OptiCORE LS-1628u Installation Guide
OptiCORE LS-1628u Installation Guide
Installation Guide
Verify that you have the most current version of this document from the OEM® Partner Community website.
Important changes are listed in Document revision history at the end of this document.
A Carrier Company
© 2022 OEMCtrl. All rights reserved.
Contents
What is the OptiCORE™ LS-1628u? ........................................................................................................................... 1
Critical Product Announcement .........................................................................................................................2
Specifications ........................................................................................................................................................3
Zone sensors .........................................................................................................................................................6
Touchscreen devices ............................................................................................................................................6
To mount the LS-1628u .............................................................................................................................................. 7
To attach LS-XP expanders ......................................................................................................................................... 9
LS-XP expander configurations using AC power ........................................................................................... 11
LS-XP expander configurations using DC power ........................................................................................... 13
Wiring for power ........................................................................................................................................................ 15
To wire for power ............................................................................................................................................... 15
Addressing the LS-1628u ......................................................................................................................................... 16
To set up autobaud ............................................................................................................................................ 17
To set the IP address ......................................................................................................................................... 18
To set the Port S1 address and baud rate ..................................................................................................... 20
To set the Port S2 address and baud rate ..................................................................................................... 20
Wiring for communications ...................................................................................................................................... 21
Wiring specifications ......................................................................................................................................... 21
To connect the LS-1628u to the Ethernet ...................................................................................................... 22
To wire to a BACnet/ARCNET network ........................................................................................................... 22
To wire to a BACnet MS/TP network .............................................................................................................. 23
To wire a third-party device .............................................................................................................................. 23
Wiring devices to the LS-1628u's Rnet port ............................................................................................................ 24
Wiring devices to the LS-1628u's Act Net port ....................................................................................................... 25
Wiring inputs and outputs......................................................................................................................................... 27
Inputs ................................................................................................................................................................... 27
Outputs ................................................................................................................................................................ 28
Wiring specifications ......................................................................................................................................... 29
To wire inputs and outputs ............................................................................................................................... 30
To adjust input and output properties ..................................................................................................................... 33
Input values ........................................................................................................................................................ 34
Output values ..................................................................................................................................................... 35
Resolution values .............................................................................................................................................. 35
Offset/Polarity values ....................................................................................................................................... 36
To use an output's Hand-Auto-Off switch ....................................................................................................... 37
Downloading the LS-1628u ...................................................................................................................................... 38
To download from the WebCTRL® interface................................................................................................. 38
Adjusting the LS-1628u driver properties ............................................................................................................... 39
Driver ................................................................................................................................................................... 39
Device .................................................................................................................................................................. 41
Notification Classes ........................................................................................................................................... 41
Calendars ............................................................................................................................................................ 42
Common and Specific Alarms ......................................................................................................................... 43
Custom Translation Tables ............................................................................................................................... 43
BACnet Router Properties ................................................................................................................................ 44
BACnet Firewall .................................................................................................................................................. 45
Network Diagnostics - Statistics ...................................................................................................................... 46
Contents
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
1
What is the OptiCORE™ LS-1628u?
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
2
What is the OptiCORE™ LS-1628u?
Specifications
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
3
What is the OptiCORE™ LS-1628u?
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
4
What is the OptiCORE™ LS-1628u?
Environmental operating -40 to 158°F (-40 to 70°C), 10-95% relative humidity, non-condensing
range NOTES
• The LS-1628u is suitable for installation inside or outside the building
envelope.
• Install in a UL Listed enclosure only.
• Do not change the position of the power or End of Net switch at temperatures
below -22°F (-30C) to ensure proper operation and electrical connectivity.
Physical Fire-retardant plastic ABS, UL94-5VA
Terminal blocks and Screw-type terminal blocks.
connectors 0.2 in (5.08 mm) pitch connectors
Mounting 35mm DIN rail mounting or screw mounting
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
5
What is the OptiCORE™ LS-1628u?
Zone sensors
You can wire ZS sensors and/or a Wireless Adapter that communicates with wireless sensors to the LS-1628u's
Rnet port. You can have up to 15 ZS and/or wireless sensors.
NOTES
• A control program can use no more than 5 ZS sensors, so you must use multiple control programs if your
Rnet network has more than 5 sensors.
• ZS and wireless sensors can share the Rnet with an Equipment Touch or OptiCORE™ ET display.
Touchscreen devices
You can connect the LS-1628u to the touchscreen devices using the Rnet port or the Ethernet Service port.
Rnet port
You can wire an Equipment Touch or OptiCORE™ ET display to the LS-1628u's Rnet port to view or change the
controller's property values, schedule equipment, view trends and alarms, and more, without having to access the
system's server. The Rnet port can have one Equipment Touch or OptiCORE™ ET display, plus ZS sensors and/or a
Wireless Adapter that communicates with wireless sensors.
NOTE These touchscreen devices are not powered by the Rnet port.
• The OptiCORE™ ET display requires a 24 Vdc external power source.
• The Equipment Touch requires a 24 Vac external power source.
Ethernet port
You can connect the OptiCORE™ ET display to the LS-1628u's Ethernet Service port to view or change the
controller's property values, schedule equipment, view trends and alarms, and more, without having to access the
system's server.
NOTES
• These touchscreen devices are not powered by the Ethernet port.
• The OptiCORE™ ET display requires a 24 Vdc external power source.
CAUTION A touchscreen device can share a power supply with the OEMCtrl® controller if:
• The power source shared by the controller and Equipment Touch is AC power.
• The power source shared by the controller and OptiCORE™ ET display is DC power.
• You maintain the same polarity.
• You use the power source only for OEMCtrl® controllers.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
6
To mount the LS-1628u
2 Place the controller on the DIN rail so that the rail is in the trough on the back of the controller.
3 Push the DIN rail tabs towards the controller until you hear them click.
4 Pull gently on the controller to verify that it is locked in place.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
7
To mount the LS-1628u
Screw Mount
Leave about 2 in. (5 cm) on each side of the controller for wiring.
Insert #6 screws through the mounting tabs. Use no more than 12 in lbs. torque to secure plastic tab to mounting
surface. Use flat washers to prevent the screw head from deforming the plastic.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
8
To attach LS-XP expanders
The expanders' outputs return to their unconfigured state if they are removed from the program or the program is
deleted from the controller. Also, outputs time out and return to their unconfigured or off state after two minutes
of inactivity. The unconfigured state results in:
• Not running control programs that are due to download
• Losing power to the controller, but not the expander
NOTE This does not apply to outputs that have been locked in the WebCTRL® application.
To wire the LS-XP expander to the I/O Bus port to enable communication (AC or DC)
Use ARC156 wiring (22 AWG, low-capacitance, twisted, stranded, shielded copper wire) to wire the LS-XP expander
to the controller. Do not exceed 1000 feet (305m) total wire length for the I/O bus.
WARNING Do not apply line voltage (mains voltage) to the expander's ports and terminals.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
9
To attach LS-XP expanders
To connect the LS-XP expander to the I/O bus edge connector (DC only)
NOTE
• The following instructions assume that the controller is already mounted either on a DIN rail or using screws.
• You cannot use the I/O bus edge connector on the LS-1628u when using an AC power supply.
WARNING This connector provides power and communication. To prevent risk of shock, do not touch
the bare edge connector if the controller's power is on.
3 DIN rail mounting only—Push down and pull out the expander's DIN rail tabs shown below.
4 Slide the expander's left edge connector down onto the LS-1628u's edge connector.
5 Do one of the following:
○ DIN rail mounting—Push in the expander's center tabs towards the expander until you hear them click.
