipe.
The earth wire (either G I wire or G I Strip of sufficient cross section to carry faulty
current safely) is carried in a G I pipe of diameter 13 mm at a depth of about 60 mm
from the ground).
Care should be taken that earth wire is well protected from mechanical injury, when it is
carried over from one machine to another.
Plate Earthing
A small masonry brick wall enclosure with a cast iron cover on top or an R C C pipe round
the earth plate is provided to facilitate its identification and for carrying out periodical
inspection and tests.
For smaller installations G I pipe earthing is used and for larger stations and transmission
lines, where the fault current, likely to be high, plate earthing is used.
Laboratory Experiment – 6
Objectives: 1. To include an HVDC transmission line and see its effect on power transfer on other
transmission line.
2. To understand the operating principle of 12-pulse thyristor converters used in HVDC
transmission systems.
1. The transmission line between buses 1 and 3 is an HVDC line, as described in the
PowerWorld file PowerFlow_HVDCline.pwb (see video clip# 8), which is located in this
Folder. Double click on this file or open it through PowerWorld. Look at various
characteristics of this HVDC system by examining its parameters; see dialog boxes below.
Compare this case with that in Example 5-4 for the various bus voltages and the power
flow on various lines due to this HVDC line. Change the set point from 200 MW to 300
MW and then to 400 MW. Explaing what you see.
4. By using the formula (7-12) and (7-13), for different firing angles, calculate the DC
voltage and match with the value obtained from the waveform. For Rectifier: w*Ls = 13.6791
ohm, VLL=213 kV, Id= Obtain from simulation For Inverter: w*Ls=13.1843 ohm, VLL=207
kV, Id= Obtain from simulation.
5. Obtain the waveforms of the input and output currents for both the transformers in rectifier
and inverter. Observe the phase shift between the primary and secondary of Wye-Delta
transformer. Explain what you see.
Theory :
Cables
A cable‘s insulation holds back the electrons; the insulation allows cables with a small
overall diameter to support a conductor at significant voltage. A 0.175-in. (4.5-mm)
thick polymer cable is designed to support just over 8 kV continuously; that‘s an
average stress of just under 50 kV per in. (20 kV/ cm). In addition to handling
significant voltage stress, insulation must withstand high temperatures during heavy
loading and during short circuits and must be flexible enough to work with. For much
of the 20th century, paper insulation dominated underground application, particularly
PILC cables. The last 30 years of the 20th century saw the rise of polymer-insulated
cables, polyethylene-based insulations starting with high-molecular weight
polyethylene (HMWPE), then cross-linked polyethylene (XLPE), then tree-retardant
XLPE and also ethylene-propylene rubber (EPR) compounds.
Some of the key properties of cable insulation are:
Dielectric constant (e, also called permittivity) — This determines the cable‘s capacitance:
the dielectric constant is the ratio of the capacitance with the insulation material to the
capacitance of the same configuration in free space. Cables with higher capacitance draw
more charging current.
Volume resistivity — Current leakage through the insulation is a function of the
insulation‘s dc resistivity. Resistivity decreases as temperature increases. Modern
insulation has such high resistivity that very little resistive current passes from the
conductor through the insulation.
Dielectric losses — Like a capacitor, a cable has dielectric losses. These losses are
due to dipole movements within the polymer or by the movement of charge carriers
within the insulation. Dielectric losses contribute to a cable‘s resistive leakage
current. Dielectric losses increase with frequency and temperature and with operating
voltage.
Dissipation factor (also referred to as the loss angle, loss tangent, tan d, and
approximate power factor) -- The dissipation factor is the ratio of the resistive current
drawn by the cable to the capacitive current drawn (IR/IX). Because the leakage
current is normally low, the dissipation factor is approximately the same as the power
factor:
Pf = = Dissipation Factor
√
Polyethylene (PE). Most modern cables have polymer insulation extruded around the
conductor — either polyethylene derivatives or ethylene-propylene properties. Polyethylene
is a tough, inexpensive polymer with good electrical properties. Most distribution cables
made since 1970 are based on some variation of polyethylene. Polyethylene is an ethylene
polymer, a long string or chain of connected molecules. In polyethylene, some of the polymer
chains align in crystalline regions, which give strength and moisture resistance to the
material. Other regions have nonaligned polymer chains — these amorphous regions give the
material flexibility but are permeable to gas and moisture and are where impurities locate.
Polyethylene is a thermoplastic. When heated and softened, the polymer chains break apart
(becoming completely amorphous); as it cools, the crystalline regions reform, and the
material returns to its original state. Polyethylene naturally has high density and excellent
electrical properties with a volume resistivity of greater than 1014 W-m and an impulse
insulation strength of over 2700 V/mil.
Within each voltage rating, more than one insulation thickness is available. Standards specify
three levels of cable insulation based on how the cables are applied. The main factor is
grounding and ability to clear line-to-ground faults in order to limit the overvoltage on the
unfaulted phases. The standard levels are 100 percent level — Allowed where line-to-ground
faults can be cleared quickly (at least within one minute); normally appropriate for grounded
circuits 133 percent level —Where line-to-ground faults can be cleared within one hour;
normally can be used on ungrounded circuits
Conductors