Intelligent Input Output Unit

The Intelligent Input/Output Unit operates with a supply voltage of 17–35 V dc and is compatible with XP95, Discovery, and CoreProtocol systems. It features nine pre-configured modes, including failsafe operation, and supports various input styles with earth fault monitoring. The unit complies with multiple standards and is designed for ease of installation and wiring.

Uploaded by

Purchase Rame
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views3 pages

Intelligent Input Output Unit

The Intelligent Input/Output Unit operates with a supply voltage of 17–35 V dc and is compatible with XP95, Discovery, and CoreProtocol systems. It features nine pre-configured modes, including failsafe operation, and supports various input styles with earth fault monitoring. The unit complies with multiple standards and is designed for ease of installation and wiring.

Uploaded by

Purchase Rame
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

PP2553/2019/Issue 3

Page 1 of 4

Intelligent Input/Output Unit

Technical data
All data is supplied subject to change without notice. Specifications
are typical at 24 V, +25°C and 50% RH unless otherwise stated.

Supply voltage 17–35 V dc


(Vmin–Vmax)
Protocol 5–13 V peak to peak
Power-up surge current 900 µA
Quiescent current 500 µA
Max current LEDs On 3.5 mA
Product overview Max current LEDs 500 µA
disabled
Product Type Input/Output Unit
Relay output contact rating 1 A at 30 V dc or ac
Part No. SA4700-102APO Isolator data Refer to Short-Circuit Isolation
Digital Communication XP95, Discovery and datasheet PP2090
CoreProtocol compatible Operating temperature – 40°C to + 70°C
Humidity 0% to 95% RH
Compliance (no condensation or icing)
Vibration, impact and shock EN 54-17, EN 54-18

IP rating IP52

Standards and approvals EN 54-17, EN 54-18, CPR, LPCB,


VdS, BOSEC, SBSC, FG
Dimensions 60 mm height x 150 mm width x
90 mm depth

Product information Weight 244 g

The Intelligent Input/Output Unit provides supervision of one


or more normally open contacts connected to a single pair of
Table 1: Digital communications protocol
cables and a set of changeover relay output contacts.
compatibility
Refer to Table 1 for digital communications protocol
Protocol Device Behaviour
compatibility and Table 2 for the Intelligent Input/Output Unit
operating modes. XP95† /Discovery† XP95

• Improved design for ease of wiring meaning faster CoreProtocol† Soteria


installation †
Fire control panel dependant
• Contains controllable isolator *
• Address range 1 - 254 *
• Nine pre-configured modes, including compatibility
mode from XP95/Discovery to CoreProtocol systems *
• Failsafe mode (meets BS 7273-4 requirements)
• Configurable input styles *
• Earth fault monitoring *
* Note: CoreProtocol enabled systems feature only, please check with
your system partner for availability.

All information in this document is given in good faith but Apollo


Fire Detectors Ltd cannot be held responsible for any omissions or
errors. The company reserves the right to change the specifications
of products at any time and without prior notice.

MANAGEMENT MANAGEMENT PRODUCT


SYSTEMS SYSTEMS CERTIFICATION

Assessed to ISO 9001:2015 Assessed to ISO 14001:2015 Cert/LPCB ref. 010


Cert/LPCB ref. 010 Cert/LPCB ref. 010 EMS
PP2553/2019/Issue 3
Page 2 of 4

Table 2: Intelligent Input/Output Unit operating modes* Figure 1: Intelligent Input/Output Unit dimensional
drawing
Mode Description

1 DIL Switch XP Mode

2 Alarm delays

3 Output and N/O input (can be equivalent for Output only)

4 Output and N/C input

90 mm
5 Output with Feedback (N/C)

6 FailSafe Output with Feedback (N/C)

7 FailSafe Output without Feedback

8 Momentary Input Activation Sets Output Relay

9 Input Activation Sets Output

* CoreProtocol enabled systems only

Failsafe

60 mm
In Failsafe mode the Intelligent Input/Output Unit will activate
the on-board relay output without being commanded by the
control panel on loss of loop or protocol loss. Failsafe mode
is selected via a DIL switch and indicated with an analogue
value of 17.
150 mm
Mechanical Construction
The Intelligent Input/Output Unit (see Figure 1) is available
in the new faceplate style enclosure. This can be mounted
with the supplied back-box for surface mounting or flush Table 3: Status Indications
mounted using a UK double gang, flush mounting back-box
Legend LED Status Description
of minimum depth 30mm.
RLY Continuous Red Relay Active
EMC Directive 2014/30/EU
RLY Continuous Yellow Relay Fault
The Intelligent Input/Output Unit complies with the essential
requirements of the EMC Directive 2014/30/EU, provided Poll/ISO Flashing Green Polling LED
that it is used as described in this datasheet.
Poll/ISO Continuous Yellow Isolator LED
A copy of the Declaration of Conformity is available from
I/P Continuous Yellow Input Fault
Apollo on request.
Conformity of the Intelligent Input/Output Unit with the EMC I/P Continuous Red Input Active
Directive, does not confer compliance with the directive on
any apparatus or systems connected to them.
Construction Products Regulation 305/2011/EU
The Intelligent Input/Output Unit complies with the essential
requirements of the Construction Products Regulation
305/2011/EU.
A copy of the Declaration of Performance is available from
Apollo on request.

Connectivity
Figures 2, 3 and 4 for unit connection information. Refer to the
Installation Guide 39215-159 for the installation instructions
on this product. Table 3 details the status indications of this
unit, from normal operation through to fault conditions.
PP2553/2019/Issue 3
Page 3 of 4

Figure 2: Intelligent Input/Output Unit standard resistive monitoring mode connectivity diagram

L- L+

INPUT/OUTPUT

NC COM NO
UNIT

L- L+
Relay contact

POLL / ISOL
0
1A at 30V
RLY Polarity
Sensitive

L+
1

IP-

1
2
4
8
16
32
64
128
FS
LED
IP+

L-
N/O IP
Contact
L- L+
Loop
20k EOL 1k

Figure 3: Intelligent Input/Output Unit normally open monitoring mode connectivity diagram
(compatible with CoreProtocol only)

L- L+

INPUT/OUTPUT
NC COM NO

UNIT

L- L+
Relay contact

POLL / ISOL
0
1A at 30V
RLY Polarity
Sensitive

L+
1
IP-

1
2
4
8
16
32
64
128
FS
LED
IP+

L-
N/O IP
Contact
L- L+
Loop

Figure 4: Intelligent Input/Output Unit normally closed monitoring mode connectivity diagram
(compatible with CoreProtocol only)

L- L+

INPUT/OUTPUT
NC COM NO

UNIT
L- L+

Relay contact
POLL / ISOL

0
1A at 30V
RLY Polarity
Sensitive
L+ L-

1
IP-

1
2
4
8
16
32
64
128
FS
LED
IP+

IP
N/C
Contact
L- L+
Loop