Pull gently on the expander to verify that it is locked to the DIN rail.
○ Screw mounting—Insert #6 screws through the expander's mounting holes.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
10
To attach LS-XP expanders
NOTE The controller has built-in I/O Bus network termination and must be the first device on the expander
network. Add termination to the last LS-XP expander on the network by setting I/O Bus End of Net? switch to Yes
(Up).
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
• The LS-1628u is powered by a Class 2 power source. Take appropriate isolation measures when mounting it
in a control panel where non-Class 2 circuits are present.
• OEMCtrl® controllers can share a power supply as long as you:
• Maintain the same polarity.
• Use the power supply only for OEMCtrl® controllers.
Using AC power
The controller draws 100 VA and each LS-XP expander draws 50 VA.
You can connect a maximum of nine expanders to the LS-1628u. The following images are two possible
configurations when using AC power. Many more configurations exist, depending on the size of the transformers
(50 or 100 VA) and the number of LS-XP expanders you have.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
11
To attach LS-XP expanders
The following configuration shows the maximum combination of connections using the I/O bus edge connector
and daisy-chained wiring to the I/O Bus port.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
12
To attach LS-XP expanders
NOTE The controller has built-in I/O Bus network termination and must be the first device on the expander
network. Add termination to the last LS-XP expander on the network by setting I/O Bus End of Net? switch to Yes
(Up).
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
CAUTIONS
• The LS-1628u is powered by a Class 2 power source. Take appropriate isolation measures when mounting it
in a control panel where non-Class 2 circuits are present.
• OEMCtrl® controllers can share a power supply as long as you:
• Maintain the same polarity.
• Use the power supply only for OEMCtrl® controllers.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
13
To attach LS-XP expanders
Using DC power
The controller draws 48 W and the LS-XP expander draws 12 W.
In the following image, the 100 W power supply can provide power to one LS-1628u and four expanders. The LS-
XP expanders are connected to the controller and to each other using the I/O bus edge connector that provides
power and communication. The following configuration shows a combination of connections for the maximum
number of expanders, using the edge connector and wiring to the I/O Bus port.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
14
Wiring for power
CAUTIONS
• The LS-1628u is powered by a Class 2 power source. Take appropriate isolation measures when mounting it
in a control panel where non-Class 2 circuits are present.
• OEMCtrl® controllers can share a power supply as long as you:
• Maintain the same polarity.
• Use the power supply only for OEMCtrl® controllers.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
15
Addressing the LS-1628u
1 Connect an Ethernet cable from a computer to the controller's Service Port, as shown below.
NOTE Be sure NOT to plug the cable into the Gig-E Port.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
16
Addressing the LS-1628u
See To set up the controller through the Service Port (page 55) for general information on using the controller
setup pages.
To set up autobaud
The LS-1628u can automatically receive or establish the baud rate on a serial network. When you configure a
device on the network for autobaud and then power it up, the device detects the incoming baud rate on the
network and sets its baud to match.
Autobaud does not work unless there is a device on the network, whether OEMCtrl® or third party, that has the
baud rate already set. You can manually set the baud rate on more than one device, as long as the rate is the
same for every device.
NOTES
• The received baud rate stays intact during power cycles.
• We recommend you set the baud rate manually on the router for the network.
MS/TP
MSTP Autobaud can be configured in either the:
• Service Port controller setup pages > BACnet tab > Port S1 or Port S2
or
• The WebCTRL® interface, on the Network tree, select your LS-1628u > Driver > BACnet Router
Properties > MS/TP Configuration on Port S1 or on Port S2. See BACnet Router Properties (page 44).
Modbus
Modbus Serial Autobaud can be configured in either the:
• Service Port controller setup pages > Modbus tab > Modbus RS-485 > Port Configuration
or
• The WebCTRL® interface, on the Network tree, select your LS-1628u and go to Driver > Communication
Status > Modbus Serial
NOTE See the Modbus Integration Guide.
NOTE If you set Autobaud or make other changes in the controller setup pages, you must upload the changes to
the system database the first time you access the controller in the WebCTRL® interface. This preserves those
settings when you download memory or parameters to the controller.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
17
Addressing the LS-1628u
NOTE Carefully plan your addressing scheme to avoid duplicating addresses. If third-party devices are integrated
into the system, make sure your addresses do not conflict with their addresses.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
18
Addressing the LS-1628u
1 Set the controller's three rotary switches to a unique address on the network. Set the left rotary switch to the
hundreds digit, the middle switch to the tens digit, and the right switch to the ones digit.
EXAMPLE The switches below are set to 125.
2 On the controller setup Ports tab under IP Port, select Default IP Address.
3 Click Save.
CAUTIONS
• If you are using Port S1, the rotary switches also determine that network's address. Although the ARCNET
address range is 1 to 255, the Default IP address range is 1 to 253. Setting the rotary switches to 0 will set
the Default IP address to 1. Setting the switches to 255 will set the Default IP to 253. Do not set the switches
to 254.
• If you set the Default IP address on the controller setup Ports tab and then change the rotary switches, you
must do one of the following to correct the IP address in the controller:
• Go to the controller setup Ports tab and click the Update IP Address.
• Cycle the controller's power.
You will then need to correct the IP address in SiteBuilder.
NOTE The default address is an intranet address. Data packets from this address are not routable to the Internet.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
19
Addressing the LS-1628u
You set this address on the LS-1628u's three rotary switches. Set the left rotary switch to the hundreds digit, the
middle switch to the tens digit, and the right switch to the ones digit.
CAUTION If you are using a Default IP address, the rotary switches also determine the IP address.
Modbus
For Modbus, see the Modbus Integration Guide.
Modbus
For Modbus, see the Modbus Integration Guide.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
20
Wiring for communications
Wiring specifications
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
21
Wiring for communications
NOTE If your system has controllers on different IP subnets separated by an IP router, you must configure one
controller on each subnet as a BACnet Broadcast Management Device (BBMD). Do not configure more than one
BBMD per subnet as this may cause circular routes. See "Setting up BACnet Broadcast Management Devices
(BBMDs)" in SiteBuilder or WebCTRL® Help.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
22
Wiring for communications
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
23
Wiring devices to the LS-1628u's Rnet port
NOTES
• ZS sensors, a Wireless Adapter, and an Equipment Touch can share the same Rnet.
• The Rnet communicates at a rate of 115.2 kbps.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
24
Wiring devices to the LS-1628u's Act Net port
CAUTIONS
• If the power source for the Act Net devices require a connection to earth ground, you must place it in the
same control panel as the LS-1628u controller, so that it shares a common earth ground reference, thereby
reducing the potential for ground loops.
• A remote Act Net power source, installed near the Act Net devices, should be floating (no local connection to
earth ground).
The LS-1628u provides an orange, three-pin removable screw terminal connector for the Act Net port.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
25
Wiring devices to the LS-1628u's Act Net port
The Act Net port's NC (not connected) terminal does not connect to any internal circuitry of the LS-1628u. It is
strictly for terminating wires in a daisy chain bus configuration.
NOTE Be careful to wire the Act Net port terminals on the controller to the matching terminal on the supported
device. They may not be in the same order. See example below.
The LS-1628u supports Act Net communication to the Act Net devices on a bus with a maximum length of 300
feet (91.44 meters). The bus should be wired with copper conductors of an appropriate size (18 AWG or larger) to
compensate for voltage drop and ensure that bus voltage does not drop below 19.2 Vac or 21.6 Vdc..
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
26
Wiring inputs and outputs
Inputs
The LS-1628u has inputs that accept the following signal types.
