Substation Automation Products
Line distance protection REL670
Overview
© SA-T Training
1MRG005473
Section 2
Main application
Line distance protection
terminal for:
Directly earthed networks
Isolated or impedance earthed networks
OH-lines and Cables
Series Compensated Lines
Double circuit lines
Single-, two- or three pole trip
Quadrilateral (“IEC”) or MHO (“ANSI”)
characteristics
© SA-T Training
1MRG005473
Slide 2
Section 2
Main characteristics
Line IED for protection, monitoring and
control
Building block in Substation Automation
Systems
Functional flexibility
Configuration flexibility
Extensive self- supervision
© SA-T Training
1MRG005473
Slide 3
Section 2
Main features in REL 670
Completely full scheme
Simultaneous measurement in each loop and
advanced phase selection
Typical operate time: One cycle
Very low requirement of time to saturation
for CT’s including maximum remanence
Complete software library for all
applications
Full Bay control functionality available.
© SA-T Training
1MRG005473
Slide 4
Section 2
Main features in REL 670
Functions
Distance protection
(up to five zones)
Current and voltage functions
Circuit breaker failure protection
Synchrocheck and energizing check
functions for single and multiple circuit
breaker arrangements
Single-, (two-) and three-pole
autoreclosing functions for single and
multiple circuit breaker arrangements,
etc.
Scheme communication
etc
© SA-T Training
1MRG005473
Slide 5
Section 2
Functionality – Pre-configured IEDs (IEC)
A21 1 CB, 3-Phase Trip
Resonance earthing
A31 1 CB, 3-Phase Trip
Solidly earthing
A32 1 CB, 1/3 Phase Trip
Solidly earthing
B31 2 CB:s, 3-Phase Trip
Solidly earthing
B32 2 CB:s, 1/3 Phase Trip
Solidly earthing
Configuration files are available on
connectivity package DVD
© SA-T Training
1MRG005473
Slide 6
Section 2
Isolated / High Impedance Networks (A21)
52PD
PD
*) B
A Iload
79
3ph
O->I DR
25/27
SC/VC
60
FF
50BF
3I>BF 21
Trip
59
Z<
86/94 Single-Breaker application
3U> I->O
Bus
68PSB 3 ph trip
27 Zpsb
3U< 50/51
3I> Options:
Neg Seq O/C 46I2
51N/67N General Current/Voltage
I Control Interlocking
59N
UN
60
FF
DR
© SA-T Training
1MRG005473
Slide 7
Section 2
Single Breaker (A31, A32)
52PD
PD
*) B
A Iload
79
1/3ph
O->I DR
25/27
SC/VC
60
FF
Single-Breaker application
50BF
3I>BF 21
Z<
3 ph trip
Trip
59
3U>
86/94
I->O
1/3 ph trip
Bus
68PSB
27 Zpsb
3U< 50/51 Options:
3I> Neg Seq O/C 46I2
PoleSlip 87
51N/67N
I Under/Over Power 37/32
Overexcitation 24
Under/Over/Rate of change requency 81
59N
UN
General Current/Voltage
Control Interlocking
60
FF
DR *) Only 1/3 ph trip alternative
© SA-T Training
1MRG005473
Slide 8
Section 2
Multi-Breaker alternative (B31, B32)
52PD *)
PD
Iload B
A
50BF
3I>BF
79 Σ
1/3ph
O->I 79 DR
94PD *) 1/3ph
PD O->I 25/27
SC/VC
60 50BF
FF 3I>BF
59
Multi-Breaker application
21
3U> Z< 86/94 3 ph trip
27
21PSB
I->O
1/3 ph trip
3U<
Zpsb
25/27 50/51 Options:
3I>
SC/VC Same as for A31/A32
50STUB 86/94
Multi-Breaker add-on: 60 3I> I->O
50STUB FF STUB
51/67N
3I>BF I
O->I
SC 59N
PD UN
TRIP
60
FUSE FAIL FF *) Only 1/3 ph trip alternative
© SA-T Training
1MRG005473
Slide 9
DR
Section 2
© SA-T Training
1MRG005473
Slide 10