Method Statement For Testing & Commissioning of Leak Detection System

This document outlines the method statement for the pre-commissioning and commissioning of a Leak Detection System. It details the necessary steps, tools, and checks required to ensure proper installation and functionality of the system. The procedure aims to ensure compliance with project requirements and satisfactory operation of the leak detection system.

Uploaded by

elwishahy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
113 views3 pages

Method Statement For Testing & Commissioning of Leak Detection System

This document outlines the method statement for the pre-commissioning and commissioning of a Leak Detection System. It details the necessary steps, tools, and checks required to ensure proper installation and functionality of the system. The procedure aims to ensure compliance with project requirements and satisfactory operation of the leak detection system.

Uploaded by

elwishahy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

d ati al

Sta on Gui
te We de
me
nt
ldi
ng
for
Me Method Statement For
for
Alu
We
ld
tall
ic Testing & Commissioning
mi
nu
m
Re
pai
r
Pip
e
Sta
Of Leak Detection System
Gla an inl
zin d ess
g Ins Ste The purpose of this procedure is to define the step by
Cla pe el
ddi cti Fab step method to implement the correct practices for the
ng on ric pre-commissioning & commissioning of Leak Detection
Wo Me ati System through the guidelines contained herein.
rks tho on
& d Ass Ensure that the job execution complies with the project
Ac Sta em
ces te bly requirements and serves the intended function to
sor me an satisfactory level.
ies nt d
Ere
cti
on

Popular
Categories
 Civil Method
Statements (85)
 Electrical Free PCB CAD Libraries
Method Statements
(47)
Ultra Librarian Download
 Fire Fighting
Systems (19)
 HVAC Method Tools & Equipment Required:
Statements (45) Portable Hand tools
 Occupational Step Ladder
Health and Safety Insulation Resistance Tester
(29) Continuity tester

 Oil & Gas


Systems (20) Pre-Commissioning Procedure for Leak Detection
 Plumbing
System
Method Statements Ensure that the Leak Detection system installation is
(41)
complete and mechanical completion is approved.
 Technical Guides
(35) Ensure that no damage has occurred between
mechanical completion & precommissioning.

Check for proper installation of leak detection panel &
the wiring termination to the leak detection panel.

Check the leak detection cable is properly installed &


there are no open ends.

Make sure the surface that the cable is laid is completely


clean, dry & free from dirt, oil or any conductive material
likely to come in contact with the sensing cable.

Make sure that the accurate room map which shows the
location of cable as well as key points which are
potential sources of leaks is readily available.

Check the availability of power to the leak detection


panel.

Repair / replace damaged components, if any.

Commissioning Procedure for Leak Detection System


Ensure that all the pre commissioning checks are carried
out successfully.

Set the DIP switches SW2-1 to SW2-4 for address-1 (all


off)

Set the DIP switch SW2-5 for 9600 baud.

Set the DIP switch SW2-6 for desired display units either
feet or meters.

Set the DIP switch SW2-7 for latching or non-latching


leak readings.

Set the DIP switch SW2-8 for non-map mode (twenty


seconds delay for leak alarms)

Set the DIP switch SW3-1 to SW3-3 for the 4-20 mA


range.

Set the DIP switch SW3-4 for the leak detect alarm relay 
to be supervised or non-supervised.
Set the DIP switch SW3-5 for the cable fault alarm relay
to be supervised or non-supervised.

Set the DIP switch SW3-6 for the alarm relays to be reset
from the display silence switch.

Set pot RA1 (sensitivity) for desired trip point.

Turn ON the power to the unit & observe the following:

(a) LED DS9 (power) is ON.

(b) LED DS8 (active) is flashing at 0.5 second rate.

(c) LEDs DS6 & DS7 are flashing at 0.5 second rate.

(d) The NORMAL LED is green.

Press the silence key to view the leakage current on the


cable. A clean cable will indicate zero.

Press the switch again to view the measured cable


length.

Test the cable for leak detection using a moist cloth on


the cable at several points.

Check the leak detected LED glows & the signal is


conveyed to the BMS.

Check the Leak detected LED switches OFF when the


signal is acknowledged in the panel.

Attachments
Pre Commissioning check sheet for Leak
Detection System
Commissioning check sheet for Leak
Detection System
Risk Assessment