WARNING Do not apply voltage to any input configured for 0-20 mA as this could damage the expander.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
27
Wiring inputs and outputs
Outputs
The LS-1628u's universal outputs can be set as analog or binary on their two DIP switches.
Analog outputs
Outputs set up as analog can be used for:
• 0-10 Vdc devices
• 0-20 mA devices
WARNING Do not apply voltage to any output whose DIP switch is set to Analog.
Binary outputs
The outputs have a built-in relay and provide a dry contact so an external voltage source must be wired to one of
the two terminals.
Outputs set up as binary can be used to switch external devices and relays up to 1A, 30 Vac/Vdc.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
28
Wiring inputs and outputs
Wiring specifications
Input wiring
Input Maximum length Minimum gauge Shielding
Thermistor 1000 feet 22 AWG Shielded
Dry contact (305 meters)
0–5 Vdc 1000 feet 26 AWG Shielded
0–10 Vdc (305 meters)
0–20 mA 3000 feet 26 AWG Shielded or
(914 meters) unshielded
RTD 100 feet 22 AWG Shielded
(30 meters)
NOTES
• OEMCtrl® recommends use of an external current transducer between an RTD and the LS-1628u to improve
accuracy and resolution.
• RTD inputs require either sensor calibration or an estimated offset correction for wiring resistance. See Offset
and Polarity values (page 36).
Output wiring
To size output wiring, consider the following:
• Total loop distance from the controller to the controlled device
NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length.
• Acceptable voltage drop in the wire from the controller to the controlled device
• Resistance (Ohms) of the chosen wire gauge
• Maximum current (Amps) the controlled device requires to operate
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
29
Wiring inputs and outputs
WARNING Do not apply line voltage (mains voltage) to the controller's ports and terminals.
The input terminals are arranged vertically. The ground (-) is below the input terminal (+). Allow .75 in. (19 mm)
extra wire length for the top (+) screw terminal than for the (-) bottom.
CAUTIONS
○ Do not allow more than .125 inch (.3 cm) bare communication wire to protrude.
.125 in.
(.3 cm)
Correct
Incorrect
Incorrect
○ If bare communication wire contacts the cable's foil shield, shield wire, or a metal surface other than the
terminal block, communications may fail.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
30
Wiring inputs and outputs
1 Verify that the LS-1628u's power and communications connections work properly.
2 Turn off the LS-1628u's power.
3 Connect the input wiring to the UI screw terminals on the LS-1628u.
WARNING Do not apply voltage to any input configured for 0-20 mA as this could damage the
expander.
NOTE Connect the shield wire to the – terminal with the ground wire. Do not connect the shield wire at the
other end of the cable as this will cause a ground loop error.
10 kOhm +
thermistor
Any input
-
Dry +
Any input
contact -
1 kOhm +
Any input
RTD
-
0-5 Vdc,
V+ 0-10 Vdc, Out
2 wire or +
4-20 mA Any input
n/c -
0-5 Vdc, Out
V+ 0-10 Vdc, +
3 wire Any input
or Gnd
4-20 mA -
0-5 Vdc,
V+ 0-10 Vdc, Out
2 wire or +
4-20 mA Any input
n/c -
0-5 Vdc, Out +
V+ 0-10 Vdc,
3 wire or Any input
Gnd
4-20 mA -
V+ Out +
4 wir e 0-5 Vdc, +
0-10 Vdc, Any input
Gnd or Out -
4-20 mA -
24 Vdc
connector
NOTE For a loop-powered 4-20 mA sensor, wire the sensor's positive terminal to the + terminal on the LS-
1628u's 24 Vdc connector. Wire the sensor's negative terminal to an input's + terminal.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
31
Wiring inputs and outputs
4 Connect binary and analog output wiring to the UO screw terminals on the LS-1628u and to the controlled
device. Connect the ground wire to the UO's – terminal.
WARNING Do not apply voltage to any output whose DIP switch is set to Analog.
– Gnd
- Coil: 24 Vac/Vdc, 1 A max.
Any UO 0-1 0 V
+
+
2-wire -
Any UO
Gnd +
- –
24 Vac/Vdc
Any UO 0-1 0 V
+ Hot
+
3-wire
- – Hot
Any UO 0-20 mA
+ + Gnd
4-wire
5 Set each output's two DIP switches to the appropriate settings for the type of device wired to the output.
CAUTION Outputs are set to Binary in the factory. To avoid damage to the controller, use a voltmeter to
verify there is no voltage on the + and – terminals before setting the DIP switch to Analog.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
32
To adjust input and output properties
1 In the WebCTRL® Geographic tree, select the equipment controlled by the LS-1628u.
2 On the Properties page, select the I/O Points tab.
3 In each point's Num field, type the number of the controller's corresponding input or output. For example, if
you use UO1 on the LS-1628u for the point Pump S/S, type 1 in the Num field for Pump S/S.
NOTES
• Exp (expander number) is 00 for the LS-1628u.
• Do not assign the same output number to more than one point.
4 For expander points, type the point's rotary switch address in the Exp field and the number of the expander's
corresponding input or output in the Num field.
EXAMPLE If UO-01 on the expander (which has a rotary switch address of 5) is used for the point Fan S/S,
enter 5:1 in the Exp:Num column for Fan S/S.
5 Enter the appropriate values for each input and output in the remaining columns. See Input values, Output
values, Resolution values and Offset/Polarity values below.
CAUTION Do not assign two input microblocks to the same physical input using Dry Contact in one and
Binary Input in the other. This results in faulty behavior.
6 If you have not performed the initial download to the attached controller, you must download now to verify
inputs and outputs.
7 To verify each input's operation, force each sensor to a known value, then compare it to the Value shown on
the Properties page on the I/O Points tab.
8 To verify each output's operation, lock each output to a known condition on the I/O Points tab, then verify
that the equipment operates correctly.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
33
To adjust input and output properties
Input values
CAUTION Do not assign two input microblocks to the same physical input using Dry Contact in one and
Binary Input in the other. This results in faulty behavior. 5
1 The sensor reads a value and sends a corresponding signal (Volt or mA) to the LS-1628u's physical input. The
Analog Input microblock uses the Min and Max values to linearly translate the signal into the engineering value
used in subsequent control logic. For example, set Min to 0 and Max to 10 for a 4–20 mA sensor that measures
velocity from 0.0 to 10.0 inches/second so that when the input reads 4 mA, the microblock outputs a value of
0. Similarly, when the input reads 8 mA, the microblock outputs a value of 2.5.
2 You can set up a custom translation table on the driver's Custom Translation Tables pages in the WebCTRL®
interface.
3 The control program must have one Pulse to Analog Input microblock for each pulse counting input.
4 To improve the accuracy for RTD sensors used with long cables, see Offset/Polarity values (page 36).
5 Binary Input and Dry Contact input types are not interchangeable. Setting an input to Dry Contact applies a
wetting voltage to sense a dry contact. Setting an input to Binary Input will not apply a wetting voltage.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
34
To adjust input and output properties
Output values
Resolution values
Resolution is not particular to a type of input or output, but the driver handles analog and binary inputs and
outputs differently. To set these values appropriately, you should understand how the driver uses them.
Resolution Notes
Analog Input (BAI) The driver rounds the microblock's present value according to the resolution.
EXAMPLE If the calculated present value is 13.789 and you set the Resolution to 0.1, the
control program uses 13.8 for any calculations downstream from the microblock.
Analog Output The driver rounds the wire input value to the microblock before performing any scaling
(BAO) calculations.
