Ferraz Shawmut Fuses Applications Transfo
Ferraz Shawmut Fuses Applications Transfo
Ferraz Shawmut Fuses Applications Transfo
AJT
L6
APPLICATION INFORMATION
TRANSFORMER PROTECTION
The National Electrical Code and the Canadian Electrical Code cover overcurrent protection of transformers. Some of the requirements in this article are summarized here.
Secondary Fuses
Selecting fuses for the secondary is simple once rated secondary current is known. Fuses are sized at 125% secondary FLA or next higher rating or at maximum 167% of secondary FLA depending on secondary current. The preferred sizing is 125% of rated secondary current Isec) or next higher fuse rating. To determine Isec, first determine transformer rating (VA or kVA), secondary voltage (Vsec) and use formulas below. 1. Single Phase : Isec = Transformer VA Vsec or Transformer kVA x 1000 Vsec 2. Three Phase : Isec = Transformer VA 1.73 x Vsec or Transformer kVA x 1000 1.73 x Vsec When Isec is determined, multiply it by 1.25 and choose that fuse rating or next higher rating. [ Isec x 1.25 = Fuse Rating ]
* If 125% does not correspond to a standard ampere rating, the next higher standard rating shall be permitted.
MAXIMUM % RATING TRANSFORMER RATED % IMPEDANCE 6 or less More than 6 & not more than 10 PRIMARY FUSE 300* 300* SECONDARY FUSE OVER 600V 250* 225* 600V or LESS 125* 125*
All
6 or less More than 6 & not more than 10
250
300 300
250 225
250 250
* Where fuse sizes doe not correspond to a standard ampere rating, the next
higher standard rating shall be permitted.
L 14
APPLICATION INFORMATION
PRIMARY FUSES FOR THREE PHASE LOW VOLTAGE TRANSFORMERS
Recommended Primary Fuses for 480 & 600 Volt, Three Phase Transformers
PRIMARY FULL LOAD AMPS 3.6 6.0 9.0 11 18 36 54 90 120 135 180 271 361 601 902 1203 1804 2406 3007 480 VOLT PRIMARY PRIMARY FUSE RATING AJT* or TRS-R A6D-R* A4BT* A4BY* 4-1/2 8 12 15 25 45 70 125 150 175 225 350 450 6 12 15 25 35 60 100 175 225 300 400 500 600 1000 1400 1800 1000 1600 2000 3000 4000 5000 PRIMARY FULL LOAD AMPS 2.9 4.8 7.2 9.0 14 29 43 72 96 108 144 217 289 481 722 962 1443 1925 2406 600 VOLT PRIMARY PRIMARY FUSE RATING AJT* or A6D-R* A4BT* A4BY* 5 10 15 17-1/2 25 45 80 150 200 225 300 450 500 700 1200 1600 2000 900 1400 1800 2500 4000 5000
TRANSFORMER RATING KVA 3 5 7-1/2 9 15 30 45 75 100 112-1/2 150 225 300 500 750 1000 1500 2000 2500
*When using these fuses, the secondary of the transformer must be fused to comply with the Code.
