Air System Inputs

The document outlines the input data for a Default Air System, specifically a 2-Pipe Fan Coil system with Dedicated Outdoor Air System (DOAS) components. It includes details on airflow control, cooling coil data, humidification data, and zone components, along with sizing data for hydronic systems. The equipment data specifies the DOAS cooling unit's design parameters and performance ratings.

Uploaded by

sengyouiphone
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views2 pages

Air System Inputs

The document outlines the input data for a Default Air System, specifically a 2-Pipe Fan Coil system with Dedicated Outdoor Air System (DOAS) components. It includes details on airflow control, cooling coil data, humidification data, and zone components, along with sizing data for hydronic systems. The equipment data specifies the DOAS cooling unit's design parameters and performance ratings.

Uploaded by

sengyouiphone
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Default System Input Data

Project: E301_V2 01/19/2025


Prepared by: I.T.C 1:41 PM

1. General Details:
Air System Name Default System
Equipment Type Terminal Units
Air System Type 2-Pipe Fan Coil
Space Model: Default Space Model
Ventilation DOAS (Air Direct to Spaces)
Notes:

2. Dedicated Outdoor Air System Components:


Ventilation Air Data:
Airflow Control Constant Ventilation Airflow
Ventilation Sizing Method ASHRAE Standard 62.1-2019

Cooling Coil Data:


Setpoint 16.0 C
Cooling Source Air-Cooled DX
Schedule JFMAMJJASOND

Ventilation Fan Data:


Fan Type Forward Curved
Configuration Draw-thru
Fan Performance 497 Pa
Overall Efficiency 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Humidification Data:
Min. RH Setpoint (Discharge) 50 %
Humidifier Type Self-contained Steam - Electric
Input Power 0.721 kWh/kg

Duct System Data:


Return Duct or Plenum Data:
Return Air Via Ducted Return

3. Zone Components:
Assigned Zones:

Zone Zone Name


1 unnamed space

Number of zones 1

Thermostats and Zone Data:

Cooling Cooling Heating Heating T-Stat Direct


T-Stat T-Stat T-Stat T-Stat Throttling Diversity Exhaust
Zone Occ. Unocc. Occ. Unocc. Range Factor Fan
(C) (C) (C) (C) (C) (%) (kW)
All 23.9 26.7 21.1 18.3 0.83 n/a 0.0

Thermostat Schedule thermostart


Unoccupied Cooling is Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temp. 14.4 C
Cooling Source Chilled Water
Schedule JFMAMJJASOND

Hourly Analysis Program 6.2 Page 1 of 2


Default System Input Data
Project: E301_V2 01/19/2025
Prepared by: I.T.C 1:41 PM

Heating Coil:
Design Supply Temp. 35.0 C
Heating Source Hot Water
Schedule JFMAMJJASOND

Fan Control 1-Speed Fan

Terminal Units Data:

Air
Distribution Air Design
Air Effectiveness Distribution Supply Fan
Zone Terminal Type Distribution Specification Effectiveness Minimum Airflow Temp. Fan Perf. Efficiency
Ceiling supply /
All Fan coil ASHRAE 62.1 <auto> 0.00 L/s/person - 62 Pa 50 %
ceiling return

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature n/a C
Heating Supply Temperature n/a C

Hydronic Sizing Specifications:


Chilled Water Supply Temperature 6.7 C
Chilled Water Delta-T 5.6 K
Hot Water Supply Temperature 60.0 C
Hot Water Delta-T 11.1 K

Safety Factors:
Cooling Sensible 0 %
Cooling Latent 0 %
Heating 0 %

Zone Sizing Data:


Zone Airflow Sizing Method Peak zone sensible load
Space Airflow Sizing Method Coincident space loads

5. Equipment Data
DOAS Cooling Unit - Air-Cooled DX
Design OADB 35.0 C
Design EWB 19.4 C
Equipment Sizing Auto-Sized
Capacity Oversizing Factor 0 %
AHRI Performance Rating 3.224 EER
DX System Configuration 1-stage, 1 compressor, 1 circuit
Low Temperature Cutoff OAT -17.8 C

Changeover Controller:
Used No

Hourly Analysis Program 6.2 Page 2 of 2