EXAMPLE If the wire input value is 13.789 and you set the Resolution to 0.1, the
microblock uses 13.8 for any scaling calculations.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
35
To adjust input and output properties
Offset/Polarity values
Offset/Polarity is not particular to a type of input or output, but the driver handles analog and binary inputs and
outputs differently. To set these values appropriately, you should understand how the driver uses them.
Offset/Polarity Notes
Analog Input (BAI) Offset value (positive or negative) adds a fine adjustment to a sensor reading after all
scaling for calibration.
EXAMPLE If a sensor reads 74.9°F when the actual measured value is 73.6°F, enter an
Offset of –1.3 to calibrate the sensor to the measured value.
RTD inputs require either sensor calibration or an estimated offset correction for wiring
resistance. Cable length and size affects RTD sensor accuracy. Use the following
information for a 100 ft. (30.48 m) cable as a guideline for entering an offset. For shorter
cable, scale the offset linearly. For example, for a 50 ft. cable, use half the offset shown
below.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
36
To adjust input and output properties
The AO Hand Override, located below the Hand-Auto-Off switch, allows you to manually control the output level of
an analog output. Place the Hand-Auto-Off switch in the Hand position, then turn the potentiometer
counterclockwise to reduce the output, or clockwise to increase the output.
The control program can monitor the status of a Hand-Auto-Off switch and display the status on the control
program's Properties page > I/O Points tab in the WebCTRL® interface. The Value of the point monitoring the
Hand-Auto-Off switch shows Off if the switch is set to Auto, and On if the switch is set to Hand or Off.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
37
Downloading the LS-1628u
Item Notes
Up to 999 control Must be in WebCTRL_for_OEMs_x.x\webroot\<system_name>\programs or
programs, depending on Field_Assistant_x.x\webroot\<system_name>\programs.
available memory
drv_fwex driver Must be in WebCTRL_for_OEMs_x.x\webroot\<system_name>\drivers or
Field_Assistant_x.x\webroot\<system_name>drivers.
NOTE To verify that you have the driver's latest version, go to
https://accounts.oemctrl.com/tsapl/ctrackweb.nsf/download, then select Drivers >
Controllers > All OptiCORE drivers. Compare the latest version to the LS-1628u's
driver in SiteBuilder.
Editable properties
Schedules
If you change any of the above items or the LS-1628u's address after the initial download, you must download
again. The first download takes longer than subsequent downloads.
CAUTIONS
• The LS-1628u will lose stored data, such as trends, when you download.
• Equipment controlled by the LS-1628u will shut down and restart when you download.
NOTES
• If the download fails, locate, and resolve the problem, then retry the download.
• You can also download from the Devices page.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
38
Adjusting the LS-1628u driver properties
Driver
The Driver page provides the following information plus the items described in the table below:
• The date/time of last parameter change or the last time the database was archived
• If control programs, properties, and schedules were successfully stored in memory
• Undelivered Alarm Status
TouchScreen Control
TouchScreen Schedule Edit Check this field to allow a user to edit this controller's schedules from an
Enable Equipment Touch or System Touch Schedules screen.
NOTE Schedules edited on an Equipment Touch or System Touch are not
uploaded to the WebCTRL® application. This could result in the controller
operating on a schedule that differs from the one you see in the WebCTRL®
interface.
Controller Clock
Clock Fail Date and Time Date and time the controller uses when its real-time clock is invalid.
Time Synch Sensitivity When the controller receives a time sync request, if the difference between the
(seconds) controller's time and the time sync's time is greater than this field's value, the
controller's time is immediately changed. If the difference is less than this field's
value, the controller's time is slowly adjusted until the time is correct.
Network Microblocks
BACnet third party Shows how many third-party BACnet points the LS-1628u allows (capacity), how
integration points capacity, many points are in the control program (requested), and how many are currently
integration points requested, active (not disabled in WebCTRL®).
and integration points active
For example, if the LS-1628u allows 1500 points, the control program has 1450
points, and you disabled 30 points in WebCTRL®, you would see:
Integration points capacity: 1500
Integration points requested: 1450
Integration points active: 1420
Modbus integration points Shows how many Modbus points the LS-1628u allows (capacity) and how many
capacity and integration are currently active.
points active
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
39
Adjusting the LS-1628u driver properties
Number of poll retries before The maximum number of retries after the initial attempt that a Network
Network Input Microblocks microblock will attempt to communicate with its target device. If unsuccessful, the
indicate failure point will transition to an idle state for 30 seconds before attempting to
communicate again. Change this field only if directed by Technical Support.
Periodic rebinding interval If a microblock uses a wildcard in its address, this timer determines how often the
microblock will attempt to find the nearest instance of its target. For example, if
an outside air temperature address uses a wildcard, a VAV application will look for
the outside air temperature on the same network segment or on the nearest
device containing that object.
BACnet COV Throttling
Enable COV Throttling Under normal circumstances, COV Throttling should be enabled to prevent
excessive network traffic if an object's COV Increment is set too low. See
EXCEPTION below.
When enabled, if an object generates excessive COV broadcasts (5 updates in 3
seconds), the driver automatically throttles the broadcasts to 1 per second. Also,
if the object's value updates excessively for 30 seconds, an alarm is sent to the
WebCTRL® application listing all objects that are updating excessively. A Return-
to-normal alarm is sent only after all objects have stopped updating excessively.
EXCEPTION: In rare circumstances, such as process control, a subscribing object
may require COV updates more frequently than once per second. For these
situations, clear this checkbox, but make sure that your network can support the
increased traffic. You will also need to disable the Excessive COV alarms under
the driver's Common Alarms.
Trend Sampling
Collect a daily midnight For values that change infrequently, select to verify at midnight daily that the
sample for all points in this point is still able to communicate trend values.
controller that are sampling
on COV
Debug
Enable Debug Messages Enable only if directed by OEMCtrl® Technical Support.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
40
Adjusting the LS-1628u driver properties
Device
The Device page provides the following information plus the items described in the table below:
• BACnet device object properties for the LS-1628u
• The character sets supported by this device for BACnet communication
Configuration
BACnet System Status The current state of the controller:
Operational
Download in Progress
Download Required
Backup in Progress
Non-Operational
The following fields refer to all networks over which the LS-1628u communicates.
APDU Timeout How many milliseconds the device will wait before resending a message if no
response is received.
APDU Segment Timeout How many milliseconds the device will wait before resending a message segment
if no response is received.
Number of APDU Retries The number of times the device will resend a message.
Controller Clock
Time Broadcaster will If you have third-party BACnet devices on one of the router's networks, you can
synchronize time every ____ have the router send a BACnet time sync to those devices at the interval you
define in this field.
Time Synchronization To define third-party BACnet devices as Time Synchronization Recipients:
Recipients
1. Click Add.
2. Select Device ID, Address, Local Broadcaster, or Global Broadcaster in the
Recipient Type field.
3. If you selected Device ID or Address, enter the information.
4. Click Accept.
Notification Classes
A BACnet alarm's Notification Class defines:
• Alarm priority for Alarm, Fault, and Return to Normal states
• Options for BACnet alarm acknowledgment
• Where alarms should be sent (recipients)
Alarms in the WebCTRL® application use Notification Class #1. The WebCTRL® application is automatically a
recipient of these alarms.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
41
Adjusting the LS-1628u driver properties
Priorities NOTE BACnet defines the following Network message priorities for Alarms and
Events.
Priority range Network message priority
00–63 Life Safety
64–127 Critical Equipment
128–191 Urgent
192–255 Normal
Priority of Off-Normal BACnet priority for Alarms.
Priority of Fault BACnet priority for Fault messages.
Priority of Normal BACnet priority for Return-to-normal messages.