L 15
APPLICATION INFORMATION
E-RATED PRIMARY FUSES FOR THREE PHASE POWER TRANSFORMERS
Primary Fuse Ratings - 2400, 4160, 4800 Volts
2400V (A055) TRANSFORMER RATING KVA2 112-1/2 150 225 300 500 750 1000 1500 2000 2500 3000 3750 5000 FULL LOAD AMPERES 27 36 54 72 120 180 241 361 482 602 722 902 1203 PRIMARY FUSE RATING1 4160V (A055) FULL LOAD AMPERES MIN. 133% 16 21 31 42 69 104 139 208 278 348 416 520 694 20E 25E 40E 50E 80E 125E 150E 250E 300E 400E 450E 600E 750E 20E 30E 40E 65E 100E 150E 200E 300E 400E 500E 600E 750E 4800V (A055) FULL LOAD AMPERES 14 18 27 36 60 90 120 180 241 301 361 451 601
MIN. 30E 40E 65E 80E 125E 200E 250E 400E 600E -
MIN. 20E 20E 30E 40E 65E 100E 125E 200E 250E 350E 400E 500E 750E
133% 20E 25E 40E 50E 80E 125E 200E 250E 400E 400E 500E 600E 900E
MIN. 10E 15E 20E 25E 40E 65E 80E 125E 150E 200E -
133% 10E 15E 20E 30E 50E 80E 100E 150E 200E -
1 Minimum fuse size shown will carry transformer magnetizing inrush current of 12 times full load amperes for .1 second. 133% fuse size permits continuous operation of transformer at 133% of its self cooled KVA rating. 2 The self-cooled rating of the transformer. (If a forced-air cooled KVA rating is given, use that rating to size the fuse and be sure the fuse will carry the higher load current.)
Recommended Fuses
Ferraz Shawmut CS-3: 5KV-A055F, 8KV-A825X*, 15KV-A155F, CL-14: 5KV-A055C, A055B, 15KV-A155C
* Consult factory for technical information.
Examples: 1. A new installation has a 300KVA transformer with 4160V primary. It is not fully loaded. What is minimum size primary fuse recommended? 4160V Source A 50E rating (Ferraz Shawmut A055F1DORO-50E or equivalent) is correct. Lower ratings may open when transformer is energized.
2. What is the normal fuse size recommended for a 1000KVA transformer with 832OV primary? 8320V Source Unless special conditions are noted, the 133% primary fuse rating is correct. For this application use a 100E rating A155F2DORO-100E or equivalent which will allow normal overload operations of transformer up to 133% of rating. L 16
APPLICATION INFORMATION
E-RATED PRIMARY FUSES FOR THREE PHASE POWER TRANSFORMERS (Continued)
Primary Fuse Ratings - 12,000, 12,470, 13,200 Volts
12,000V (A155) TRANSFORMER RATING KVA2 112-1/2 150 225 300 500 750 1000 1500 2000 2500 3000 FULL LOAD AMPERES 5.4 7.0 10.8 14.4 24 36 48 72 96 120 144 PRIMARY FUSE RATING1 12,470V (A155) FULL LOAD AMPERES MIN. 133% 5.2 7.0 10.4 14 23 35 46 70 92 116 139 10E 10E 15E 15E 25E 40E 50E 80E 100E 125E 150E 10E 10E 15E 20E 30E 50E 65E 100E 125E 200E 200E 13,200V (A155) FULL LOAD AMPERES 4.9 6.6 9.8 13 22 33 44 66 88 109 131
MIN. 10E 10E 15E 20E 30E 40E 65E 80E 125E 125E 150E
133% 10E 10E 15E 20E 40E 50E 65E 100E 150E 200E 200E
MIN. 10E 10E 15E 15E 25E 40E 50E 80E 100E 125E 150E
133% 10E 10E 15E 20E 30E 50E 65E 100E 125E 150E 200E
MIN. 10E 10E 15E 15E 25E 40E 50E 80E 100E 125E 150E
133% 10E 10E 15E 20E 30E 50E 65E 100E 125E 150E 200E
MIN. 10E 10E 10E 15E 25E 40E 50E 65E 100E 125E 150E
133% 10E 10E 15E 20E 30E 40E 65E 80E 125E 150E 200E
1 Minimum fuse size shown will carry transformer magnetizing inrush current of 12 times full load amperes for .1 second. 133% fuse size permits continuous operation of transformer at 133% of its self cooled KVA rating. 2 The self-cooled rating of the transformer. (If a forced-air cooled KVA rating is given, use that rating to size the fuse and be sure the fuse will carry the higher load current.)
Recommended Fuses
Ferraz Shawmut CS-3: 5KV-A055F, 15KV-A155F, CL-14: 5KV-A055C, A055B, 15KV-A155C
L 17