Ack Required for Off-Normal, Specifies whether alarms associated with this Notification Class require a BACnet
Fault, and Normal Acknowledgment for Off-Normal, Fault, or Normal alarms.
Calendars
Calendars are provided in the driver for BACnet compatibility only. Instead, use the Schedules feature in the
WebCTRL® interface.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
42
Adjusting the LS-1628u driver properties
NOTE To set up alarm actions for controller generated alarms, see Setting up alarm actions in the WebCTRL®
Help.
For the input to use the translation table, navigate to the input in the Geographic tree, select the Details tab,
then set Sensor Type (Scaling Method) to Non-Linear, Custom Table #__.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
43
Adjusting the LS-1628u driver properties
ARCNET Configuration
Address The address that is set on the three rotary switches.
MS/TP Configuration
Address For Port S1—The address that is set on the three rotary switches.
For Port S2—A unique address on the MS/TP network.
MS/TP Autobaud To enable autobaud, select Yes. This device will receive its baud rate from the
master device.
MS/TP Baud Rate Set this to a baud rate that all other devices on the MS/TP network are set to.
Max Masters To increase MS/TP performance, enter the highest address used on the MS/TP
network for a master controller. This number must be less than or equal to 127.
Max Info Frames This is the maximum number of information messages a controller may transmit
before it must pass the token to the next controller. Valid values are 1 to 255.
TIP Set Max Info Frames to a number in the range 20 to 100 so that the
router does not become a bottleneck for traffic being routed from a high-speed
network to the slower MS/TP network.
End of Network Switch
Status
Switch Status This displays the state of the End of Net? termination switch for the Port S1 and
Port S2 networks.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
44
Adjusting the LS-1628u driver properties
IP Configuration
Allow remote management When this field is enabled, you can set up IP addressing through an external tool.
of IP configuration IP addressing is typically set up through the Service Port.
Enable IP configuration Only for custom static IP addressing—Select this field to remotely change the
changeover router's IP Address, Subnet Mask, and Default Gateway Address.
Type the new addresses and the UDP Port that your server is using to
communicate to all controllers.
In the Changeover timeout field, enter:
• A specific length of time for the controller to attempt to communicate with the
Next Default Gateway Address. The controller will use the Next setting as
soon as the controller can communicate with the Next Default Gateway
Address, or when the timeout occurs, whichever comes first.
• 0:00 to have the controller use the Next settings as soon as the controller
can communicate with the Next Default Gateway Address.
See "To remotely change a controller's IP address" in WebCTRL® Help for more
information on using this feature.
NAT Configuration
Enable NAT Routing Reserved for future use.
BACnet Router Options
Ignore all Reject-Message-to- Clear to delete and rediscover a router if a network's router indicates that the
Network, Reason=1 network is no longer present (reason=1).
messages
Select to continue routing messages to a network even if its router indicates that
the network is no longer present.
Color/Prime Variable Caching
Peer Caching Enabled This checkbox will be checked for the router that was defined in SiteBuilder as the
peer caching router.
Disable Color Cache Clear (enable) to improve responsiveness in retrieving colors.
Select (disable) to reduce network traffic to third-party (non-color-supporting)
devices.
NOTE Selecting this checkbox also disables dead module alarms.
Dead Controller Timeout After this period (minutes:seconds) of non-response from an OEMCtrl® controller,
the router sends an alarm to the server.
Reports colors to The BACnet Object Identifier of the router that was defined in SiteBuilder as the
peer caching router.
BACnet Firewall
If this IP controller is accessible from the Internet, you can increase security by enabling its BACnet firewall. When
enabled, this feature prevents the controller from responding to BACnet messages from unidentified sources and
allows communication only with IP addresses that you define. These can be all private IP addresses and/or a list
of IP addresses. Follow the instructions in the WebCTRL® interface to set up the BACnet firewall.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
45
Adjusting the LS-1628u driver properties
Router Statistics
Router Sourced Packets Shows the number of packets initiated by the LS-1628u that are not in response
to a request from another device. The numbers in this table will also appear in the
appropriate columns in the Network Activity tab.
Trends Error Rate Trend—Shows the total number of errors within the trend sampling
interval.
Packet Rate Trend—Shows the total number of packets transmitted and received
within the trend sampling interval.
Gig-E Port Statistics
BACnet/IP Statistics BACnet/IP Rx Unicast Packets—BACnet/IP packets received from a single BACnet
device.
BACnet/IP Tx Unicast Packets—BACnet/IP packets transmitted to a single BACnet
device.
BACnet/IP Rx Broadcast Packets—BACnet/IP broadcast packets received by the
LS-1628u.
BACnet/IP Tx Broadcast Packets—BACnet/IP broadcast packets transmitted by
the LS-1628u.
Whitelist Rejections (if BACnet Firewall (page 45) is enabled)—Messages blocked
by the BACnet Firewall because the IP address that sent the message was not in
the whitelist.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
46
Adjusting the LS-1628u driver properties
Ethernet Statistics Ethernet Rx packets—All packets (including non-BACnet packets such as a ping)
received by the LS-1628u.
Ethernet Tx packets—All packets (including non-BACnet packets such as a ping)
transmitted by the LS-1628u.
Receive Errors (total)—All errors related to received packets such as CRC errors,
FIFO errors, frame errors, length errors, missed errors, and overrun errors.
Transmit Errors (total)—All errors related to transmitted packets such as aborted
errors, carrier errors, dropped errors, FIFO errors, heartbeat errors, and window
errors.
Dropped Packets—Packets dropped by the LS-1628u's Ethernet interface.
Trends Error Rate Trend—Shows the total number of errors within the interval time.
Packet Rate Trend—Shows the total number of packets transmitted and received
within the trend sampling interval.
Port S1 Statistics
when used for ARCNET
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
47
Adjusting the LS-1628u driver properties
Port S1 Statistics
when used for MSTP
or
Port S2 Statistics
Error Counters UART Errors—UART receive and transmit errors such as break errors, framing
errors, parity errors, and overrun errors.
Invalid Frames—Received MS/TP frames that contain an error such as CRC.
Dropped Packets—Dropped receive and transmit frames. These may be dropped
due to buffer allocation failures, length errors, or APDU timeouts (in the case of
transmit frames)
Dropped Tokens—Dropped tokens that have been retransmitted.
No responses—Messages that did not receive a response from the destination
device.
Activity Counters BACnet/MSTP Rx Packets—BACnet/MSTP data packets received by the LS-
1628u.
BACnet/MSTP Tx Packets—BACnet/MSTP data packets transmitted by the LS-
1628u.
Latency Average Value (milliseconds)—The average time from when a packet is queued to
be transmitted until it is actually transmitted on the bus.
Maximum Value (milliseconds)—The maximum time from when a packet is
queued to be transmitted until it is actually transmitted on the bus
Trends Error Rate Trend—Total number of errors within the interval time on this network,
including break errors, framing errors, etc.
Packet Rate Trend—Percentage of total bus bandwidth used to transmit data
packets.
NOTE This is for all bus traffic, not just traffic generated by the LS-1628u.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
48
Adjusting the LS-1628u driver properties
○ If the port is set up for MS/TP, select an option in the Capture section.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
49
Adjusting the LS-1628u driver properties
I/O Expanders
The I/O Expanders page provides the configuration and status information described in the table below.
Error: Comm Fail The controller and LS-XP expander are not
communicating.
Error: Unsupported The LS-XP expander type is not compatible with the
Type controller firmware version.
Disabled Status briefly shown before Error: Comm Fail appears.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
50
Adjusting the LS-1628u driver properties
Act Net Bus Status This table shows devices connected to the Act Net port. All fields are read-only.
Device Address Act Net device address (1 to 16). The same address is used as exp# in the
microblock configuration with the input/output number for all Act Net devices set
to 1.
Device Description This text is editable in the Act Net Bus Configuration table directly below.
Serial Number The serial number of the Act Net device. This number is printed on a label on the
device.
Device Status Displays the current status of the device
Possible statuses Description
No Communication with LS-1628u has lost communication with the Act Net
the device device
Duplicate Address on More than one device has the same Device Address.
the network
Unsupported Device Device is not recognized
Type
Act Net Wiring Error Loopback error on Act Net bus, possibly caused by
wiring problem or hardware failure.
Act Net Bus Configuration This table shows devices connected to the Act Net port. Most fields are editable.
Current Address Bus address of the Act Net device
Device Description Edit the name if needed.
Serial Number Serial Number of the device corresponds to Current Address in the same row. This
field is read-only if the corresponding device is in communication, otherwise
becomes editable so that user can enter the serial number manually (can be found
as a label on the actuator).
New Device Address Select a new bus address from the drop-down list.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
51
Adjusting the LS-1628u driver properties
Configuration Status Once all changes are accepted, after applying changes this fields shows
success/fail statuses.
Possible statuses Description
Auto addressed device When a device that does not have an address is found
on the bus, an unused address in automatically
assigned.
You can select a different address in the New Device
Address field, if needed.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
52
Adjusting the LS-1628u driver properties
Communication Status
The Communication Status page shows the status of the protocols currently running on the LS-1628u's ports.
Field Notes
Sample every _:_:_ (hh:mm:ss) (Recommended method) To record the value at a regular time interval, enter
hh:mm:ss in this field.
Sample on COV To record the value only when the value changes by at least the amount of
(change of value) the COV Increment, set the Sample every field to 0:00:00 and enter a value
in the COV Increment field.
Max samples Network Statistic trends have a non-configurable maximum trend log buffer
size of 1440.
NOTE Trending consumes memory in the controller. Click Reset to delete all
samples currently stored in the controller.
Stop When Full Check this field to stop trend sampling when the maximum number of
samples is reached.
Enable trend log at specific Collects trend data for the specific period of time you define in the time and
times only date fields.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
53
Adjusting the LS-1628u driver properties
Field Notes
Enable Trend Historian Archives trend data to the system database.
Store Trends Now Writes all trend data in the controller to the system database without having
to enable trend historian.
Write to historian every __ trend Writes all trend data in the controller to the system database each time the
samples controller collects the number of samples that you enter in this field. This
number must be greater than zero and less than the number entered in the
Max samples field. The number of trends specified must be accumulated at
least once before the historical trends can be viewed.
NOTE Any trends not stored in the historian will be lost if the controller loses
power.
Trend samples accumulated Shows the number of samples stored in the controller since data was last
since last notification written to the database.
Last Record Written to Historian Shows the number of trend samples that were last written to the database.
Keep historical trends for __ This is based on the date that the sample was read. Select the first option to
days use the system default that is defined on the System Settings > General tab.
Select the second option to set a value for this trend only.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
54
To set up the controller through the Service Port
1 Connect an Ethernet cable from a computer to the controller's Service Port, as shown below.
NOTE Be sure NOT to plug the cable into the Gig-E Port.
NOTE The first time you access the controller in the WebCTRL® interface after you have changed settings through
the Service Port, be sure to upload the changes to the system database. This will preserve those settings when
you download memory or parameters to the controller.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
55
To set up the controller through the Service Port
ModStat tab
This tab provides the controller's Module Status report that gives information about the controller and network
communication status. See Appendix - Module Status field descriptions (page 75).
Device tab
The information on the Devices tab is typically defined in the WebCTRL® interface and then downloaded to the
controller. However, you would set the information on the controller setup Device tab if the controller is stand-
alone without a WebCTRL® system.
BACnet Object
Device Instance Autogenerated—The Device Instance is automatically set to a number equal to
the (IP network number) x 100 + rotary switch address.
Assigned—Lets you enter a specific number that is unique on the BACnet network.
Device Name Autogenerated—The Device Name is automatically set as the word
device + the Device Instance. For example, device2423911.
Assigned—Lets you enter a specific name that is unique on the BACnet network.
Device Location You can enter an intuitive location for the device in the WebCTRL® interface.
Device Description You can enter an intuitive description for the device in the WebCTRL® interface.
Configuration
APDU Timeout How many milliseconds the device will wait before resending a message if no
response is received.
APDU Segment Timeout How many milliseconds the device will wait before resending a message segment
if no response is received.
APDU Retries The number of times the device will resend a message.
Controller Information
Clear Counts/Logs Clears Reset counters and the three message history fields from the Module
Status.
Data Backup and Restore
Backup Displays time of the last backup. Click button to backup the controller's control
programs, properties, and schedules.
Restore Displays time of the last restore. Click button to restore the most recent backup
of the controller's control programs, properties, and schedules.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
56
To set up the controller through the Service Port
Ports tab
IP Port
IP Addressing Select the type of addressing the controller is to use. See Addressing the LS-
1628u (page 16).
Port S1
End of Network Indicates status of the controller's End of Net? switch.
Active Protocol Indicates status of the controller's Port S1 Configuration rotary switch.
0=Disabled
1=MS/TP
2=ARCNET
3=Modbus
Address The address that is set on the three rotary switches. See To set the Port S1
address and baud rate (page 20).
Port S2
End of Network Indicates status of the controller's End of Net? switch.
Active Protocol The protocol that has been enabled for Port S2 on the BACnet or Modbus tab.
BACnet tab
The information on the BACnet tab is typically defined in SiteBuilder or the WebCTRL® interface and then
downloaded to the controller. However, you would set the information on the controller setup BACnet tab if the
router is stand-alone without a WebCTRL® system.
IP Port
BACnet Network Number Disable Routing—Select if the IP port is not used.
Autogenerated—The BACnet/IP network number is automatically set to 2400.
Assigned—Lets you enter a specific number.
BACnet UDP Port The port that the WebCTRL® application will use for BACnet communication.
Enable NAT Routing For future use.
Check if the LS-1628u is behind a NAT router (firewall).
Global NAT IP Address For future use.
Public IP address of the NAT router.
Global NAT BACnet UDP Port For future use.
Port number assigned to the NAT router's public interface.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
57
To set up the controller through the Service Port
BACnet Secondary IP Net If the LS-1628u has two BACnet/IP networks communicating on the Gig-E port,
Number enter the second IP network number in this field.
If the LS-1628u is behind a NAT router and there is a second network with
BACnet/IP devices behind the NAT router, enter the second network number in
this field to logically connect the LS-1628u to the devices on the second network.
BACnet P rivate Public
router s ide N s ide
R
A
C T
Sec ondary I P
Controller network
BACnet Secondary UDP Port If the LS-1628u has two BACnet/IP networks communicating on the Gig-E port,
enter the port number that the WebCTRL® application will use for BACnet
communication. This port must be different than the BACnet UDP Port.
Ethernet Port
Address A factory assigned Ethernet MAC Address for the Gig-E port.
BACnet Network Number Specify a number for the BACnet/Ethernet network or set to 0 if the port is not
used.
Port S1
End of Network Indicates status of the controller's End of Net? switch.
Active Protocol Indicates status of the controller's Port S1 rotary switch.
0=Disabled
1=MS/TP
2=ARCNET
3=Modbus
Address The address that is set on the three rotary switches. See To set the Port S1
address and baud rate (page 20).
MSTP Autobaud Select Yes to enable this slave device to automatically receive its baud rate from
a master on the network that has the fixed baud rate.
MSTP Baud Rate Set this to a baud rate that all other devices on the MS/TP network are set to.
MSTP Max Master To increase MS/TP performance, enter the highest address used on the MS/TP
network for a master controller. This number must be less than or equal to 127.
MSTP Max Info Frames This is the maximum number of information messages a controller may transmit
before it must pass the token to the next controller. Valid values are 1 to 255.
TIP Set Max Info Frames to a number in the range 20 to 100 so that the
router does not become a bottleneck for traffic being routed from a high-speed
network to the slower MS/TP network.
BACnet Network Number Select:
Disable Routing if Port S1 is not used.
Autogenerated to have the network number for Port S1 automatically set to a
number equal to ((IP network number + rotary switch address) x 10).
Assigned to enter a specific number.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
58
To set up the controller through the Service Port
Port S2
End of Network Indicates status of the controller's End of Net? switch.
Active Protocol Shows one of the following:
• Modbus if enabled on the Modbus tab
• BACnet/MSTP if you enter a BACnet Network Number below for an MS/TP
network
• Disabled if neither of the above have been done
Address The controller’s unique address on the MS/TP network.
MSTP Autobaud Select Yes to enable this slave device to automatically receive its baud rate from
a master on the network that has the fixed baud rate.
MSTP Baud Rate Set this to a baud rate that all other devices on the MS/TP network are set to.
MSTP Max Master To increase MS/TP performance, enter the highest address used on the MS/TP
network for a master controller. This number must be less than or equal to 127.
MSTP Max Info Frames This is the maximum number of information messages a controller may transmit
before it must pass the token to the next controller. Valid values are 1 to 255.
TIP Set Max Info Frames to a number in the range 20 to 100 so that the
router does not become a bottleneck for traffic being routed from a high-speed
network to the slower MS/TP network.
BACnet Network Number Select:
Disable Routing if Port S2 is not used.
Autogenerated to have the network number for Port S2 automatically set to a
number equal to ((IP network number + rotary switch address) x 10) + 3.
Assigned to enter a specific number.
Home Network This is typically the network that is communicating with the building automation
system's application. This sets the BACnet Address of the Device object.
Modbus tab
If the controller will be used with Modbus devices, see the Modbus Integration Guide for information on using this
tab.
Security tab
BACnet Firewall If your BACnet Firewall configuration in the WebCTRL® interface did not include
the WebCTRL® server IP address, thus blocking communication with the
WebCTRL® server, you can disable the controller's BACnet Firewall on the
controller setup Security tab.
NOTE You can enable the BACnet Firewall only in the WebCTRL® interface.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
59
To communicate through the BACnet/IP Service Port network
1 Connect an Ethernet cable from a computer to the controller's Service Port, as shown below.
NOTE Be sure NOT to plug the cable into the Gig-E Port.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
60
To communicate through the BACnet/IP Service Port network
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
61
To communicate locally through the Rnet port
PREREQUISITES
• A computer with a USB port
• A USB Link Kit. See the USB Link Kit Technical Instructions.
NOTES
○ The USB Link Kit driver is installed with a WebCTRL® v6.5 or later system. Please refer to the Silicon
Labs website and search "CP210x USB to UART Bridge VCP Drivers" for the most current device drivers.
Install the driver before you connect the USB Link Kit to your computer.
○ You will use only the portion of the USB Link Kit that has the USB connector.
CAUTION If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link
Kit and the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and
the USB Link Kit. Purchase a USB isolator online from a third-party manufacturer.
• A 3-pin screw terminal connector and 3-wire cable
2 Connect the other end of the 3-wire cable to the LS-1628u's Rnet port as shown in the drawing above in step
1.
3 Connect the 3-pin connector to the portion of the USB Link Kit shown in the drawing below, then connect the
USB connector to the computer.
NOTE If using a USB isolator, plug the isolator into your computer's USB port, and then plug the USB Link Kit
cable into the isolator.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
62
To communicate locally through the Rnet port
11 On the Network tree, select the controller that you are connected to.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
63
Troubleshooting
Troubleshooting
If you have problems mounting, wiring, or addressing the LS-1628u, contact OEMCtrl® Technical Support.
LEDs
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
64
Troubleshooting
Blue 2 blink Controller has same MAC address as Duplicate address on Change rotary switch to
another connected device MSTP unique address
3 blink Controller is the only device on the No other devices • Check that network cable
Blue
network detected on is connected properly
ARCNET/MSTP • Check that baud rate is
correct
4 blink Excessive errors detected over 3 Excessive • Check that network cable
Blue
second period communication errors is connected properly
on ARCNET/MSTP • Check that baud rate is
correct
5 blink ARCNET traffic overload possibly due Event System Error - • Check the network
Blue
to circular route or excessive COVs FPGA RX FIFO full configuration for a
(change of values) circular route
• Increase the time
between COVs to reduce
excessive COV traffic
Green On All enabled networks are functioning No errors No action required
properly
Magenta Operating system changes are N/A No action required
downloading
WARNING This process could take
several minutes. Do NOT power off the
controller during the download.
Red 2 blink Restarting after an abnormal exit Auto restart delay due After 5 minute delay has
to system error on expired, if condition occurs
startup again then cycle power
Red 4 blink Firmware image is corrupt Firmware error Download driver again
Red Fast Firmware error has caused the Fatal error detected No action required
blink firmware to exit and restart
Green 3 blink BACnet Device ID is not set Download required Download the controller
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
65
Troubleshooting
Blue Fast Linux is running but it could not start N/A Download driver
blink the firmware application
Magenta Operating system changes are N/A No action required
downloading
WARNING This process could take
several minutes. Do NOT power off the
controller during the download.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
66
Troubleshooting
• In the WebCTRL® application—Right-click the controller on the Network tree, then select Module Status.
• In the WebCTRL® application—Select the controller on the Network tree. On the Properties page, click
Module Status.
• On the controller setup ModStat tab—See To set up the controller through the Comm/Service ports (page
55).
1 In the WebCTRL® Geographic or Network tree, select the equipment controlled by the OptiCORE™
LS-1628u.
2 On the Properties page, select the I/O Points tab.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
67
Troubleshooting
3 Click the Name of any input or output whose name is red (indicates an error) to open its dialog box.
4 On the Details tab, scroll down to see the Reliability field under BACnet Configuration.
5 Anything other than No Fault Detected indicates an error. See the table below to determine the error and
possible actions to take.
Shorted Loop • Internal voltage feedback does not • The load on the output is within the valid
correspond with commanded value. range.
• A voltage/current source has not been
connected to an output.
Open Loop • Internal current feedback does not • The load on the output is within the valid
correspond with commanded value. range.
• A voltage/current source has not been
connected to an output.
Unreliable Other • Feedback does not correspond with • Device may be faulty. Contact OEMCtrl®
commanded value (for example, the Technical Support.
output relay is not in commanded
state).
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
68
Troubleshooting
WARNING You must not use this value as an input in a control program, as it could damage the
controller or controlled equipment. The value must only be trended.
Changes to the power demands of the controller, such as output state, input power requirements, peripheral
current draw, etc., can impact the reading, which results in a potential feedback loop and output cycling.
The Input power state does not take all factors into account, which could result in an incomplete evaluation
of conditions. You must only use these values for troubleshooting and not for equipment logic.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
69
Troubleshooting
NOTE You can click Device Log Archive to download a file containing multiple Device Logs to your computer. This
also contains any network packet captures that have been run from the Network Diagnostics - Packet Captures
driver page.
• A QR code, serial number, and MAC address printed on a sticker on the cover
• A laser-etched number and QR code on the inside circuit board.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
70
Troubleshooting
• I/O bus edge connector fuse—The LED is not lit on downstream expanders connected to the edge
connector.
NOTE If the LS-1628u's power fuse blows but not the I/O bus edge connector fuse, the LS-1628u will be off but
not the downstream expanders.
If you suspect a fuse is blown, remove the fuse as described below, and use a multimeter to check it. If the fuse is
blown, try to determine why it blew before you replace it. Check the power wiring polarity of the LS-1628u and any
other devices that share the power supply. Use the same polarity for all of them.
The fuses are fast-acting, 5mm x 20mm glass fuses that you can purchase from one of the following vendors:
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
71
Troubleshooting
4 On both ends of the LS-1628u, insert a small flathead screwdriver as shown below, and then gently pry up
the cover until it is released from the base.
11 Verify the LEDs on the LS-1628u and any downstream expanders are lit.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
72
Troubleshooting
WARNING This erases all archived information and user-configured settings. When recovery is complete,
you must connect locally to the LS-1628u and manually reconfigure all BACnet, IP, and firewall information. We
highly recommend that you revert the default settings only under the guidance of OEMCtrl® Technical Support.
1 Copy the newest driver to the root directory of a FAT32-formatted USB flash drive.
NOTE To verify that you have the driver's latest version, go to
http://accounts.oemctrl.com/tsapl/ctrackweb.nsf/download, then select Drivers > Controllers. Compare the
latest version to the LS-1628u's driver in SiteBuilder.
2 Remove power from the LS-1628u.
3 Set the rotary switches to 911.
4 Apply power to the LS-1628u.
NOTE The Sys and Net LEDs change to magenta after the boot sequence.
5 Plug the USB drive into the controller's USB port.
NOTES
○ The Sys LED blinks faster when recovery is in progress.
○ When the Sys LED turns solid green, the process is complete.
6 Remove power from the LS-1628u.
7 Remove the USB drive from the USB port.
8 Set the rotary switches back to the normal address.
9 Apply power to the LS-1628u.
NOTE The controller is now running the new version of the firmware and is in the default state.
10 Configure the IP address and all other necessary parameters.
WARNING This erases all archived information and user-configured settings created since the last backup.
If changes were made to the BACnet, IP, and firewall information since the last backup, you must connect locally
to the LS-1628u and manually reconfigure this information after recovery.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
73
Compliance
Compliance
FCC Compliance
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
1 This device may not cause harmful interference.
2 This device must accept any interference received, including interference that may cause undesired
operation.
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate
radio frequency energy, and if it is not installed and used in accordance with this document, it may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference, in which case the user will be required to correct the interference at his own expense.
CAUTION Any modifications made to this device that are not approved by OEMCtrl® will void the authority
granted to the user by the FCC to operate this equipment.
WARNING This is a Class B product. In a light industrial environment, this product may cause radio
interference in which case the user may be required to take adequate measures.
BACnet Compliance
Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of BACnet
International. BTL® is a registered trademark of BACnet International.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
74
Appendix - Module Status field descriptions
Field Description
Date/Time Date and time the Modstat was run
CM The controller's rotary switch address (MAC address)
Model Name Identifies the Product Type
Device Instance A unique ID assigned to the controller
Driver built When the driver was built
Downloaded by When and where the last download was performed
Application Software Version The name of the first control program that is downloaded
Data Partition Version Not applicable to this device.
# PRGs initialized If applicable, the number of control programs that were downloaded vs. the
# PRGs running number that are running. If these numbers are not the same, the controller
has a problem such as lack of memory.
Driver version The name, version, and date of the driver, as well as all the bundles and
versions.
Reset Counters: The number of times each of the following events have occurred since the last
time the controller was commanded to clear the reset counters.
See NOTE below this table.
Power failures Interruption of incoming power
Commanded boots Includes commands issued from the WebCTRL® interface such as the zap
manual command, plus commands issued during a memory download.
System errors Error in the controller's firmware or hardware
S/W Watchdog Watchdog is firmware that monitors the application firmware for normal
timeouts operation. If the watchdog firmware detects a problem, it restarts the
application firmware.
H/W Watchdog H/W Watchdog will restart the controller if it detects a severe problem with the
timeouts controller's operating system
System status Gives the current status of the controller's operation. See LEDs (page 64) for
all possible conditions.
Network status Gives the current status of the controller's networks. See LEDs (page 64) for
all possible conditions.
System error message history High-severity errors since the last memory download. Shows the most recent
10 messages.
See NOTE below this table.
Warning message history Low-severity errors and warning messages since the last memory download.
Shows the most recent 10 messages.
See NOTE below this table.
Information message history Information-only messages since the last memory download. Shows the most
recent 10 messages.
See NOTE below this table.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
75
Appendix - Module Status field descriptions
Field Description
ARC156 reconfigurations during An ARCNET network normally reconfigures itself when a controller is added to
the last hour or taken off the network. The Total field indicates the number of
reconfigurations in the last hour. Initiated by this node indicates the number
of reconfigurations initiated by this controller. Typical sources of the problem
could be this controller, the controller with the next lower rotary switch
address, any controller located on the network between these two controllers,
or the wiring between these controllers. An excessive number in these fields
indicates a problem with the network.
Core and Base board hardware Gives the following information about the controller's boards:
• Type and board numbers that are used internally by OEMCtrl®.
• The manufacture date and serial number.
Number of BACnet Objects The number of BACnet objects that were created in the device and the
number of those objects that are network visible.
Database Partition Non-Volatile partition (16 MB maximum) contains data that needs to be
preserved through a power cycle and archived to flash such as parameters
and trend data.
Volatile partition (6 MB maximum) contains data that does not need to be
preserved through a power cycle such as status values that are calculated
during runtime.
IP Networks - BBMDs Shows the following information for each active IP network:
BBMD Active shows whether the BACnet Broadcast Management Device is
currently active (1) or inactive (0).
BBMD Entries—the number of entries in the BBMD table (500 maximum).
FDT Entries—the number of entries in the Foreign Device Table (500
maximum).
Third party integration points Shows number of points used.
Network Information The various network addresses for the controller. The Current and Assigned
addresses will be the same unless the Enable IP configuration changeover on
the BACnet Router Properties page is being implemented.
Statistics and Network Activity Shows network communication statistics to assist with troubleshooting. See
Network Diagnostics - Statistics (page 46) for more information.
Route Information BACnet networks that a router is currently routing traffic to. The list changes
Port Number as BACnet routers are added or removed from the system.
NOTE If you want to clear the Reset counters and the three message history fields, click the Clear Counts/Logs
button on the controller's Properties page in the WebCTRL® application or in the controller setup Device tab.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
76
Document revision history
Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not
listed.
Specifications
Adjusting the LS-1628u driver Added Local Broadcaster and Global Broadcaster options X-D
properties > Device in Controller Clock > Time Synchronization recipients
Inputs Updated pulse counting note X-TS-RB-R-RB
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier.
Rev. 6/10/2022 All rights reserved.
77
Document revision history
Important changes to this document are listed below. Minor changes such as typographical or formatting errors are not
listed.
OptiCORE™ LS-1628u OEMCtrl Proprietary and Confidential A Carrier Company. © 2022 Carrier
Rev. 6/10/2022 All rights reserved
78
OEMCtrl® · 1025 Cobb Place Blvd, Kennesaw, GA 30144 · 770-429-3060 · www.oemctrl.com
6/10/2022